Technical Data
T060D201-00 Version February 2006
a-eberle
Application
All measurement, control monitoring and regulation tasks of tap-changing transformers can be executed using the new REG-DA Tapchanger control & Transformer monitoring system (TCTMS). The REG-DA TCTMS features a world innovation as it is equipped with a high-capacity transformer monitoring function in accordance with CEI IEC 354 (VDE 0536). This function allows the operator to call up information about the hot-spot temperature and the lifetime consumption of the transformer at any time. If required, the device can even activate up to six cooling levels. The oil temperature can either be recorded directly (PT 100) or via a mA input. Apart from its basic function, every REG-DA device can be used as a measurement transducer, recorder, statistical unit, paragramer and transformer monitor all at the same time. All important network measurement quantities are displayed in measurement transducer mode. The trends in the voltage that is to be regulated over time and a second, selectable, measurement quantity are shown in recorder mode. The statistical unit for the tap-change position offers a clear presentation of all switching operations of the tap changer. The paragramer provides a complete busbar simulation. Interconnection of multiple Tapchanger control & Transformer monitoring system on a network enables the mutual exchange of data between devices over long distances.Various communications methods can be used to transfer data.This allows monitoring of multiple transformers from a centralised control centre. Parallel connection of several transfomers can be very easily implemented this way. Application-specic tasks can be implemented via freely programmable inputs and outputs. The REG-DA TCTMS is able to communicate with a control centre via all common scada protocols.
Technical Data
Description
1 6 7
REG-DA TCTMS
Various processes are available to control the transformers, and they are listed in Table 1 according to those that operate in parallel on a busbar and those that are simply freely switched in parallel. An essential factor in this context is that no additional components are required as all function units required for parallel operation are accommodated within the regulators. Case differentiation
COM 1 COM 2 COM 3
P
2 8
LCD
3
LED RAM
E-LAN RS485
ROM CLOCK
I sin (S) Transformers with different powers, different or equal tap changes Masterslave Freely switched in parallel cos Identical transformers, equal tap change Any transformers, any tap changes
Figure 1 Functions of the REG-DA TCTMS (maximum extension) 1 3x current and 2x voltage transformers 2 Analogue inputs 3 Binary inputs 4 Input for tap-changer display 5 Auxiliary voltage 6 Display and processing unit 7 Analogue outputs 8 Binary outputs 9 E-LAN connection (2 x RS485 with repeater function) 10 COM1, RS232 11 COM2, RS232 12 COM3, RS485 13 Status indication (relay)
REG-DA
a-eberle
Regulator mode
The regulator constantly compares the actual value and a xed or load-dependent setpoint value and, depending on the deviation, determines the correcting variable for the tap changer of the transformer. The regulator parameters can be optimally adjusted to the dynamic time behaviour of the network voltage, which allows for a high control quality at a low number of switching operations.
SERVICE BLOCKED
F1 F2 F3 F4 F5
AUTO
ESC
MENU
REG-DA
SERVICE BLOCKED
a-eberle
F1 F2 F3 F4 F5
Furthermore, measurement values which are transferred to the regulator as mA signals from external sources can be displayed.
Recorder mode
AUTO REMOTE LOCAL ACK ESC MENU
Parallel connection of transformers All regulators are able to control several transformers connected in parallel to one busbar without any additional devices. Every regulator constantly indicates which reactive current I sin is being used.
The change in the voltage over time and a second selectable measurement quantity are continuously shown on the display in the form of a line chart. The time grid for the recording is adjustable. The present tap position is recorded in addition to the measurement values. Therefore it is possible to review the voltage and the corresponding tap position at any time during the recording.The average recording time for voltages and tap changes is approximately six weeks. The stored values can be displayed with a time and date via the keyboard or the WinREG operating software.
Technical Data
REG-DA
SERVICE BLOCKED
REG-DA TCTMS
a-eberle
REG-DA
SERVICE BLOCKED
a-eberle
F1 F2 F3 F4 F5
F1 F2 F3 F4 F5
AUTO
ESC
MENU
AUTO
ESC
MENU
Statistics mode
In the statistics mode, all switching operations of the tap changer are registered. A differentiation is made between switching operations under load and switching operations without load.
The gure shows the two transformers T1 and T3 working on busbar a, while transformer T2 feeds off busbar b.
REG-DA
SERVICE BLOCKED
a-eberle
F1 F2 F3 F4 F5
AUTO
REMOTE LOCAL
ESC
MENU
REG-DA
SERVICE BLOCKED
a-eberle
ACK
F1 F2
Additionally, a record is kept for every single tap in tabular form. How many tap changes have been carried out during which time period and how often each tap has been selected can be checked using these data. This information can be used to optimise the regulator settings. The saved statistics values can be selected using the keyboard or loaded and printed using WinREG.
F3 F4 F5
AUTO
ESC
MENU
ParaGramer mode
The PARAGRAMER is a support tool for the automatic preparation of parallel connections and the online display of the switching statuses. The articial word PARAGRAMER is a combination of the two terms parallel and one-line diagram. The PARAGRAMER shows the switching status of the individual transformers in a one-line diagram. The function is activated by feeding each device with a complete busbar replica (position of circuit breakers, disconnectors, bus ties and bus couplings). Based on the switching states of all devices involved in the parallel connection, the system autonomously detects which transformer is to work with which other transformer(s) in parallel connection on a busbar. Busbars that are connected via bus coupling(s) are treated as one single busbar by the system.
3
The device is equipped with a mA input as standard. The temperature can be received as a mA signal by an upstream temperature measurement transducer using this input. If other combinations are required, e.g. temperature as a direct PT 100 connection and hot-spot temperature as a mA output, the desired combination can be selected from the E and C groups of characteristics.
Technical Data
REG-DA TCTMS
Temp-Trafo
REG-DA
I
SERVICE BLOCKED
U
a-eberle
F1 F2 F3
Fan 1 to fan 6
Tapchanger (TC)
F4 F5
MENU
LOCAL
ACK
Hydrocal etc.
DNP 3.0 IEC 101 IEC 103 IEC 104 IEC 61850 MODBUS SPA-BUS LON Profibus DP
Technical characteristics,
Regulations and standards
IEC 1010/ EN61010 (VDE 0411) CAN / CSA - C 22.2 No. 1010.1 - 92 VDE 0110 IEC 255 - 4 DIN 43807 EN 61326 - 1 / A1 IEC 688 - 1 IEC 529 EN 50178 / VDE 0160 / 11.94 (currently draft) VDE0106 part 100
The regulator is equipped with an analogue input as standard. The inputs can be continuously short-circuited or operated open. All inputs are galvanically isolated from all other circuits.
A. Eberle GmbH & Co. KG 4
Technical Data
Temperature input PT 100
Number Connection Current through sensor Line compensation Transmission behaviour Only one PT 100 input possible 3-conductor circuit < 8 mA No compensation required Linear
REG-DA TCTMS
Binary inputs (BI)
Inputs E1 ... E16 (... E22, ... E28) Control signals Ust 48 V...230 V in the AC/DC range
Curve shape, permissible H level L level Signal frequency Switching delay Input resistance Electrical isolation
Rectangular, sinusoidal 48 V < 10 V DC ... 60 Hz Selectable in the range 1..999 s 108 k Optocoupler; groups of 4, each galvanically isolated from each other.
Display elements
The TCTMS has 14 LEDs LED 1 : Normal operation LED 2 : Faulty operation LED 3 ... LED 10 : Freely programmable LED 11 ... LED 14 : Freely programmable Green Red Yellow Red
The outputs can be constantly short-circuited or operated open. All output connections are galvanically isolated from all other circuits.
The individual LEDs can be labelled yourself. However, if at the time of ordering you specify the labels you require, the labelling can be carried out in our factory.
Technical Data
Measurement quantities (optionally as mA value)
Voltages Current TRMS TRMS U12, U23, U31 ( 0.25 %) I1, I2 , I3 ( 0.25 %) P ( 0.5 %) Q ( 0.5 %) S ( 0.5 %) cos ( 0.5 %) ( 0.5 %) I sin ( 1 %) f ( 0.05 %) EMC requirements
REG-DA TCTMS
EN 61326-1 Device class A Continuous, non-monitored operation, in industrial applications and EN 61000-6-2 and 61000-6-4
Active power Reactive power Apparent power Power factor Phase angle Reactive current Frequency
Reference conditions
Reference temperature Input quantities Auxiliary voltage Frequency Curve shape Load (only for characteristics E91..E99) Other 23C 1 K UE = 60 ... 140 V IE = 0 ... 1A / 0 ... 5 A H = Hn 1 % 50 Hz...60 Hz Sinusoidal, form factor 1.1107 Rn = 5 V / Y2 1 % IEC 688 - Part 1
EN 61000-3-2 EN 61000-3-3
Immunity to interference EN 61326 Table A1 and EN 61000-6-2 ESD IEC 61000-4-2 8 kV / 15 kV contact / air IEC 61000-4-3 80 2000 MHz: 10 V/m IEC 61000-4-4 4kV / 2kV IEC 61000-4-5 4kV / 2kV IEC 61000-4-6 150 kHz 80 MHz: 10 V
Electromagnetic elds
Electrical safety
Protection class Degree of pollution Overvoltage category III
Input circuits of the current and voltage transformers Auxiliary voltage
I 2 II, III II
Control circuits, analogue inputs, analogue outputs COMs, E-LAN
Magnetic elds with heavy IEC 61000-4-8 electrical frequencies 100 A/m (50 Hz), continuous 1000 A/m (50 Hz), 1 s Voltage dips IEC 61000-4-11 30 % / 20 ms, 60 % / 1 s
Operating voltages 50 V
E-LAN, COM1...COM3, analogue inputs, analogue outputs, inputs 10...50 V
Interruptions to the voltage IEC 61000-4-11 100 % / 5s Damped oscillations IEC 61000-4-12, Class 3, 2.5 kV
150 V
Voltage inputs, current inputs
230 V
Auxiliary voltage, binary inputs (E1...E16), relay outputs (R1...R13), status
Test voltages
Housing / COM 1 Auxiliary voltage COM 2/3 / IEC / DNP.. Binary outputs Binary inputs (250 V) Analogue inputs Analogue outputs Input voltage Input current Hous. Uh COMs BO BI AI AO UE IE
Hous. COM 1 2.2 0.35 2.0 2.0 0.35 0.35 1.35 2.0
COM 2 COM 3 0.35 3.7 2.3 2.3 0.5 0.5 2.8 2.8
Notes: All test voltages are AC voltages in kV which may be applied for 1 minute. E-LAN, COM2, COM3 are tested against each other with 0.5 kV.
A. Eberle GmbH & Co. KG 6
Technical Data
Power supply
Characteristic AC (internal) AC DC Power input Frequency Microfuse H0 85 ... 264 V 88 ... 280 V 15 VA 50 Hz T2 250 V H2 18 ... 72 V 10 Watts T2 250 V
REG-DA TCTMS
Optical interface
The REG-DA Regulator can be equipped with a bre optic interface.(ST or FSMA connectors).Both plastic and glass bre are supported for Multimode transmission. Characteristics V13 to V19 give an overview of the various possibilities.
The following applies to all characteristics: Voltage dips at nominal voltage that last 50 ms cause neither a loss of data nor a malfunction.
Environmental requirements
Dry, cold Dry, hot Constant humid heat IEC 60068-2-1, - 15 C / 16 h IEC 60068-2-2, + 65 C / 16 h IEC 60068-2-78 + 40 C / 93 % / 2 days IEC 60068-2-30 12+12 h, 6 cycles +55 C / 93 % IEC 60068-2-31 100 mm drop, unwrapped IEC 60255-21-1, class 1
Optical transmitter
Product Type Fibre Pmin [dBm]
1)
Pmax [dBm]
1)
Toppling
POF_ST
Vibration Impact
POF_SMA
Pmax [dBm]
2)
Glass ST HFBR 2412 T 100/140 m Glass SMA HFBR 2402 NA=0.3 0 ... 5 MBd = 820 nm POF_ST HFBR 2515 B 1 mm POF 0 ... 10 MBd = 650 nm 200m HCS
-24.0
-10.0
Mechanical design
Housing Height Width Total depth Mounting depth Weight Housing doors Front plate Control panel cutout Height Width Degree of protection Rain Test Sheet steel, RAL 7035 grey 288 mm 216 mm 114 mm 87 mm 3 kg With silica glass Plastic, RAL 7035 grey on aluminium support 282 mm 210 mm IP 54 3R UL50
Technical Data
REG-DA TCTMS
REG-DA
SERVICE BLOCKED
F1 F2 F3 F4 F5
AUTO
REMOTE
ESC
MENU
281 x 209
LOCAL
307
ACK
REGSys
www.regsys.de
12 18 87 250
Mechanical dimensions
Panel
Technical Data
REG-DA TCTMS
65
127
5.5 6.5
200 270
Technical Data
General information about the connections
The TCTMS is equipped with three circuit board / connection levels.
REG-DA TCTMS
The auxiliary voltage, input voltage and currents, as well as the relay outputs, binary inputs, etc. are connected to Level I. The hardware for all the instrumentation and control connections is contained on Level II. The appropriate connection elements on Level II must be used for RS232 or RS485 connections. If an ethernet connection is used, the corresponding connection on Level II is also available (must be connected for IEC 61850 or IEC 60870-5-104!). For bre optic cable connections ST or FSMA connectors are mounted directy on the ange plate.This provides acess for cable termination without having to open the Regulator. Fibre optic cable connection (FSMA connection) Furthermore, additional binary inputs and outputs as well as mA inputs and outputs can also be accommodated on Level II. In total two spare slots are available and they can be equipped with the following modules: Module 1 : 6 binary inputs, 48 V...250 V AC/DC Module 2 : 6 relay outputs Module 3 : 2 mA inputs Module 4 : 2 mA outputs Level III contains the connections for the individual COMs, E-LAN, the analogue inputs and outputs as well as the PT 100 direct connection / resistance input for the tap-change potentiometer of the motor drive / the tap-changer.
10
Technical Data
Terminal assignment
No. Option 2 5 8 10 1 3 4 6 7 9 21 22 63 64 61 62 65 66 67 68 11 12 13 14 15 16 17 18 19 20 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 M1* M2* Triple-wound transformer* Nr. 47 48 49 50 51 52 53 54 55 56 57 58 59 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86
REG-DA TCTMS
>I >U <U Local Remote TC error ** GND Closes if fault occurs Life contact (status) opens if fault occurs MANUAL MANUAL / AUTO AUTO EE+ EAEA+ EE+ EAEA+ Tx+ TxRx+ RxTxD RxD RTS CTS GND E-LAN (L) R11 R10 R9 R8 R7 R6 R6...R11 R13
UL1 Input voltage U1 U1 Input voltage UL2 Input voltage UL3 U2 Input voltage k Current input I1 l k Current input I2 l k Current input I3 l L / (+) UH = Auxiliary voltage L / (-) mA input + A1 mA input A1 mA input or output + A2 mA input or output A2 mA input or output + A3 65 mA input or output A3 66 mA input or output + A4 mA input or output A4 68 Binary input 1 Activity lamp Binary input 2 Freely programmable Binary input 3 Freely programmable Binary input 4 Freely programmable Binary input 1...4 GND Binary input 5 AUTO Binary input 6 MANUAL Binary input 7 Freely programmable Binary input 8 Freely programmable Binary input 5...8 GND Binary input 9 BCD 1 Binary input 10 BCD 2 Binary input 11 BCD 4 Binary input 12 BCD 8 Binary input 9...12 GND Binary input 13 BCD 10 Binary input 14 BCD 20 Binary input 15 BCD sgn. Binary input 16 Freely programmable Binary input 13...16 GND
Freely programmable R5 Freely programmable R4 Freely programmable R3
Level I
Level I
R12
Level III
E-LAN (R)
Level III
See Level II pin assignment for additional Level II connections (page 13)
Level I
Option M1 Used for standard applications, balanced load ( I1 = I2 = I3 ). Option M2 Only used for unbalanced load ( I1 I2 I3 ). Two different voltage inputs for U1 and U2 are required for triple-wound transformer applications.
**
TC = tap changer
Lower
R2
*** Please refer to the instrumentation and control connections listed in the operating manual.
11
Technical Data
REG-DA TCTMS
Location of the connection terminals, Characteristics D0, D1, D4
REG-DA
SERVICE BLOCKED
a-eberle
F1
F2 F3 F4 F5
AUTO
REMOTE
ESC
MENU
LOCAL ACK
1
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 81 83 84 85 86
87 88 89 90
91 92 93 94
9 10
11 12 13 14 15 16 17 18 19 20
23 24 25 26 27 28 29 30 31 32 21 22
33 34 35 36 37 38 39 40 41 42 43 44 45 46
47 48 49 50 51 52 53 54 55 56 57 58 59 60
a-eberle
F1
F2 F3 F4 F5
AUTO
REMOTE
ESC
MENU
LOCAL ACK
1
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 81 83 84 85 86
87 88 89 90
91 92 93 94
9 10
11 12 13 14 15 16 17 18 19 20
23 24 25 26 21 22
ON 1 2
33 34 35 36 37 38 39 40 41 42 43 44 45 46
47 48 49 50 51 52 53 54 55 56 57 58 59 60
12
Technical Data
Level II pin assignment
Characteristics C01 ... C09 Characteristic C01 6 additional binary inputs, 48 V ... 250 V AC/DC No. 100 101 102 103 104 105 106 Binary input Binary input Binary input Binary input Binary input Binary input GND E17 E18 E19 E20 E21 E22 E17 ... E22 Module 1
REG-DA TCTMS
Characteristic C05 6 additional binary inputs, 48 V ... 250 V AC/DC and 6 relay outputs (NO contact) No. 100 101 102 103 104 105 106 107 108 109 110 111 112 113 Binary input Binary input Binary input Binary input Binary input Binary input GND E17 E18 E19 E20 E21 E22 E17 ... E22 R14 R15 R16 R17 R18 R19 GND R14...R19
Module 1
Characteristic C02 12 additional binary inputs, 48 V ... 250 V AC/DC No. 100 101 102 103 104 105 106 107 108 109 110 111 112 113 Binary input Binary input Binary input Binary input Binary input Binary input GND Binary input Binary input Binary input Binary input Binary input Binary input GND E17 E18 E19 E20 E21 E22 E17 ... E22 E23 E24 E25 E26 E27 E28 E23 ... E28
Module 1
Characteristic C06 2 additional analogue inputs No. 100 101 102 103 + + Module 3
Module 2
E10 E11
Module 1
Characteristic C07 4 additional analogue inputs No. 100 101 102 103 104 105 106 107 + + + + Module 3
Characteristic C03 6 additional relay outputs (NO contact) No. 100 101 102 103 104 105 106 R14 R15 R16 R17 R18 R19 GND R14 ... R19
Modue 2
Characteristic C08 2 additional analogue outputs No. 100 101 102 103 + + Module 4
Characteristic C04 12 additional relay outputs (NO contact) No. 100 101 102 103 104 105 106 107 108 109 110 111 112 113 R14 R15 R16 R17 R18 R19 GND R14 ... R19 R20 R21 R22 R23 R24 R25 GND R20 ... R25
13
Module 3
A10 A11
Module 2
Characteristic C09 4 additional analogue outputs No. 100 101 102 103 104 105 106 107 + + + + Module 4
Module 2
Module 4
Level
RXD
RTS
TXD
CTS
GND
GND
Rx Tx -
Rx + Tx +
E-
E+
EA E-
EA + E+
EA -
EA +
Technical Data
I2
P
display CLOCK RAM/ROM
Level
Characteristicl E 91...99
A2 + 100
A3 + -
A4 + -
TC in op.
progr.
progr.
progr.
AUTO
MANUAL
progr.
progr.
mA input
mA input
Input or output
Input or output -
Input or output +
Input or output -
Input or output +
Input or output -
E1
E2
E3
E4
GND E1...E4
E5
E6
E7
E8
GND E5...E8
E9
BCD 1
E10 BCD 2
E11 BCD 4
E12 BCD 8
GND E9...E12
E13 BCD 10
E14 BCD 20
E16 progr.
REG-DA TCTMS
Level
GND E13...E16
optional
Legend:
Level 23 24 25 26 27 28 29 30 31 32
Terminal no. 63 64 61 62 65 66 67 68
113
11 12 13 14 15 16 17 18 19 20
33 34 35 36 37 38 39 40 41 42 43 44 45 46
*) The double module can either be a double-mA input or a double-mA output module. If direct temperature detection is required, the space is occupied by a PT 100 module.
85 84 86 83 82 81 80 79 78 77 69 70 71 72 73 74 75 76 COM 2 RS232 COM 3 RS485 E-LAN L E-LAN R Opens R13 Life contact
(Status)
I3
52 51 50 49 48 47 53 57 58 59 54 55 56
COM 1
RS232
1 2 3 4 5
6 7 8 9
Closes AUTO MANUAL GND R6...R11 R11 R9 >I R10 >U <U R8 Local R7 Remote R6 TC fault R12 MANUAL / AUTO
U1
Characteristic M2
U2
10
Keyboard
I1
Characteristic M2
LCD LED
14
Inputs E1 ... E8 50...230 V AC/DC
R1
Raise
L / (+)
21
UH
R2
Lower
L / (-)
22
Double modulel
Technical Data
Network / parallel connection
The networking of several TCTMS is particularly required with transformers connected in parallel. The I sin, I sin (S) and Master-Slave parallel connection programs can only be implemented by the system bus (E-LAN). This enables the individual group members of a parallel connection to communicate with each other and without the need for additional components. The devices do not need to be connected for the operation of a parallel connection which works in accordance with the cos procedure. Due to the large distances, such connection is not normally possible anyway.
REG-DA TCTMS
RS485 interfaces TCTMS Every REG-DA TCTMS is provided with a double E-LAN interface as a standard. It provides the bus connection of individual monitoring units to a form total integrated system. E-LAN (Energy- Local Area Network) Characteristics 255 stations can be addressed Multimaster structure Integrated repeater function Open ring, bus or a combination of ring and bus is possible The record is based on SDLC/HDLC framework Transfer rate 62.5 or 125 kbit / sec Telegram length 15.6 ... 375 kbit / s Average throughput approx. 100 telegrams / sec at 62.5 k COM3 For connection of 15 interface modules (BIN-D, ANA-D) in any combination to any REG-DA regulator.
Serial interfaces
RS232 interfaces The REG-DA has two RS232 interfaces (COM1, COM2). COM 1 interface is used for conguring the regulator and COM 2 is the scada interface designed to connect the TCTMS to a higher-level instrumentation and control device. Connection elements COM1
COM2
Sub Min D in the terminal compartment, pin assignment as with PC Pin connection in the terminal compartment. PC, terminal, modem, PLC Parity 8, even, off, odd 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 RTS / CTS or XON / XOFF
HANDSHAKE
REGSys - Overview
bl e tic ca
E-LAN
WinREG
Windows 95 Windows 98 Windows NT Windows 2000 Windows XP
Et he rn et R S2 32
R S4 85
Fi br e
op
EOR-D
a . e b er le gmbh
EOR-D
a. e be r le gmbh
EOR-D
a. e be r le gmbh
EOR -D
a. e be r le gmbh
St atus 1 2 3 4 Reset
Stat us 1 2 3 4 Reset
Stat us 1 2 3 4 Reset
Stat us 1 2 3 4 Reset
C OM1
COM1
COM1
COM1
EOR-D
E-LAN E-LAN
COM3
RS485
gmbh a. eberle
a. eberle gmbh
P QI- D
Status 1 2 3 4 Reset
C O M1
BIN-D E-LAN
ANA-D
REG-BO
REG-DA
RS485
PAN - D
a. eberle
gmbh
REG - D
a. eberle gmbh
MMU-D
gmbh a. eberle
a. eb e rle gmbh
REG - DE
Stat us
M A: REG -D E Re geln Ipos = 98 .0 A Uo = 0.85 %
Uo 10
a. eber le
gm bh
Strung
Regler
Lauflampe Rckfhrung
luft
F1 F2 F3 F4 F5
Status 1 2 3 4 Reset
Strung
Stufenschalter
Auslsung
Leitungsschalter
F3
1
F4
0.1
F5
20A I m in I max 200A
AUTO
Test
COM1
AUTO
ESC
MENU
COM1
C O M1
AU TO
ESC
MENU
C OM1
<
ANA-D
REG-PC REG-BO
PAN-D
REG-D
MMU-D
REG-ST
REG-DP
COM1
RS232
RS232
BCD-CODE
ANA-D
ANA-D
REG-S
REG-F(X)
15
E-
LA
km
PQI-D
ANA-D
ANA-D
Technical Data
WinREG parameterisation and conguration software
WinReg was designed for the set up and programming of the REG-DA. WinREG can be operated in three different modes. In the Panel mode, up to six devices can be simultaneously displayed and operated via the mouse. All settings which can be directly entered via the devices membrane keypad can be carried out centrally with WinREG, provided that all devices are connected to each other via E-LAN. This operating mode provides a considerably simplied and more transparent operation, particularly when the transformers are operated in parallel. If WinREG is used to change all the TCTMS on the transformers that are operating in parallel into the measurement transformer mode, all the circulating reactive currents of the transformers can be displayed on a PC monitor in real time. The Parameter mode allows for easy setup.Individual settings can be entered, stored for future use or transferred to a station using the clearly structured tab format. The Terminal-Mode provides the possibility of direct communication with the system. Therefore, WinREG terminal is far easier to use than traditional terminal programs and considerably simplies the system programming. WinREG runs under Windows 95, 98, Windows 2000, NT or Windows XP and is also available in a modem enabled version for remote access.
REG-DA TCTMS
Recorder mode
YT time grid 14 sec/div, 1 min/div, 5 min/div,10 min/div,
All measured values are stored in seconds, independent of the selected YT time grid (feed speed). The value every second represents the arithmetic average of the previous 10 measurement values generated in intervals of 100 ms.
Overwriting; FIFO overwriting (First In First Out) > 18.7 days worst case On average > 1 month
Analogue output
Parameterisation
REG-DA parameters (selection) Parameters
Permissible regulative deviation Time factor 1st setpoint value 2nd setpoint value 3rd setpoint value 4th setpoint value Time behaviour
Setting range
0.1 ... 10% 0.1 ... 30 60.0 ... 140.0 V 60.0 ... 140.0 V 60.0 ... 140.0 V 60.0 ... 140.0 V U t = const REG 5A/E LINEAR CONST Apparent current Active current Reactive current LDC 0 ... 40 % 0 ... 40 % R : 0 ... 30 X : 0 ... 30 -25 % ... +10 % 0 ... 25 % 0 ... 210 % (1A / 5A) 60 V ... 160 V 0 ... -35 % 0 ... 35 % -75 % ... 0 % 1 ... 999 s
(high-speed forward switching 2...999 s)
Current inuence Apparent current / active current Gradient Limitation LDC (Line-Drop Compensation) Undervoltage <U Overvoltage >U Overcurrent >I Tripping High-speed forward switching High-speed backward switching Standstill Switching delay for <U, >U, <I, tripping, high-speed switching The standstill can be set separately
A. Eberle GmbH & Co. KG
16
Technical Data
Order details
Only one code may be selected from codes with identical capital letters. If the digit 9 follows the capital letter in the code, additional information in text form is required. If only zeroes follow the capital letter in the code, they can be omitted from the code.
REG-DA TCTMS
X characteristics e.g. XE91 cannot be freely combined with all other characteristics. Please note the extra information in the text. CHARACTERISTIC
REG-DA Tapchanger control & Transformer monitoring system Standard version, with double E-LAN interface, COM 2, COM 3 and a mA input channel e.g. to measure oil temperature or to measure tap-change position via resistance measurement transformer, with 16 binary inputs and 12 relay outputs plus status output Includes WinREG software to congure, program and display all regulator data. Includes connection cable. Note: Com 2 when no Scada connection is required. Design: Power supply: Input currents (can be altered later) Panel-mounting or wall-mounting version (H x W x D) 307 x 250 x 102 mm with standard mounting rail adapter External 85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 V DC External 18 V ... 60 V ... 72 V DC IEN 1 A IEN 5 A REG-DA
CODE
B0 B1 H0 H2 F1 F2 M1 M2 M3 M9 S0 S1 T0 T1 K0 K1 E00 E91 E92 E93 E94 E95 E96 E97 E98 E99
Measurement transducer display functions for network quantities Three-conductor three-phase current with balanced load Three-conductor three-phase unbalanced loads Voltage measurement (upper voltage), current and voltage measurement (lower voltage) and other applications of the three current transformers and the two voltage transformers Recorder functions for network quantities with evaluation software Transformer monitoring Parallel operation Additional analogue inputs and outputs without with one PT 100 input with two mA inputs with two mA outputs with one PT 100 input and one mA output with two mA inputs and one mA output with three mA outputs Tap-change potentiometer input, total resistance 200 Ohm ... 2 kOhm Tap-change potentiometer input, total resistance >2 kOhm ... 20 kOhm other combinations of inputs and outputs Note for XE91...XE99: If known, please specify the scale! E.g.: 1 E.g.: 3 -100 ... 0 ... +100 MW -20 ... 0 ... +20 mA 1 ... 19 taps 0 ... 20 mA E.g.: 2 E.g.:4 0 ... 80 ... 120 V 4 ... 16 ... 20 mA 50 ... 140C 4 ... 20 mA without with without with without rmware for parallel operation with rmware for parallel operation
Binary inputs and tap-change potentiometer input 16 binary inputs, 48...250 V AC/DC 8 binary inputs, 10..48 V AC/DC and 8 binary inputs, 48...250 V AC/DC 1 tap-change potentiometer input (total resistance 200...2 kOhm) and 8 binary inputs, 48. .250 V AC/DC 1 tap-change potentiometer input (total resistance >2...20 kOhm) and 8 binary inputs 10 ..48 V AC/DC 16 binary inputs 10 ..48 V AC/DC D0 D1 D2 D3 D4
17
Technical Data
Characteristics continued Characteristic REG-DA
Level II: additional inputs and outputs without with 6 binary inputs 48 V...250 V AC/DC with 12 binary inputs 48 V...250 V AC/DC with 6 relay outputs with 12 relay outputs with 6 binary inputs and 6 relay outputs with 2 analogue inputs with 4 analogue inputs with 2 analogue outputs with 4 analogue outputs other combinations of 6 inputs, 6 outputs, 2 analogue inputs, 2 analogue outputs Note about C90: Two slots are normally available on Level II. Each terminal can be equipped with either 6 binary inputs, 6 binary outputs or an analogue module. Each analogue module has either 2 inputs or 2 outputs. The regulator can be equipped with 4 additional modules if no instrumentation and control connections (XW90, 91 or L1, L9) are used. Integrated instrumentation and control connections according to IEC61850 or IEC 60870- 5-104 without IEC 60850 - 5 - 104 (extended with group of characteristics G) Note: please enter target system if to be connected according to IEC 60850-5-104 IEC 61850 (extended with group of characteristics G) Integrated instrumentation and control connections according to IEC 60870- 5-101/ ..-103, DNP without (extended with group of characteristics G) for the instrumentation and control connection of a REG-DA or the instrumentation and control connection of multiple systems (REG-D/DA/DP, etc.) Note: L9 can only be combined with characteristics XW90, Z15 to Z19 and Z91. Type of connection: Copper RS 232 RS 485, 2-wire operation only V10 V11 V13 V15 V17 V19 Z10 Z11 Z12 Z13 Z14 Z90 Z15 Z17 Z18 Z19 Z91 Z20 Z21 Z22 Z23 XW00 XW90 XW91 L0 L1 L9 C00 C01 C02 C03 C04 C05 C06 C07 C08 C09 C90
REG-DA TCTMS
CODE
Fibre optic cable with FSMA connection Glass bre (wavelength 800...900 nm, range 2000 m) plastic (wavelength 620...680 nm, range 50 m) Fibre optic cable with ST connection Glass bre (wavelength 800...900 nm, range 2000 m) plastic (wavelength 620...680 nm, range 50 m) Protokoll: IEC60870-5-103 for ABB IEC60870-5-103 for Areva IEC60870-5-103 for SAT IEC60870-5-103 f0r Siemens (LSA/SAS) IEC60870-5-103 f0r Sprecher Automation IEC60870-5-103 for other IEC60870-5-101 for ABB IEC60870-5-101 for IDS IEC60870-5-101 for SAT IEC60870-5-101 for Siemens (LSA/SAS) IEC60870-5-101 for other DNP 3.00 LONMark SPABUS MODBUS RTU A. Eberle GmbH & Co. KG 18
Technical Data
Continuation of characteristics CHARACTERISTIC REG-DA
Operating manual German English French Spanish Italian Russian Other German English French Spanish Italian Russian Other G1 G2 G3 G4 G5 G6 G9 A1 A2 A3 A4 A5 A6 A9
REG-DA TCTMS
CODE
Display language
Additions to REG-DA
Probus-DP interface module can be installed on standard mounting rails, without power supply for ext. Uh 24 V DC Dimensions: (120 x 75 x 27) mm incl. RS 485 interface and connection cable 10MB/s TCP/IP adapter can be installed on standard mounting rails with power supply for Uh 230 V AC as 8TE plug-in module, 3HE with power supply: 85 V...110 V...264 V AC / 88 V...220 V...280 V DC as 8TE plug-in module, 3HE with power supply: 18 V...60 V...72 V DC 100MB/s TCP/IP adapter Fibre optic cable module with ST connection (glass or plastic) with FSMA connection (glass or plastic) Probus DP
CODE
CODE
19
Technical Data
Accessories
Cable for PC connection (null modem cable) Cable for modem connection 1 pack of T2 L 250 V microfuses Fibre optic cable coupler DCF 77 radio clock Modem for REG-Dx/EOR-D/PQI-D/MMU-D (standard version Uh: 230 V AC) Modem for industrial applications Uh: 230 V AC Analogue input module (2 inputs) Analogue output module (2 outputs) Analogue input module (1 input) Analogue output module (1 output) Input module for tap-change potentiometer total resistance 200 Ohm...2 kOhm Input module for tap-change potentiometer total resistance >2 kOhm...20 kOhm Additional input module for PT 100 according to DIN 43760 in 3-conductor circuit. E- LAN Y-connection with booster E- LAN PC adapter with booster E- LAN PC adapter Y-connection with booster E- LAN booster (wide-range network) REG-DA operating manual G1...G8 (please specify language)
REG-DA TCTMS
Ident. No.
582.020 8 582.2040 582.1019 111.9030.10 111.9024 111.9030.02 111.9030 320.0004 320.0003 356.2009.00 320.0007 320.0002 320.0002.1 320.0005 REG-ST REG-PC REG-ST3 REG-B0 Gx