PHASE FAILURE RELAYS

These relays are suitable for monitoring incoming 3-phase supply from Mains (Electricity distribution line). Being independent of load, they can be used for any HP/KW rating of load.

MODELS VSP D1, VSP D2, P1 PFS1, P1 PFS2, S2 VMR1, S2 VMR2, S2 VMR3, D1 HLS1, HLV D2, ALV D2, VST D1, D1 VMR1, D2 VMR1, D2 VMR2, S1 VMR1, S1 VMR3
FEATURES

Fixed/adjustable unbalance settings Fixed/adjustable undervoltage/over-voltage settings Fixed/adjustable trip delays Built-in or external power supply Resetting Auto or Manual Output contacts : 1 CO or 2 CO Choice of enclosures (DIN-Rail, Plug-in, Flush) Models with Micro-Controller based design Use of SMD Technology User-friendly LED indications

PROTECTIONS / FUNCTIONS
Phase Failure (Phase Loss / Single Phasing), Phase sequence reversal, Voltage Unbalance, Under Voltage, Over Voltage

Ordering Instructions
Family Name Product Model Name Supply Voltage System & Frequency Aux. Supply / Control supply voltage
09

P H A S E F A I L U R E R E L A Y S
VSP D1
Phase Failure Relay

VSP D2
Phase Failure Relay

P1 PFS1
Phase Sequence Relay

Phase Failure, Unbalance, Phase Sequence, Auto Reset, Fixed Unbalance Setting, 1 CO output Relay

Phase Failure, Unbalance, Phase Sequence, Auto / Manual / Remote Reset, Adjustable Unbalance setting, 2 CO output relay

Phase Sequence, Phase Loss Auto Reset, 1 CO output relay

Supply Voltage System Auxiliary Output Contacts Trip Setting (Volts) Phase Sequence Phase Unbalance Trip Time Delay On Phase Failure/Unbalance Resetting Mode Weight Dimensions (mm) Overall (L x W x D) Mounting (L x W)

100-120/220-240/380-440 V AC 20% 50 / 60 Hz 100-120/220-240/380-440 V AC 20% 1 CO Yes 40 V 6 V (fixed)

100-120/220-240/380-440 V AC 20% 50 / 60 Hz 100-120/220-240/380-440V AC 20% 2 CO Yes 30 V to 70 V 6 V (adjustable)

110 / 240 / 380 / 415 V AC 10%, 50 / 60 Hz Built-in 1 CO (Pick-up on correct phase sequence) Yes N.A.

3.5 sec. 1.5 sec. Auto 320 gms. 76 x 30.5 x 117.5 68 centre to centre / 35 mm rail Mounting

3.5 sec. 1.5 sec. Auto / Manual / Remote 400 gms. 76 x 56.5 x 117.5 67 x 46 / 35 mm rail Mounting

N.A. Auto 175 gms. 50 x40 x 80 8 - Pin Plug-in

Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) * Available on request.

Aux Supply
RYB R B Y R B R Y B

Aux Supply
RYB R B Y R B R Y B
Phase Fail

RYB

R B Y

R Y B

3 Ph

3 Ph

3 Ph
17 14

Phase Fail

7
Td : 2-5 Sec.

16

13

13

14

Td : 2-5 Sec.

1
18

13

15

16

13

15

R Y B

L1 L2 L3

R Y B

L1 L2 L3

OFF

Y B

OFF

N/V

ON
N/V

ON

DOL STARTER

DOL STARTER

1 2 3 4 5 6
1 2 3

VSP D2

VSP D1

4
AUX. SUPPLY

5 6 7

AUX. SUPPLY 7 8 9

3
7 8 9 10 11 12

2 1 8
Bottom view

13 14 15

13 14 15 16 17 18

Relay contact position shown in 'Power on' (Healthy) condition


10

P H A S E F A I L U R E R E L A Y S
P1 PFS2
Phase Failure Relay

P2 PFS1
Phase Failure Relay

S2 VMR1
Phase Failure Relay

S1 VMR1
Phase Failure Relay

US

US

DISCONTINUED

Phase Failure, Unbalance, Phase Sequence, Auto/Reset, fixed unbalance setting, 1 CO output relay

Phase Failure, Unbalance, Phase Sequence Auto/Reset, Adjustable Unbalance setting, 2 CO output relay

Microcontroller design, SMD Technology Phase Failure, Unbalance, Phase Sequence Auto/Manual Reset, Adjustable Unbalance setting, 2 CO output relay
100-120 / 220-240 / 380-440V AC 20%, 48-63 Hz Built In 2 CO Yes 4 % TO 20 % (Variable) 5% of full scale.

Phase Failure, Unbalance, Phase sequence, Auto Reset, fixed unbalance setting, 1 CO output relay

110 / 240 / 380 / 415 V AC 10%, 50 / 60 Hz Built-in 1 CO Yes 40V 6V (fixed)

110/240/380/415 V AC 10%, 50/60Hz Built-in 2 CO Yes 30 V to 70 V 6V (adjustable)

100-120 / 220-240 / 380-440V AC 20%, 3PH-3 Wire, 48-63 Hz Built In 1 CO Yes 10% (Fixed) 2%

3.5 sec. 1.5 sec. Auto 175 gms. 50 x40 x 80 8 - Pin Plug-in

1 - 5 secs. (variable) Auto 250 gms. 80 x 35 x 95 11 - Pin Plug-in

4 Sec 1 Sec / RP-Instant Auto/ Manual Reset (Selectable by Front Push Button) 100 gms (Approx.) 90 X 35 X 60 35 mm Rail Mounting

4 Sec 1 Sec (Fixed) Auto Reset 90 gms (Approx.) 89 X 17.5 X 59 35 mm Rail Mounting

RYB

R B Y

R B

R Y B

3 Ph
1 3

Phase Fail /Reverse

RYB

R B Y

R B

R Y B

RYB

R Y

R B Y

Td : 2-5 Sec.
1 3

3 Ph
11 9

Unbalance >30 - 70V set value or Reverse phase

3 Ph
Td : 3-5 Sec.

Aux Supply
RYB 3 Ph
Td : 2-5 Sec.

RB
Phase Fail

RYB

Td : 2 to 5 Sec.

10

11

Unbalance >4 - 20 %

11

10

12

R Y B

Y B

R Y B

R Y B

N/V

OFF ON

S1 VMR1

4 3 2 1

5 6 7 8
4 3 2

6 7 8 9
10

5 6

11

Bottom view

Bottom view

Relay contact position shown in 'Power on' (Healthy) condition

Relay position shown in 'Power off' condition


11

P H A S E F A I L U R E R E L A Y S
S2 VMR2
Phase Failure Relay

HLV D2
Phase Failure with UV / OV Relay

ALV D2
Phase Failure with UV / OV Relay

US

Microcontroller design, SMD Technology, Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage Auto reset, Fixed Unbalance setting, Fixed UV/OV settings, 2 CO output relay

Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage Manual reset, Fixed Unbalance setting, Adjustable UV/OV settings, 2 CO output relay

Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage Auto Reset, Fixed Unbalance setting, Adjustable UV/OV settings, 2 CO output relay

Supply Voltage System Auxiliary Output Contacts Trip Setting (Volts) Phase Sequence Phase Unbalance Under For 380-440V AC Voltage For 220-240V AC For 100-120V AC For 380-440V AC Over Voltage For 220-240V AC For 100-120V AC Trip Time Delay On Phase Failure On UV/OV Resetting Mode Weight Dimensions (mm) Overall (L x W x D) Mounting (L x W)

100-110-120 / 220-230-240 / 380-415-440V AC 20%, 48-63 Hz, Selectable by Front Knob Built In (from 3 Phase) 2 CO Yes 10% (Fixed) 10%

110 / 240 / 380 / 415 / 440 V AC 20% 50 / 60 Hz 110 / 240 / 380 / 415 / 440 V AC 20% 50 / 60 Hz 110 V (Fixed) or (220 - 230 - 240) or (380 - 415 - 440) V AC 20% selectable 2 CO 2 CO Yes 40 V 6 V (fixed) 80% to 95% (adjustable) Yes 40 V 6 V (fixed) 80% to 95% (adjustable)

20% (Fixed)

105% to 120% (adjustable)

105% to 120% (adjustable)

2 - 5 Sec. (Fixed) / RP-Instant Auto Reset 100 gms (Approx.) 90 X 35 X 60 35 mm Rail Mounting

3.5 secs. 1.5 sec


Less than 2 secs. for OV & 2 - 5 secs for UV

3.5 secs. 1.5 sec Less than 2 secs. Auto Reset 400 gms. 76x 56.5 x 117.5 67 x 46 / 35 mm rail Mounting

Manual / Remote 430 gms. 76 x 56.5 x 117.5 67 x 46 / 35 mm rail Mounting

Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) * CE marked products available on request.

RYB

RY
Unbalance / Phase fail

R B Y
UV Td : 2-5 Sec.

OV

3 Ph
7 8 10 11

Aux Supply

UV
RYB R B
Unbal./ Phase Fail

OV
Aux Supply
RYB R B
Unbal./ Phase Fail

UV
RBY RYB

OV

RBY

RYB

Td : 2-5 Sec.

3 Ph
13 14 16 17

3 Ph
13 14 16 17

Td : 2-5 Sec.

Td : 2-5 Sec.

10

12

13

15 16

18

13

15 16

18

R Y B

R Y B

L1 L2 L3

L1 L2 L3

MOTOR

Y B

MOTOR

N/V

OFF

ON

N/V

OFF

ON

DOL STARTER

DOL STARTER

1 2 3 4 5 6

ALV D2
1 2 3 4 5 6

HLV D2
AUX. SUPPLY 7 8 9 10 11 12

AUX. SUPPLY 7 8 9 10 11 12

13 14 1516 17 18 13 14 1516 17 18

Relay contact position shown in Power off' condition


12

Relay contact position shown in Power on' (Healthy) condition

P H A S E F A I L U R E R E L A Y S
D1 HL S1
Phase Failure with UV / OV Relay

VST D1
Phase Failure with Under Voltage

S1 VMR3
Phase Failure with UV / OV Relay

D1 VMR1
Phase Failure with UV / OV Relay

New

US

Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage Auto reset, Fixed Unbalance setting, Fixed UV/OV settings, 2 CO output relay

Phase Failure, Phase Sequence, under voltage, Auto Reset, Adjustable trip delay, Adjustable UV setting, 1 CO output relay Selectable range of supply voltage

Phase Failure, Unbalance, Phase sequence, Under & Over voltage, Auto Reset, fixed unbalance and UV/OV setting, 1 CO output relay

Phase Failure, Unbalance, Phase sequence, Under & Over voltage, Auto Reset, fixed unbalance setting, Adjustable UV/OV settings, fixed trip delay, 2 CO output relay

100-110-120/220-230-240/380-415-440V AC20%, 48-63 Hz, Selectable by Front Knob Built-in 2 CO Yes 10% (Fixed) 75% of system supply (Fixed)

240 / 415 / 575 V AC 3 Phase (15% selectable) Built-in 1 CO Yes N.A. 80% of V set

100-110-120 / 220-230-240 / 380-415-440 V AC 20%

Built-in ( from 3 Phase ) 1 CO Yes 10% (fixed) 2% of set Value 80% (Fixed) 2% of set Value

100-120/220-240/380-440 VAC20%, 3Ph-3Wire Built-in 2 CO Yes 10% (fixed) 285-425V AC [Variable] 165-225V AC [Variable] 75-115V AC [Variable] 400-520V AC [Variable] 230-290V AC [Variable] 105-140V AC [Variable] 3.5 secs 1.5 sec. 3.5 secs 1.5 sec. Auto 430 gms. 76 x 30.5 x 117.5 68 centre to centre / 35 mm rail Mounting

120% of system supply (Fixed)

N.A.

120% (Fixed) 2% of set Value

3.51.5 secs. [Fixed] Less than 2 secs. Auto 200 gms. 76 x 30.5 x 117.5 68 centre to centre / 35 mm rail Mounting

0.2 - 10 secs. (variable) 0.2 - 10 secs. (same for UV & SP) Auto 300 gms. 76 x 30.5 x 117.5 68 centre to centre / 35 mm rail Mounting

5 secs. 1 sec (Fixed) UV-5 secs. 1 sec (Fixed), OV-Less than 1 secs. Auto 100 gms. (Approx.) 89 x 17.5 x 59 (Approx.) 35 mm rail Mounting

Aux Supply

UV
RYB R B
Unbal./ Phase Fail

OV
3 Ph

RYB

RY
Phase fail

R B Y
UV

RYB R B

R B Y RP UV

OV
RYB RY
Unbalance / Phase fail Td : 3.5 Sec.

RBY

RYB
13 14

Td :0.2-10 Sec.

3 Ph 4 5 6

R B Y
UV

OV

UB/ SP

3 Ph

3 Ph
13 14

Td : 2-5 Sec.

T1

T2

T3
13 14 1 2

13

15

13

15

4
L1 L2 L3

13

15

L O A D

R Y B

MOTOR

R Y B

L O A D

N/V

OFF

ON

DOL STARTER
1 2 3

N/V

OFF ON

DOL STARTER

VST D1

S1 VMR3

D1 HLS1

9
4 5 6

13 14 15

Relay contact position shown in 'Power off' condition

Relay contact position shown in 'Power on' (Healthy) condition

Relay contact position shown in 'Power off' condition

13

P H A S E F A I L U R E R E L A Y S
D2 VMR 1
Phase Failure with UV / OV (3-3W)

D2 VMR 2
Phase Failure with UV / OV (3-4W)

S2 VMR 3
Phase Failure with UV / OV Relay

US

US

US

Suitable for 3 Ph-3W system, Microcontroller design, Absolute values of UV/OV settings, Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage, Auto/Manual reset, Adjustable settings for Unbalance, UV/OV and trip delays, 2 CO output relay

Suitable for 3 Ph-4W system, Microcontroller design, Absolute values of UV/OV settings Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage Auto/Manual reset, Adjustable settings for Unbalance, UV/OV and trip delays, 2 CO output relay

Microcontroller design, SMD Technology, Absolute values of UV/OV settings, Phase Failure, Unbalance, Phase Sequence, under voltage, Over Voltage Auto/Manual reset, Adjustable settings for Unbalance, UV/OV and trip delays, 2 CO output relay

Supply Voltage System Auxiliary Output Contacts Trip Setting (Volts) Phase Sequence Phase Unbalance Under Voltage For 380-440V AC For 220-240V AC For 100-120V AC For 380-440V AC For 220-240V AC For 100-120V AC

100-120 / 220-240 / 380-440V AC 20%, 48-63 Hz Built In (from 3 Phases) 2 CO YES 4 % - 20 % [Variable] 285-425V AC [Variable] 165-225V AC [Variable] 75-115V AC [Variable] 400-520V AC [Variable] 230-290V AC [Variable] 105-140V AC [Variable] Instant 1 To 10 Sec [Variable) Auto/ Manual Reset (For NC Push Buttons) 300 gms. 76 X 56.5 X 117.5 67 x 46 / 35 mm rail Mounting

100-120 / 220-240 / 380-440V AC 20%, 48-63 Hz Built In (from 3 Phases) 2 CO YES 4 % - 20 % [Variable] 165 - 245V AC [Variable] 95 -135V AC [Variable] 45 - 65V AC [Variable] 230-310V AC [Variable] 130-170V AC [Variable] 60-80V AC [Variable] Instant 1 To 10 Sec [Variable) Auto/ External Manual Reset (For NC Push Buttons) 300 gms. 76 X 56.5 X 117.5 67 x 46 / 35 mm rail Mounting

100-120 / 220-240 / 380-440V AC 20%, 48-63 Hz Built In (from 3 Phases) 2 CO YES 4 % - 20 % [Variable] 285-425V AC [Variable] 165-225V AC [Variable] 75-115V AC [Variable] 400-520V AC [Variable] 230-290V AC [Variable] 105-145V AC [Variable]

Over Voltage

Trip Time Delay On Phase Sequence On SP/UV/OV Resetting Mode Weight Dimensions (mm) Overall (L x W x D) Mounting (L x W)

Instant 1 To 10 Sec [Variable) Auto/ Manual Reset [Selectable] 110 gms (Approx.) 90 X 35 X 60 35 mm Rail Mounting

Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)


13 14

RYB
RYB RY
Unbalance / Phase fail Td : 1-10 Sec. Td : 1-10 Sec.

RY
Unbalance / Phase fail

R B Y
UV

OV

RYB

RY
Unbalance / Phase fail

R B Y
UV

OV

R B Y
UV

OV

3 Ph
16 17

3 Ph N
13 14 16 17

3 Ph
7 8 10 11

Td : 1-10 Sec. Td : 1-10 Sec.

Td : 1-10 Sec. Td : 1-10 Sec.

13

15

16

18

13

15

16

18

10

12

R Y B

L O A D

R Y B N

L O A D

R Y B

MANUAL RESET PB

MANUAL RESET PB

D2 VMR 1

D2 VMR 2

Relay position shown in 'Power off' condition

14