CT Dimension Ing
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
Protection CT
Measuring CT
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Magnetising Curve
10
CT Excitation - BH Curve
10
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Magnetising Curve
V = 2 f A N B = 4.44 f A N B V = induced voltage f = frequency A = cross sectional area of magnetic core N = number of secondary turns B = flux density L I = H N I = magnetising current L = mean magnetic path H = magnetising force
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Magnetising Curve
Es tim ate d CT Excitation Cur ve 35
30
20
15
10
Knee Point
0 0.00
0.05
0.10
0.15
0.20
0.25
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Measuring vs Protection Measuring CT Under over current, the CT should limit the secondary current to avoid thermal overload of the connected equipment At rated burden (cos = 0.8) and rated security factor, the composite error should be > 10% Protection CT In case of over current, the CT should maintain the secondary current within the rated limit to enable proper protection operation At rated burden (cos = 0.8) and rated accuracy limit factor, the composite error should be less than 5% or 10%
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Magnetising Curve
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Magnetising Curve
excitation limiting voltage (TPS Class) 10%
100%
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Saturation
Factors affecting CT saturation
CT ratio Core cross-sectional area Core design Connected burden B-H characteristic of core Amount of remanent flux Fault current & DC offset System time constant
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Saturation
Steady-state saturation with a.c. current
d di e = n = L dt dt
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Saturation
IP
saturation flux
IS
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Saturation
Transient CT saturation due to DC component
ISC
DC flux non-saturated
AC flux
Im
Magnetising current
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Standards IEC/AS 60044-1: Instrument transformers - Part 1 Current transformers (ed. 1.2 2003) IEC/AS 60044-6: Instrument transformers - Part 6 Requirements for protective current transformers for transient performance IEC/AS 60044-8: Instrument transformers -Part 8 Electronic current transformers AS 1675: Current Transformers Measurement & Protection (now superseded) BS7626 (BS 3938): Specification for current transformers (now superseded)
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Equivalent Circuit
n2Zpri 1:n Ideal Tx Iexcitation ZCT Zwire
Zburden
Xm
Rm
Zburden
Ipri/n
ZCT
Zwire
Zburden
Xm
Rm
Zburden
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT AS 60044 - 1
Definition of Ratio Error
rerror = 100
rerror
where
= permeabili ty = atan
Xs + Xz Rs + R z
CT AS 60044 - 1
Definition of Angle Error
where
= permeabili ty = atan
Xs + Xz Rs + R z
CT AS 60044 - 1 Class P
Rated Composite Error at ALF (turn ratio error, iron / copper losses, saturation) IEC/AS 60044-1 / BS3938: multiple of rated current at which, with rated burden, will maintain the accuracy IEC/AS 60044-1 / BS3938 specify Rated Burden
AS 60044: AS 1765:
Rated Secondary Reference Voltage Vref (the RMS secondary voltage upon which the performance is based)
Accuracy Limit Factor (ALF) (the factor which, when applied to at rated primary current, gives the accuracy limit primary current)
(Appendix H, AS1675)
CT AS 60044 - 1 Class P
Composite Error:
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT AS 60044 - 1 Class P
Max. Composite Error at Rated Accuracy Limit 5% 10%
Accuracy Class
5P 10P
60 min. -
1.8 centiradians -
AS 1675: Current error at rated current with Rb < 0.04 ohm: Ipri > 100A 1% Ipri 100A 2%
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT AS 60044 - 1 Class PR New to AS, e.g. 5PR 10VA Ts Rct Intended for limiting the remanence Additional requirements: Saturation flux (s) Remanent flux (r) Remanence factor (Kr =100r /s < 10%) Rated secondary loop time constant (Ts=Ls/Rs) (to be specified by purchaser) Secondary winding resistance (Rct) at 75oC Application: current differential protection for generators, motors, transformers, busbars and transmission lines.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT AS 60044 - 1 Class PX Low leakage flux Marking, e.g. 5PX 10VA Ek Ie Rct Kx Rb Rated turns ratio, turns ratio error < 0.25% Rated knee point e.m.f. (Ek) Maximum exciting current (Ie) at rated knee point e.m.f. and/or at stated percentage thereof Maximum resistance of the complete secondary winding at a temperature of 75 (Rct) C Purchaser may also specify: Dimensioning factor (Kx) Rated resistive burden (Rb)
Siemens. Innovation for generations.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT AS 60044 - 1 Class PX
(similar to BS 3938 Class X AS 1675 Class PL)
Rated knee point Max. secondary winding o voltage (Ek or Vk) resistance (Rct) at 75 C
CT AS 60044 - 1 Class PX
Ek = K x ( Rct + Rb ) I sn
Ek = rated knee point emf Kx = multiple of Isn at which the CT must perform satisfactorily Isn = rated secondary current Rb = rated resistive burden Rct = winding dc resistance at 75oC
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
, Rb = 15
, Rb = 15/25
Example
, Rb = 15
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT AS 60044 - 6 Class TP
At rated primary current Class Ratio error Phase Displacement Min. 60 Centered 1.8 At rated accuracy limit Peak instantaneous error 10% during specified duty cycle 10% (ac) during single energization with max. d.c. offset at specified secondary loop time constant 10% during specified duty cycle Remanence
1.0%
<10%
1.0%
180 18
5.3 0.6
negligible
TPX (closed iron core, low leakage flux) TPS (closed iron core, low leakage flux)
0.5%
30
0.9
no limit
0.25%
specify excitation current limit at excitation limiting secondary voltage (if not, then < excitation current at 10% peak instantaneous error of TPX class)
no limit
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Dimensioning
Operational Accuracy Limit Factor ALF
ALF' = ALF Pi + PN Ri + RN = n Pi + PB Ri + RB
with: RB=RL+RR= total burden resistance RL= resistance of connecting cable RR= relay burden resistance
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Dimensioning
Operational Accuracy Limit Factor ALF
I ALF ' K OD SC IN
Where KOD is the total over-dimensioning factor:
Theory:
No saturation during BMax XN K' TF = = 1 + TN = 1 + total fault duration:
B~
RN
K OD K TF K Rem
K Rem % remanence = 1+ 100
tM tM TN TS TN K ' 'TF = 1+ (e e TS TN TS
Practice:
K OD = KTF
Remanence only considered in extra high voltage systems (EHV) KTF-values acc. to relay manufacturers guides
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Dimensioning
Choice of CT rated power Rated burden > total connected burden For GIS and MV switchboard with modern relays/measuring devices, class P 1A CTs with small rated burden are sufficient, e.g. 5VA, 10VA Choice of Accuracy Limit Factor Relay manufacturers recommendation should be followed + engineering security factor CT performance depends on operational ALF
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Dimensioning
Choice of CT Ratio CT ratio should be based on the protected object, however, it may need to be go higher: limitation of difference in CT ratio for low impedance differential protection as recommended by the relay manufacturer Avoid excessive over-dimensioning: Imax, switchgear / Ipri-rated > 100 ! Such CT can damage the relay because there is no CT saturation
If a more precise estimation of the CT performance is necessary, then RCT and the magnetising curve is required.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT Dimensioning
Choice of Measuring CT For classes 0.1 1, the accuracy is based on a total connected burden between 25% to 100% of the rated burden For classes 0.1, 0.2 and 0.2S with rated burden < 15VA, an extended range of burden can be specified (from 1VA to 100% of the rated burden) For classes 3 and 5, the accuracy is based on a total connected burden between 50% to 100% of rated burden Instrument security factor (FS) defines the maximum secondary current that will flow under short circuit of primary circuit Instrument security factor (FS) is based on the rated burden Under-burdened measuring CT can damage connected instrument during short circuit or overload of the primary circuit
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT symmetry
4 4 3 3
5 5 5 5
5 3 4
1 3
1.00 0.50
0.75
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
CT saturation is allowable provided the remaining fundamental current is sufficient to trigger Zone 1 operation
CT saturation is allowable only after the preset time delay for tripping command
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
Our Vision
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.
Zstabilise
Xm
Rm
Zrelay
Xm
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.