CT Dimensioning

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Current Transformers Dimensioning

Protection CT

Measuring CT

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Magnetising Curve

10

CT Excitation - BH Curve

Flux Density - B (tesla)

Measured Knee Knee' 0 0 1


Exciting Current (A-tuns/cm)

10

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Magnetising Curve

V = 2 f A N B = 4.44 f A N B V = induced voltage f = frequency A = cross sectional area of magnetic core N = number of secondary turns B = flux density L I = H N I = magnetising current L = mean magnetic path H = magnetising force

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Magnetising Curve
Es tim ate d CT Excitation Cur ve 35

30

25 E c tio V lta e(V x ita n o g )

20

15

10

Knee Point

0 0.00

0.05

0.10

0.15

0.20

0.25

Excitation Cur re nt (A)

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Measuring vs Protection Measuring CT Under over current, the CT should limit the secondary current to avoid thermal overload of the connected equipment At rated burden (cos = 0.8) and rated security factor, the composite error should be > 10% Protection CT In case of over current, the CT should maintain the secondary current within the rated limit to enable proper protection operation At rated burden (cos = 0.8) and rated accuracy limit factor, the composite error should be less than 5% or 10%

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Magnetising Curve

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Magnetising Curve
excitation limiting voltage (TPS Class) 10%

100%

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Saturation
Factors affecting CT saturation

CT ratio Core cross-sectional area Core design Connected burden B-H characteristic of core Amount of remanent flux Fault current & DC offset System time constant

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Saturation
Steady-state saturation with a.c. current

Transient saturation with offset current

d di e = n = L dt dt
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Saturation
IP

saturation flux

IS

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Saturation
Transient CT saturation due to DC component

ISC

Short circuit current

DC flux non-saturated

AC flux

Im

Magnetising current

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Standards IEC/AS 60044-1: Instrument transformers - Part 1 Current transformers (ed. 1.2 2003) IEC/AS 60044-6: Instrument transformers - Part 6 Requirements for protective current transformers for transient performance IEC/AS 60044-8: Instrument transformers -Part 8 Electronic current transformers AS 1675: Current Transformers Measurement & Protection (now superseded) BS7626 (BS 3938): Specification for current transformers (now superseded)

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Equivalent Circuit
n2Zpri 1:n Ideal Tx Iexcitation ZCT Zwire

Zburden

Xm

Rm

Zburden

Ipri/n

ZCT

Zwire

n:1 Ideal CT Iexcitation

Zburden

Xm

Rm

Zburden

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1
Definition of Ratio Error

rerror = 100

I sec nr I prim I prim

Ratio Error (pu)

rerror
where

I s Z slcore sin( + ) 2fAcore N s I p N p

= permeabili ty = atan
Xs + Xz Rs + R z

= phase angle of excitation


(+ error due to stray capacitance)
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1
Definition of Angle Error

= angle( I sec ) angle( I prim )


Phase Angle Error (radians)

I s Z slcore cos( + ) 2fAcore N s I p N p

where

= permeabili ty = atan
Xs + Xz Rs + R z

= phase angle of excitation


For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1 Class P
Rated Composite Error at ALF (turn ratio error, iron / copper losses, saturation) IEC/AS 60044-1 / BS3938: multiple of rated current at which, with rated burden, will maintain the accuracy IEC/AS 60044-1 / BS3938 specify Rated Burden

AS 60044: AS 1765:

5P20 5VA 5P 100 F20

Rated Secondary Reference Voltage Vref (the RMS secondary voltage upon which the performance is based)

Conversion: Vref I sec = VA ALF


For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Accuracy Limit Factor (ALF) (the factor which, when applied to at rated primary current, gives the accuracy limit primary current)
(Appendix H, AS1675)

Siemens. Innovation for generations.

CT AS 60044 - 1 Class P

Composite Error:

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1 Class P
Max. Composite Error at Rated Accuracy Limit 5% 10%

Accuracy Class

Max. Current Error at Rated Primary Current 1% 3%

Phase Displacement at Rated Primary Current

5P 10P

60 min. -

1.8 centiradians -

Accuracy limit based on steady state symmetrical primary current

AS 1675: Current error at rated current with Rb < 0.04 ohm: Ipri > 100A 1% Ipri 100A 2%
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1 Class PR New to AS, e.g. 5PR 10VA Ts Rct Intended for limiting the remanence Additional requirements: Saturation flux (s) Remanent flux (r) Remanence factor (Kr =100r /s < 10%) Rated secondary loop time constant (Ts=Ls/Rs) (to be specified by purchaser) Secondary winding resistance (Rct) at 75oC Application: current differential protection for generators, motors, transformers, busbars and transmission lines.

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1 Class PX Low leakage flux Marking, e.g. 5PX 10VA Ek Ie Rct Kx Rb Rated turns ratio, turns ratio error < 0.25% Rated knee point e.m.f. (Ek) Maximum exciting current (Ie) at rated knee point e.m.f. and/or at stated percentage thereof Maximum resistance of the complete secondary winding at a temperature of 75 (Rct) C Purchaser may also specify: Dimensioning factor (Kx) Rated resistive burden (Rb)
Siemens. Innovation for generations.

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

CT AS 60044 - 1 Class PX
(similar to BS 3938 Class X AS 1675 Class PL)

0.05PX 450 R3 10VA Kx Rb


Max. exciting current (Ie) at rated knee point voltage Dimensioning Rated resistive factor (Kx) burden (Rb)

Rated knee point Max. secondary winding o voltage (Ek or Vk) resistance (Rct) at 75 C

Turn ratio error within 0.25%


AS 1675: or 50/Ns whichever the greater, where Ns = number of secondary turns
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1 Class PX

Ek = K x ( Rct + Rb ) I sn
Ek = rated knee point emf Kx = multiple of Isn at which the CT must perform satisfactorily Isn = rated secondary current Rb = rated resistive burden Rct = winding dc resistance at 75oC

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 1 Class PX Conversion from Class P to Class PX


( Rb + Rct ) I sn K ssc Vk = 1.3 Example

600/1, 5P10, 15VA, Rct = 4


(15 + 4) 1 10 Vk = = 146V 1.3

, Rb = 15

3000/5, 5P10, 15VA, Rct = 4


(15 / 25 + 4) 5 10 Vk = = 177V 1.3
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

, Rb = 15/25

Siemens. Innovation for generations.

CT AS 60044 - 1 Class PX Conversion from Class PX to Class P


K ssc = 1.15 Vk ( Rb + Rct ) I sn

Example

600/1, 0.05PX 150, 15VA, Rct = 4


K SSC = 1.15 150 1 = 9.1 (15 + 4)

, Rb = 15

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT AS 60044 - 6 Class TP
At rated primary current Class Ratio error Phase Displacement Min. 60 Centered 1.8 At rated accuracy limit Peak instantaneous error 10% during specified duty cycle 10% (ac) during single energization with max. d.c. offset at specified secondary loop time constant 10% during specified duty cycle Remanence

TPY (anti-remanence air gap)

1.0%

<10%

TPZ (linear core)

1.0%

180 18

5.3 0.6

negligible

TPX (closed iron core, low leakage flux) TPS (closed iron core, low leakage flux)

0.5%

30

0.9

no limit

0.25%

specify excitation current limit at excitation limiting secondary voltage (if not, then < excitation current at 10% peak instantaneous error of TPX class)

no limit

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning
Operational Accuracy Limit Factor ALF
ALF' = ALF Pi + PN Ri + RN = n Pi + PB Ri + RB

P + PB Ri + RB ALF = ALF' i = ALF' Pi + PN Ri + RN

Rated CT burden: Internal CT burden: Actually connected burden :

PN Pi=Ri I2N2 PB= RB I2N2

with: RB=RL+RR= total burden resistance RL= resistance of connecting cable RR= relay burden resistance
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning
Operational Accuracy Limit Factor ALF
I ALF ' K OD SC IN
Where KOD is the total over-dimensioning factor:

Theory:
No saturation during BMax XN K' TF = = 1 + TN = 1 + total fault duration:

B~

RN

K OD K TF K Rem
K Rem % remanence = 1+ 100

No saturation for the specified time tM:

tM tM TN TS TN K ' 'TF = 1+ (e e TS TN TS

Practice:

K OD = KTF
Remanence only considered in extra high voltage systems (EHV) KTF-values acc. to relay manufacturers guides
For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning
Choice of CT rated power Rated burden > total connected burden For GIS and MV switchboard with modern relays/measuring devices, class P 1A CTs with small rated burden are sufficient, e.g. 5VA, 10VA Choice of Accuracy Limit Factor Relay manufacturers recommendation should be followed + engineering security factor CT performance depends on operational ALF

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning
Choice of CT Ratio CT ratio should be based on the protected object, however, it may need to be go higher: limitation of difference in CT ratio for low impedance differential protection as recommended by the relay manufacturer Avoid excessive over-dimensioning: Imax, switchgear / Ipri-rated > 100 ! Such CT can damage the relay because there is no CT saturation

If a more precise estimation of the CT performance is necessary, then RCT and the magnetising curve is required.

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning
Choice of Measuring CT For classes 0.1 1, the accuracy is based on a total connected burden between 25% to 100% of the rated burden For classes 0.1, 0.2 and 0.2S with rated burden < 15VA, an extended range of burden can be specified (from 1VA to 100% of the rated burden) For classes 3 and 5, the accuracy is based on a total connected burden between 50% to 100% of rated burden Instrument security factor (FS) defines the maximum secondary current that will flow under short circuit of primary circuit Instrument security factor (FS) is based on the rated burden Under-burdened measuring CT can damage connected instrument during short circuit or overload of the primary circuit

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning Overcurrent Protection


CT saturation is allowable provided the remaining fundamental current is higher than I>> setting

Isec, fundamental > I >

Isec,funfamental > I >>


Pn + PCT I >> ALF' = ALF > P '+ PCT In

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning Differential Protection


Differential protection should be stable on external faults High sensitivity for internal fault
Protected Object Relay Type Requirement for Internal Faults Requirements for External Faults

min. saturation free time (ms)

min. over dimensioning KTF 0.75 0.75 0.50 0.50

min. saturation free time (ms)

min. over dimensioning KTF 1.20 1.20 1.20 1.20

CT symmetry

Generator Transformer O/H Line, Cable with digital communication

7UM6 7UT6 7SD52 7SD61

4 4 3 3

5 5 5 5

O/H Line, Cable with pilot wires Busbar

7SD600 7SS52 7SS600

5 3 4

1.20 0.50 0.75

1 3

1.00 0.50

0.75

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

4 0.75 Siemens. Innovation for generations.

CT Dimensioning Distance Protection


Zone 1 faults should be cleared without delay Faults outside Zone 1 should trip after preset delay

CT saturation is allowable provided the remaining fundamental current is sufficient to trigger Zone 1 operation

CT saturation is allowable only after the preset time delay for tripping command

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning CT Requirements SIPROTEC Catalogue Part 2

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning CT Requirements SIPROTEC Catalogue Part 2

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

CT Dimensioning CT Requirements SIPROTEC Catalogue Part 2

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Our Vision

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

High Impedance Differential Scheme

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

High Impedance Restricted Earth Fault

For internal use only / Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

High Impedance Scheme Through Fault Stability


n2Zpri 1:n Ideal Tx Iexcitation ZCT Zwire Zwire ZCT n2Zpri n:1 Iexcitation Ideal Tx Rm

Zstabilise

Xm

Rm

Zrelay

Xm

Stabilising resistor Knee point voltage Non-linear resistor Effective setting


Siemens. Innovation for generations.