4-INCH PIPE
2. Min. Working Pressure (PSI) = 200
LB * = X
@ 100 PSI 1,810 3,620 / 1,500 1.5 = 3,620 LB = 2.41 = 3.62 S.F. S.F. USE 2' WIDE X 2' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 2,559 5,118 / 1,500 1.5 = 5,118 LB = 3.41 = 5.12 S.F. S.F. USE 2.5' WIDE X 2.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 1,385 2,770 / 1,500 1.5 = 2,770 LB = 1.85 = 2.77 S.F. S.F. USE 2' WIDE X 1.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 706 1,412 / 1,500 1.5 = 1,412 LB = 0.94 = 1.41 S.F. S.F. USE 1.5' WIDE X 1' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 355 710 / 1,500 1.5 = 710 = 0.47 = 0.71 LB S.F. S.F. USE 1' WIDE X 1' HIGH THRUST BLOCK
6-INCH PIPE
2. Min. Working Pressure (PSI) = 200
LB * = X
@ 100 PSI 3,739 7,478 / 1,500 1.5 = 7,478 LB = 4.99 = 7.48 S.F. S.F. USE 3' WIDE X 2.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 5,288 10,576 / 1,500 1.5 = 10,576 LB = 7.05 S.F. USE 4' WIDE X 3' HIGH THRUST BLOCK = 10.58 S.F.
LB * = X
@ 100 PSI 2,862 5,724 / 1,500 1.5 = 5,724 LB = 3.82 = 5.72 S.F. S.F. USE 2.5' WIDE X 2.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 1,459 2,918 / 1,500 1.5 = 2,918 LB = 1.95 = 2.92 S.F. S.F. USE 2' WIDE X 1.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 733 1,466 / 1,500 1.5 = 1,466 LB = 0.98 = 1.47 S.F. S.F. USE 1' WIDE X 1.5' HIGH THRUST BLOCK
8-INCH PIPE
2. Min. Working Pressure (PSI) = 200
LB * = X
@ 100 PSI 6,433 12,866 / 1,500 1.5 = 12,866 LB = 8.58 = 12.87 S.F. S.F. USE 4' WIDE X 3.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 9,097 18,194 / 1,500 1.5 = 18,194 LB = 12.13 = 18.19 S.F. S.F. USE 5' WIDE X 4' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 4,923 9,846 / 1,500 1.5 = 9,846 = 6.56 = 9.85 LB S.F. S.F. USE 3.5' WIDE X 3' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 2,510 5,020 / 1,500 1.5 = 5,020 = 3.35 = 5.02 LB S.F. S.F. USE 3' WIDE X 2' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 1,261 2,522 / 1,500 1.5 = 2,522 = 1.68 = 2.52 LB S.F. S.F. USE 2' WIDE X 1.5' HIGH THRUST BLOCK
10-INCH PIPE
2. Min. Working Pressure (PSI) = 200
LB * = X
@ 100 PSI 9,677 19,354 / 1,500 1.5 = 19,354 LB = 12.90 = 19.35 S.F. S.F. USE 5' WIDE X 4' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 13,685 27,370 / 1,500 1.5 = 27,370 LB = 18.25 = 27.37 S.F. S.F. USE 5.5' WIDE X 5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 7,406 14,812 / 1,500 1.5 = 14,812 LB = 9.87 = 14.81 S.F. S.F. USE 4' WIDE X 4' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 3,776 7,552 / 1,500 1.5 = 7,552 = 5.03 = 7.55 LB S.F. S.F. USE 3' WIDE X 3' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 1,897 3,794 / 1,500 1.5 = 3,794 = 2.53 = 3.79 LB S.F. S.F. USE 2' WIDE X 2' HIGH THRUST BLOCK
12-INCH PIPE
2. Min. Working Pressure (PSI) = 200
LB * = X
@ 100 PSI 13,685 27,370 / 1,500 1.5 = 27,370 LB = 18.25 = 27.37 S.F. S.F. USE 6' WIDE X 5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 19,353 38,706 / 1,500 1.5 = 38,706 LB = 25.80 = 38.71 S.F. S.F. USE 6' WIDE X 7' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 10,474 20,948 / 1,500 1.5 = 20,948 LB = 13.97 = 20.95 S.F. S.F. USE 5' WIDE X 4.5' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 5,340 10,680 / 1,500 1.5 = 10,680 LB = 7.12 = 10.68 S.F. S.F. USE 4' WIDE X 3' HIGH THRUST BLOCK
LB * = X
@ 100 PSI 2,683 5,366 / 1,500 1.5 = 5,366 = 3.58 = 5.37 LB S.F. S.F. USE 2.5' WIDE X 2.5' HIGH THRUST BLOCK