Professional Documents
Culture Documents
Screw Compressor Troubleshooting Guide: Caution: Never Run The Compressor in Reverse!
Screw Compressor Troubleshooting Guide: Caution: Never Run The Compressor in Reverse!
I Insure oil feed lines are open (oil solenoid). I Check oil pressure at compressor manifold with a gauge.
Suction Access Port Min Pressure 10 vacuum
Suction Service Valve Max temp 65F, 6 from the service valve
Motor Temperature (5K thermistor connection on terminal plate) Economizer/ Subcooler Port (not shown) Rotalock valve, 7/8 sweat connection must have 15F - 20F superheat
Discharge Service Valve Max Temp 230F, 6 from the service valve (5K thermistor strapped to discharge line)
Oil Port Access Port (1/4 Schrader, not shown) Liquid For field gauge connections Injection Port Oil Press Transducer (3/8 Flare, Max Press Differential used if necessary) (discharge - oil) 50psi VI (Volume Index) Valve energize coil at Oil Inlet Min Differential Pressure (Oil - Suction) 45psi pressure ratios > 5:1 (3/8 Flare)
Compressor Periodically Makes Loud Noise or Becomes Very Quiet for a Short Time
I Check for excessive liquid/oil return to compressor.
Support/Contact
I Call Application Engineering for further assistance at 800.532.5036. Carlyle Compressor Division P. O. Box 4808 Syracuse, NY 13221 Phone: 800.532.5036 Fax: 315.432.3274
0604 Lit. No. 574-081 Rev. A
05T Model
I Compressor is running in reverse, check phase sequence and bump compressor to insure proper rotation (check pressure at outlet port). I Insure LonCEM module and discharge pressure transducer are wired and functioning correctly.
When compressor cycles off:
I Pressure switch set too high, reset as low as necessary (older systems with reverse rotation switch). Oil Pressure Differential Trips
I Insure all manual oil line valves are open. I Check pressure drop through oil system, oil filters may have to be changed. I Insure oil line solenoid is functioning properly. I Insure LonCEM module and pressure transducers are wired and functioning properly.