JINDAL STEEL AND POWER LTD.

PT1

CALIBRATION TEST REPORT


Date :.. 7-Mar-12

Make

ROSEMOUNT

Model.

2051T62A2B21AB4M504

Due Date:

07/03/2013

Serial No..

0002434

Inst Range.

0-150 psi

Location

Furnace

Process Range.

0.00-5.00Kg/cm2

Medium
Test
1. PORTABLE FURNACE - SL No :- 12345
instruments
used..
2. DIGITAL MULTIMETER- SL No :- 12345
Pre - Calibration Data

INCREMENT
Input
In
Kg/cm2

Expected
output in
mA

DECREMENT

OUT PUT AS FOUND


Increasing
in
mA

Error
in
%

Input
In
Kg/cm2

Expected
output in
mA

Decreasing
in
mA

Error
in
%

0.00

4.00

2.00

-12.50

0.00

4.00

7.00

18.75

1.25

8.00

8.00

0.00

1.25

8.00

8.00

0.00

2.50

12.00

12.00

0.00

2.50

12.00

12.30

1.88

3.75

16.00

16.00

0.00

3.75

16.00

16.00

0.00

5.00

20.00

20.00

0.00

5.00

20.00

20.00

0.00

Post - Calibration Data

INCREMENT
Input
In
Kg/cm2

Expected
output in
mA

DECREMENT

OUT PUT AS LEFT


Increasing
in
mA

Error
in
%

Input
In
Kg/cm2

Expected
output in
mA

Decreasing
in
mA

Error
in
%

5.00

20.00

20.00

0.00

5.00

20.00

20.00

0.00

0.00

4.00

4.00

0.00

0.00

4.00

4.00

0.00

1.25

8.00

8.00

0.00

1.25

8.00

85.00

481.25

2.50

12.00

12.00

0.00

2.50

12.00

12.00

0.00

3.75

16.00

16.00

0.00

3.75

16.00

16.00

0.00

Note:Maximum allowable error in the instrument is : +/- 0.25 %

=> 0.04 mA

Remarks :tested
Name

Designation.

Signature

Date

Performed by admin

admin

07/03/2012

Verified by

admin

admin

07/03/2012

Reviewed by. admin

admin

07/03/2012