Subject:OperationofSteamTurbine Issuedby:CHPChiefOperatingEngineer MaximumReviewPeriod: 2Years NumberE.31 Pages:1 Date:June2010

OPERATIONOFSTEAMTURBINEE.31 1.0Forward A300h.p.dresserRandsinglestageturbineservesasanalternatedriveforBoilerNo.6forced draftfan.BoilerNo.8forceddraftfanisequippedwitha220H.P.Westinghousesteamturbine asanalternatedrive.FeedwaterpumpNo.2hasaWorthington170H.P.turbineasaprime mover. 2.0StartUpProcedure 1. Ensurealldrainsareopen. 2. Checktheoillevelinbearingsandgovernors. 3. Turnoncoolingwatertobearings. 4. FeedPumpNo.2turnontheoiltothegovernorbearing. 5. Slowlyopentheexhaustvalveanwarmuptheturbine. 6. Crackopenthesteamsupplyvalve.Closethedrainvalveswhenallthecondensatehas beendrainedfromtheturbinecasing. 7. Continuetobringtheturbineuptospeed. 8. Triptheturbineusingtheoverspeedtrip. 9. Restarttheturbineandputitonline. 10. Aftertheturbinehasbeeninoperationforafewminutesadjusttheoilsupplytothe governor(feedwaterturbine).Checklubricationtobearingsandbearingtemperatures. Ensuretheturbineisrunningnormally.