Comment 2, Guardrail for mezzanine shall be not less than 42 in (1065mm) as per clause 7.2.2.4.5.2 of NFPA 101.

Comment 3, According to section 5.1.1.3 and 5.1.1.4 of NFPA 850, the warehouse, maintenance workshop shall be separated from adjacent area by fire barriers. Fire barriers separating fire areas should be a minimum of 2-hour fire resistance rating.

Comment 1, the minimum stair tread depth, T, shall be 280mm as per Table 7.2.2.2.1.1 (a) of NFPA 101 which shall be followed according to ER.