Professional Documents
Culture Documents
Controls
q
Wiring
Design Guide
This Guide is provided for general information only. The building or heating system designer is responsible for all design details and for compliance with all building codes, local and national. Refer to AlumiPex Technical Information sheets for specific certifications and listings of AlumiPex Radiant Tubing. AlumiPex Radiant Tubing is not certified for potable water applications. Consult local requirements before installing a radiant heating system. Install AlumiPex tubing following all of the applicable codes and all specifications and methods prescribed by the building designer and heating system designer. Do not use AlumiPex Radiant Tubing to conduct natural gas. Such an application could result in severe personal injury, death or substantial property damage. Material referenced in this Guide is subject to change without notice. Review all equipment installation instructions for compatibility before installing. Install all equipment in accordance with the equipment manufacturers instructions and all applicable codes. Failure to do so could result in severe personal injury, death or substantial property damage. Do not use AlumiPex Radiant Tubing in potable water or in systems which use boiler system water for potable use. The tubing is not approved for domestic water use. In combination space heating/potable water heating applications, chemical or biological contamination in the system water is possible and could result in severe personal injury, death or substantial property damage. Use only AlumiPex Fittings with AlumiPex Tubing. Use of any other method can result in severe personal injury, death or substantial property damage. Finished flooring: Use only finished flooring approved by the flooring manufacturer for use with heated floors. Failure to follow this guideline could result in substantial property damage. Do not expose AlumiPex Radiant Tubing to petroleum products or solvents.
Contents
I II Overview .................................................................................................................................. 4 Piping & control methods
Three temperature control ...................................................................................................... ..................................................... 5 Exceptions .................................................................................................................................................................................... 6 Piping/ controlling methods ......................................................................................................................................................... 6 Method 1 - Variable speed injection mixing ............................................................................................................................... 7 Method 2 - Dual three-way valves .............................................................................................................................................. 9
III IV
Primary/secondary piping
Why use primary/secondary piping? ........................................................................................................................................ 10 Primary/secondary piping tips ................................................................................................................................................... 12
V VI
IX X XI
Selecting pumps
Method 1 - select pump from pump curve ............................................................................................................................... 39 Method 2 - select pump from quick selector curves ................................................................................................................ 41
Overview
Whats in this guide?
We intend this Guide to provide system designers with the information needed to select and specify controls, pumps and piping for AlumiPex radiant heating systems.
Determining flow rates provides suggestions on how
to calculate the flow rates needed for each type of circuit in a radiant system - for multiple purpose systems as well as for radiant heating only.
Determining head loss provides means for calculating head losses in copper and steel piping and in AlumiPex radiant tubing circuits. Selecting pumps provides pump curves for common
The most important message in this guide is the need to control not just space and supply water temperatures, but to design and install systems that regulate the boiler return water temperature.
two basic piping/control designs which meet the needs of AlumiPex radiant heating systems and the needs of noncondensing boilers. These are
pumps. This section includes a new approach to pump sizing - curves for , and 1 AlumiPex tubing and through 2 copper piping that show pump GPM vs system equivalent length for common circulators (pumps). This allows you to directly select a pump based on your system equivalent length and flow rate, or to see what will happen if you place a different pump on your system, without having to draw a system curve.
Piping radiant circuits and Domestic water heating
Variable speed injection mixing (preferred method) Dual three-way valves (alternate method)
Though other designs can accomplish similar performance, we have chosen to concentrate on a limited selection to assure coverage in depth.
Primary/secondary piping outlines the reasons for using
introduce the final section of this guide, devoted to specific methods for piping and controlling radiant systems and multiple purpose systems (radiant heating plus domestic water heating and baseboard heating). These sections provide the background for the radiant heating piping examples which follow.
Radiant heating examples includes 12 examples of radiant heating systems, including multiple purpose systems for domestic water and baseboard heating. These do not represent all of the possibilities, but show some effective applications of the principles discussed in this Guide. Note, in particular, the emphasis on threetemperature control control the boiler return water temperature (to protect the boiler) in addition to space and supply water temperatures.
outdoor reset and discusses continuous (or extended) circulation in radiant heating, along with some guidelines for setting up reset controls.
Injection mixing components gives a brief introduction to the Weil-McLain Injection Pump Control, the IPC, and the Injection Pump Panel, the IPP. For further information on these components, refer to the Injection
This guide does not include radiant heating heat loss calculations or tubing placement design. These are handled in separate publications. Weil-McLain currently provides a computer-based sizing system the AlumiPex Radiant Expert program. We recommend using the A.R.E. in combination with this guide for the most comprehensive coverage of radiant heating design with our products.
Part Number 650-000-240/1098
II
Three temperature control
Regulate the space temperature by: sensors located in the space and outside (if outdoor reset is used) correct placement of radiant tubing and other heating units regulation of heating water temperature and flow Regulate the system supply temperature by: using a control designed for radiant heating using primary/secondary piping as described in this guide using variable speed injection mixing or a correctly placed three-way valve Regulate the boiler return water temperature by: using primary/secondary piping as described in this guide using a variable speed injection mixing system or correctly placed three-way valve Why regulate the boiler return water? Flue gases contain water and acid vapors. When the flue gases contact a surface below the dewpoint temperature, acid and/or water will condense on that surface. This could damage the boiler and lead to premature failure. Controlling the return water at or above 130 F will provide protection for most boilers. Radiant heating systems typically operate with supply water below 130 F and return water from 90 to 110 F. Water this cool will cause condensation damage and may cause thermal shock as well. The controls and piping must be designed and installed to return water to a noncondensing boiler at or above 130 F to prevent condensation and possible thermal shock. Failure to follow this guideline could result in substantial property damage.
Part Number 650-000-240/1098
II
Piping/controlling methods
This Guide focuses on the two preferred methods of regulating space, supply water and return water temperatures Method 1 - Variable speed injection mixing. Method 2 - Dual three-way mixing valves.
Method 2 may, in some cases, have a lower first cost than Method 1. But Method 2 cannot provide outdoor reset control without motorized valves - this could cause Method 2 to be more costly than Method 1.
Exceptions
There are exceptions to the need for return water temperature control - but ONLY for cases where the return water temperature will naturally remain above the minimum specified by the boiler manufacturer. An example is the special case of floor heating using tubing suspended in the joist bays (not stapled to the floor). For such systems, the supply water temperature is usually 160 F or higher. Moreover, the radiant system has low mass because the tubing is not in contact with the floor. So, these systems will behave similarly to finned tube baseboard systems - return water temperature will nearly always be above 130 F, and any periods of lower return temperature will be brief. Such exceptions are not illustrated in this Guide (except for System CP1, discussed below) to avoid confusing the issue. Most radiant heating installations require
return water control because most of the heating sources require a minimum.
Interchangeability
Figures 2 and 3 are simplified schematics of Methods 1 and 2, respectively.
Note the piping contained in the dotted rectangles of these schematics. Wherever an IPP Injection Pump
You will find an exception to regulated return temperature in Radiant heating system examples, System CP1. This special case applies to a small radiant circuit added to an existing baseboard heating system. For this situation, return water protection is unnecessary because the radiant circuit will not reduce the return water temperature significantly.
Panel (Method 1) is shown in piping diagrams in this Guide, you can substitute the piping in the dotted rectangle in Figure 3. That is, the dual three-way mixing valves, piped as shown, will provide the same regulation and protection as Method 1. Bear in mind, if outdoor reset is desired with Method 2, a motorized valve and appropriate controls will be required.
Figure 1 is a simplified injection mixing circuit. The injection pump pulls hot water from the primary loop at C. This water (at temperature TH) is injected into the secondary (heating) circuit at A, where it mixes with the cooler return water (temperature TR). The result is heating circuit supply water at temperature TS. If the injection flow rate, FI, is increased the supply water temperature will increase. If the injection flow rate is decreased the supply water temperature will decrease.
The return water from the secondary (heating) circuit lowers the water temperature returning to the boiler. So the IPC Injection Pump Control monitors boiler return water temperature (see Figure 2) as well as heating circuit supply water temperature. Should the boiler circuit return water temperature approach 130 F, the IPC slows down the injection pump. This raises the temperature returning to the boiler because less cool heating circuit water is injected into the boiler (primary) circuit.
TH
Balancing valve
TH FI
Injection pump
TR
System return
TS FS
System supply
II
Refer to Section VI, Injection mixing components, for application and sizing information.
(The piping enclosed in the dotted rectangle represents the components included in a Weil-McLain IPP Injection Pump Panel)
2 to 4 pipe diameters
Expansion tank
Boiler return sensor
IPC
Injection pump
Manifolds
Boiler
Radiant loops
With the piping as shown, the heating system may operate at any desired temperature without risk of causing condensation in the boiler. Likewise, the boiler supply temperature may be set as high as desired without causing excessive temperature in the heating system because the heating system three-way valve controls the temperature sent to the system.
not be necessary for finned tube baseboard heating systems which have a small, low mass radiant loop as shown in example system CP-3. Small means the radiant circuit load must not exceed 10% of the boiler output. This radiant application must only be for suspended floor applications not for slab applications (neither thick nor thin slab).
Expansion tank
2 to 4 pipe diameters
Radiant loops
III
Why use primary/ secondary piping?
Primary/secondary piping
Traditional piping for residential hydronic heating uses series loop or two-pipe piping. Commercial systems are usually two-pipe design. These piping designs lack the versatility and efficiency needed for today's systems, particularly for radiant heating. Use primary/secondary piping for radiant heating (and for any system using outdoor reset or energy management). Look at Figures 4 through 7 for a comparison of a traditional two-pipe system to a primary/ secondary system. Notice that the system pump must provide all the flow needed for every branch in a traditional two-pipe system. But the flow in each secondary circuit (branch) of the primary/secondary system is individually controlled by the loop components.
Advantages
This discussion emphasizes the advantages of primary/secondary piping in radiant heating systems. You should see that the versatility of primary/secondary designs and the ability to more easily control temperatures and flows in each loop make this approach essential.
The operation of pumps and control valves in a secondary circuit has no effect on pressure in other secondary circuits of a primary/secondary system. There is no concern of over-pressuring the control valve seats. In a traditional two-pipe system the pressure on control valves increases as other loop valves close because the reduced flow causes the system pump to shift up on its pump curve. Since closure of a secondary circuit has no impact on other secondary circuits, any circuit can be isolated for service without impacting the rest of the system. Secondary circuit piping and components (pumps and valves) are sized only for the needs of that circuit not for the system as a whole. The flow and head loss through the primary pump never changes and the flow circuit is never interrupted due to closure of control valves. On traditional two-pipe systems, the flow rate changes constantly due to action of the control valves. And a by-pass pressure regulator is needed to protect the pump from high head conditions (dead heading) as branch control valves close. With multiple boilers on secondary loops, there is no flow through idle boilers. So stand-by loss is virtually eliminated. Individual boilers can be isolated for service without affecting the rest of the system.
Disadvantages
The need for a pump in every secondary circuit could be deemed a disadvantage. On the other hand, the individual pumps provide primary/secondary systems with their versatility.
10
LOAD
LOAD
Flow/check valves Secondary pump
LOAD
LOAD
Flow/check valves Secondary pump
LOAD LOAD
Control valves Balancing valves
Flow/check valves
Secondary pump
Pump
Primary pump
Fill Expansion tank
Fill Expansion tank
Secondary pump
BOILER
BOILER
Flow/check valves
Primary piping
Primary piping
LOAD
Balancing valve Control valve
2 to 4 pipe diameters
Secondary piping
LOAD
Part Number 650-000-240/1098
11
III
Primary/secondary piping tips
Common piping must be sized for the larger of the primary or secondary piping. Continue this pipe size at least 8 pipe diameters upstream of the first secondary circuit tee. 4 pipe diameters downstream of the second tee.
Size the secondary circuit tees for whichever flow is larger the primary or the secondary circuit. Space secondary circuit tees no wider than 4 common piping pipe diameters. The tees must be spaced closely to minimize the pressure difference caused by flow through the primary circuit. This pressure difference, if too large, would induce flow in the branch. Secondary pump should flow into secondary circuit (away from primary piping) to raise pressure in the secondary circuit when pump comes on. Thoroughly ream copper piping between tees to prevent causing a pressure drop or turbulence due to burrs.
Where secondary loop piping is above the secondary circuit tees, use two flow/check valves (Figure 9) or one flow check on the supply and a minimum 18 inch thermal trap on the return (Figure 10). Note you can use a swing check valve in place of the flow/check valve on the return piping if piped horizontally. Where secondary circuit piping is below the branch tees at least 18 inches, no traps or check valves are needed (Figure 11). With an injection mixing circuit piped below the primary piping at least 18 inches, as in Figure 12, no additional thermal trapping or flow/check valves are required, provided the injection pump is turned off when connected branches are satisfied. Do not install flow/ checks in injection risers. Boiler loop piping (for boiler piped on a secondary loop) no flow/check valves are needed if primary piping is below the boiler(s). Otherwise, use a flow/check valve on the supply line. Indirect water heaters refer to Figure 14. Use a flow/check valve in the piping when the water heater is located below the primary. This will prevent gravity flow caused when the water heater water is hotter than the primary loop.
Circuit sequencing
When possible, sequence the secondary circuits off of the primary with the circuits requiring the hottest water first and those requiring the coolest water last. This will reduce the flow rate required in the primary circuit.
12
To secondary circuit
2 to 4 pipe diameters
Common piping
Primary circuit
Primary circuit
Figure 10 Alternate use a flow/check valve in the branch supply line and a thermal trap below the primary as below.
LOAD
Flow/check valve Secondary pump Flow/check or swing check valve
Flow/check valve
LOAD
Secondary pump
2 to 4 pipe diameters
2 to 4 pipe diameters
18" Min
13
III
LOAD
2 to 4 pipe diameters
18 min
2 to 4 pipe diameters Primary
Secondary pump
Balancing valve Injection pump Secondary pump
Primary
18" Min
LOAD
2 to 4 pipe diameters
Figure 13 Provide minimum 8 pipe diameters between air separator and pump inlet connection as shown below.
8 pipe diameters minimum
Figure 14 Use a flow/check valve in the return line when an indirect water heater is piped below the primary piping to prevent gravity circulation.
2 to 4 pipe diameters
Air separator
Fill
Pump
flow/check valve
14
IV
Combining spaces for zoning
When combining spaces for a zone, make sure they are similar with respect to
t The type of radiant heat application in the space must be similar
Slab on grade, thin slab, below floor, above floor, etc. dont mix system types on the same zone. Below floor applications usually require higher water temperature than other types. The mass of a slab system responds differently from a low mass suspended floor system (above floor or below floor tubing installation). Select radiant circuits requiring similar water temperatures when combining in common zones. Availabe floor area will affect the supply temperature required. So floor area available in spaces must be considered when combining on a zone. Kitchens, sun rooms and rooms with large window areas have different needs from family rooms, bathrooms and bedrooms, for example. Entry areas will have different responses because of the influx of cold air as doors are opened. Carpet acts as an insulator, requiring higher water temperature to the tubing. Tile, on the other hand, is a heat conductor and requires lower supply water temperature. Both have different needs from wood or linoleum. Bedrooms should be zoned separately from high usage living areas, for example.
t Finished flooring (tile, carpet, wood, etc.) should have similar R-values
Zone valves or valve actuators allow independent operation of zones. This provides a smarter, more adaptive system. Even the best designed radiant heating system may cause uncomfortable space conditions if the space thermostat can't regulate the heat input to the space. With AlumiPex nickel-plated brass manifolds, optional valve actuators (2-wire or 4-wire) are available. Use zone valves or valve actuators whenever possible, with the exception of some constant circulation applications. Some zones of constant circulation systems should never have the flow stopped for example, zones heating warehouse spaces adjacent to loading dock doors. (Keep the water moving in these zones to reduce the potential for freeze-up should the heating source be off while the loading doors are opened.) When using constant circulation with zone valves or valve actuators, install a by-pass pressure regulator in the piping to provide a water path should all zones close for a time (see Figure 65). This will protect the circulator from cavitation caused by high head/low flow operation. Use 4-wire valve actuators to allow the actuators to signal the heating system of the need for heat. For spaces with multiple tubing circuits, use one "master" 4-wire valve actuator on one of the circuits, with 2-wire zone valve actuators on the remaining circuits (as shown in the examples at the end of this Guide). Try to combine small zones as slave zones to larger ones to prevent a small zone from being the only heat zone during a call for heat to the boiler. (Using a buffer tank will also help to reduce cycling of the boiler during light loads.)
15
IV
Combining circuits on manifolds
Zoning . . .
continued
When combining radiant circuits on manifolds, make sure the supply temperature requirements of the connected circuits are similar (maximum 10 F difference in design temperature). If circuit lengths vary by more than 10% from one another, provide means for flow balancing, preferably AlumiPex Manifolds with integral valves plus AlumiPex Flow Indicators. Suggestions for combining circuits at manifolds
t Combined flow rate of all connected circuits on any manifold no greater than
12 gpm.
t Locate manifolds centrally to the heated spaces to reduce leader lengths. t Limit leader length to approximately 50 feet, using multiple manifolds in
different locations if necessary to accomplish this.
t Use a zone valve (or valve actuator) on each circuit to allow adaptive control.
See Figures 16 and 17 for typical uses of zone valves and valve actuators. These diagrams also show the use of multiple manifolds either where needed because of the zone size or because multiple temperatures (differing by more than 10 F) are required on the same or multiple zones.
t When using zone valves with constant circulation systems, install by-pass
pressure regulator between manifold supply and return to provide a flow path for the circulator when all zone valves are closed.
Ensure that the control circuit transformer is large enough for the connected zone valves (or valve actuators) and controls. The rule of thumb is to allow 10 va plus 6 va for each connected AlumiPex manifold valve actuator. See Figure 15, below, for suggested sizing. Be sure to add capacity for controls not considered below, such as other types of zone valves. The AlumiPex manifold valve actuator is available ONLY with a 24 VAC coil. Figure 15 Suggested control circuit transformer sizing when using AlumiPex manifold valve actuators
16
4-wire actuator
2-wire actuator
17
IV
Figure 17a
Zoning . . .
continued
t One zone per manifold t One or more tubing loops per zone t Loop lengths uniform within 10% Use a manifold without integral valves. Tubing loop lengths should be similar; i.e., lengths should not vary more than 10% otherwise, use a manifold with integral valves to allow flow balancing. Use a zone valve to regulate flow, as shown.
Return
Zone valve Supply End switch wiring (to boiler, IPC, etc.)
t One zone per manifold t One or more tubing loops per zone t Loop lengths vary more than 10% Use manifolds with integral valves. Tubing lengths vary more than 10%, so the integral valves are needed to allow flow balancing. The optional flow indicators shown are recommended because they simplify balancing and reduce time required.
Thermostat
Return
Zone valve Supply End switch wiring (to boiler, IPC, etc.)
t t t t
Multiple rooms per zone Multiple temperatures needed One or more tubing loops per manifold Loop lengths uniform within 10%
Thermostat
Return
Return
Use manifolds without integral valves. If design supply temperature for connected loops varies more than 5F, provide separate manifold(s) as needed. Tubing loop lengths should be similar; i.e., lengths should not vary more than 10% otherwise, use a manifold with integral valves to allow flow balancing. Use flow indicators to simplify balancing and reduce time required.
Zone valve Supply Supply End switch wiring (to boiler, IPC, etc.)
Zone valve
Temp 1
Temp 2
t t t t
Multiple rooms per zone Multiple temperatures needed One or more tubing loops per manifold Loop lengths vary more 10%
Thermostat
Return
Return
Same as above, except use manifolds with integral valves to allow balancing flow. Use flow indicators to simplify balancing and reduce time required.
Zone valve Supply Supply End switch wiring (to boiler, IPC, etc.)
Zone valve
18
t Multiple zones per manifold t One or more tubing loops per zone
Thermostat Zone 1
Thermostat Zone 2
Use a manifold with integral valves. Provide a 4-wire actuator for each zone plus 2-wire actuators as needed for additional loops on the same zone. If tubing loop lengths in a zone differ by more than 10%, provide flow indicators to simplify balancing and reduce time required.
4-wire actuator
RETURN
Return
2-wire actuator
SUPPLY
Zone 1
Supply Zone 2
t t t t
Multiple rooms per zone Multiple temperatures needed One or more tubing loops per zone Loop lengths vary more than 10%
Thermostat Zone 1
Thermostat Zone 2
Use manifolds with integral valves. If design supply temperature for connected loops varies more than 5F, provide separate manifold(s) as needed. Provide a 4-wire actuator for each zone plus 2-wire actuators as needed for additional loops on the same zone. If tubing loop lengths in a zone differ by more than 10%, use manifolds with integral valves and provide flow indicators to simplify balancing and reduce time required.
4-wire actuator
RETURN RETURN
Return
2-wire actuator
Return
Zone valve
SUPPLY
Zone 1
SUPPLY
Supply
Temperature B
Alternate arrangement for loop lengths all within 10% of one another
RETURN
Return
Zone valve
SUPPLY
Supply
Temperature B
19
V
Outdoor reset
Figure 18 Typical outdoor reset curves Notice that supply water temperature drops as outdoor temperature rises. Outdoor reference temperature is usually 70 F, but can be changed on the IPC Injection Pump Control if needed. Supply water temperature will equal the outdoor temperature when the outdoor temperature reaches the reference temperature. This is the point at which there is zero heat loss, so no heat will be added to the space. The reset ratio is the change in supply water temperature for each degree change in outdoor temperature. To calculate the right ratio, determine the supply temperature needed at the ODT (outdoor design temperature) for the location. For a 70F outdoor reference, the ratio is: R = (Supply temp -70)/(70-ODT).
190
R=
R=1.5
(1.5 to 1 Ratio)
160
where 70 = Outdoor reference temperature (point of no heat requirement) ODT = Outdoor design temperature for the location Supply temp = water supply temperature needed at outdoor design temperature
R=1
(1 to 1 Ratio)
130
R=0.67
(1 to 1.5 Ratio)
100
70 70 50 30 10 -10
Outdoor temperature
Part Number 650-000-240/1098
20
Constant circulation
Constant operation of the distribution circulator throughout the system reduces temperature swings in the floor and the heated space. Consider using constant circulation for wood floor applications because it will reduce thermal stressing of wood flooring. Use constant circulation on zones supplying heat to warehouse areas adjacent to load dock doors. With constant circulation in the tubing, the possibility of freeze-up is reduced, even for times when the door is open and the boiler is off. This is because the circulating water can take stored heat from other floor areas to replace the high heat loss near the door.
Summary
In general, the best performance for the radiant system will come from using outdoor reset with zone valves on each zone. With the outdoor reset control correctly adjusted, and flow rates and supply temperatures for each zone set properly, it will probably not be necessary to set the circulator for constant operation because the matching of heat input to heat loss will keep the circulator on most of the time anyway.
21
VI
Power
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
System Pump
Boiler
The Weil-McLain IPC Injection Pump Control is microprocessorbased, and is designed to control temperatures (system supply and boiler return) by providing variable speed output to an injection pump.
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
The IPC can either maintain a fixed radiant supply temperature - Fixed Temperature system - or can vary the radiant supply temperature based on outdoor temperature Outdoor Reset system. The IPC control logic provides PID control/ response methodology; i.e., the control regulates its reaction to a temperature change based on how fast as well as how much the system responds.
POWER 120 VAC Supply temp Call for heat (24 vac or 120 vac signal not used when indoor sensor is installed)
The IPC also provides 120 VAC for an on/off heating system pump. For added flexibility, the control can interface with a zone controller or accept the inputs from an indoor temperature sensor.
Injection pump
System pump
Zone control
OR
Indoor sensor
Outdoor sensor
Boiler
22
Adjusting the starting point of the heating line is sometimes referred to as parallel shifting the line. Figure 20 shows the results of shifting a typical heating curve. Figure 20 Heating curve changes with changes in starting point temperature
80, 80
70, 70
F 80 0, f8 to oin F gp 0 tin ,7 tar 70 s f or to ef oin urv F gp C 60 rtin 0, sta f6 o for int rve po Cu ng rti sta for rve Cu
Reset ratio
Reset ratio is the slope of the heating line. The heating line shifts with the starting point temperature.
Starting point
Starting temp shifts along this line when being adjusted.
60, 60
Outdoor temperature
Part Number 650-000-240/1098
23
VI
IPP panels
Long term protection - Boiler return water protection is fixed by the IPC, unlike manual by-pass arrangements,
which can be defeated by incorrect adjustment of balancing valves. Manual by-pass systems cannot be applied effectively when outdoor reset is desired.
IPP components
The heart of the IPP is the Weil-McLain IPC Injection Pump Control. (This control can be also be used to control a field-supplied injection pump and heating system pump.) Included with the IPP are sensors for heating system water, boiler return water and outdoor temperature. The IPP-150 is factory packaged with both the injection pump, 1, and the heating system pump, 2, pre-piped and pre-wired on the common panel. Also included is a memory stop set manual balancing valve used to adjust the pressure drop in the injection pump circuit, thus providing accurate control even at low injection flow rates.
Energy efficiency
The IPC, combined with injection mixing, allows water supply temperature regulation to be "matched" to radiant heating system response by adjusting the settings of the reset ratio and starting temperature. This pays off in reduced energy usage because room temperature swings will be reduced - particularly when compared to fixed temperature control provided by most mixing valve systems. Using the indoor sensor or zone control option could also reduce heating energy usage due to the improved responsiveness to room temperature. Injection mixing does not introduce a head loss in the primary or distribution circuits, whereas a mixing valve
IPP advantages
When evaluating alternatives for temperature regulation in radiant heating systems, consider the advantages of the IPC Injection Pump Control and IPP Injection Pump Panel
Simplicity
Versatility
temperature regulation for the radiant heating circuit as well as the boiler return water. The IPP includes the secondary (heating) circuit pump as well as the operating control and the injection pump.
The IPC provides outdoor reset capability (more difficult and costly to accomplish when using mixing valves). To obtain outdoor reset with mixing valves, motorized valves must be used. In addition, an outdoor reset controller or electronic control must be added. The IPC allows future modifications, such as changing to zone control or indoor temperature sensors when system performance indicates the need.
24
25
VII
first secondary circuit and at least 20 F higher than highest of any other required secondary supply temperature.
Rule 2
Table 2 in this Guide for the minimum temperature needed at the IPP-150 Injection Pump Panel, based on Btuh load and radiant circuit return water temperature. To calculate a flow rate when you know the temperature drop and heat load Equation 1 Flow rate, GPM = Btuh / (K1 x DT)
where DT is the temperature drop K1 = 494 for water; 449 for 50/50 glycol/water
Use Equation 1 or Table 1 to find the minimum flow rate that will ensure return water to the boiler at no less than 140 F. The Btuh value is the total of all secondary heating loads. Determine maximum temperature drop DT = Supply temperature - 140 F Select K1 (494 for water; 449 for 50/50 glycol) Calculate minimum flow rate from Equation 1 Minimum flow rate = Btuh/(K1 x DT); or use Table 1 to select the minimum flow for this temperature drop. The primary loop flow rate must be no less than this value. A lower flow rate would cause a greater temperature drop, and the return water to the boiler could be low enough to cause condensation or thermal shock.
If you know the flow rate and want to find the temperature drop (or rise) Equation 2 DT = Btuh/(Flow rate x K1)
where DT is the temperature drop K1 = 494 for water; 449 for 50/50 glycol/water Flow rate is in GPM
For an initial estimate, assume a supply temperature no lower than the temperature required at the
Find a flow rate which will ensure each secondary circuit the minimum supply water temperature needed. Assume a trial flow rate equal to the minimum flow rate determined in Step 2. Calculate the temperature drop caused by the first secondary circuit using the assumed flow rate in Equation 2. Subtract this temperature drop from the primary loop supply temperature to determine the supply temperature available to the next secondary circuit. Then calculate the temperature drop caused by this secondary circuit and subtract the number from the primary loop temperature to determine the temperature available to the third secondary circuit. Repeat this process for the entire system to verify that each secondary circuit will receive the minimum required water temperature. If the assumed flow rate results in one or more secondary circuits not receiving adequate supply water temperature, increase the initial primary supply temperature or increase the flow rate, or both, until the selected flow rate and temperature satisfy both Rule 1 and Rule 2.
Part Number 650-000-240/1098
26
Table 1 Minimum water only (not glycol) flow rates use this table to find the minimum flow rate required for a given maximum temperature drop, F
2
2.0 4.0 5.1 10.1 15.2
4
1.0 2.0 2.5 5.1 7.6
6
0.7 1.3 1.7 3.4 5.1 6.7 8.4
8
0.5 1.0 1.3 2.5 3.8 5.1 6.3 7.6 8.9
10
0.4 0.8 1.0 2.0 3.0 4.0 5.1 6.1 7.1 8.1 9.1
15
0.3 0.5 0.7 1.3 2.0 2.7 3.4 4.0 4.7 5.4 6.1 6.7 8.1
20
0.2 0.4 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.6 5.1 6.1 7.6 9.1
25
0.2 0.3 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.9 6.1 7.3 8.1
30
0.1 0.3 0.3 0.7 1.0 1.3 1.7 2.0 2.4 2.7 3.0 3.4 4.0 5.1 6.1 6.7 8.4
40
0.1 0.2 0.3 0.5 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 3.8 4.6 5.1 6.3 7.6
50
0.1 0.2 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.4 3.0 3.6 4.0 5.1 6.1 8.1
60
0.1 0.1 0.2 0.3 0.5 0.7 0.8 1.0 1.2 1.3 1.5 1.7 2.0 2.5 3.0 3.4 4.2 5.1 6.7 8.4
70
0.1 0.1 0.1 0.3 0.4 0.6 0.7 0.9 1.0 1.2 1.3 1.4 1.7 2.2 2.6 2.9 3.6 4.3 5.8 7.2
80
0.1 0.1 0.1 0.3 0.4 0.5 0.6 0.8 0.9 1.0 1.1 1.3 1.5 1.9 2.3 2.5 3.2 3.8 5.1 6.3
90
0.0 0.1 0.1 0.2 0.3 0.4 0.6 0.7 0.8 0.9 1.0 1.1 1.3 1.7 2.0 2.2 2.8 3.4 4.5 5.6
100
0.0 0.1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.5 1.8 2.0 2.5 3.0 4.0 5.1
50.6 25.3 16.9 12.7 10.1 60.7 30.4 20.2 15.2 12.1
75.9 38.0 25.3 19.0 15.2 10.1 91.1 45.5 30.4 22.8 18.2 12.1
150,000 151.8 75.9 50.6 38.0 30.4 20.2 15.2 12.1 10.1
200,000 202.4 101.2 67.5 50.6 40.5 27.0 20.2 16.2 13.5 10.1
250,000 253.0 126.5 84.3 63.3 50.6 33.7 25.3 20.2 16.9 12.7 10.1
TIP
If the required Btuh is not listed in the table, you can add multiples together. For example 300,000 Btuh is 50,000 plus 250,000 so you could add the flow rate for 50,000 to the flow rate for 250,000 to determine the flow for 300,000 Btuh.
27
VII
Primary circuit flow rate calculation example, Figure 22
Secondary circuit 1 requires 180 F, so the primary loop supply temperature must be at least 180 F. Secondary circuit 2 requires 180 F, the highest of the remaining circuits. Add 20 F to this for an initial estimate of the primary loop supply temperature, T1, of 200 F . Determine the temperature drop in the primary loop if the water returns to the boiler at the minimum allowable temperature of 130 F DT = 200 F - 130 F = 70 F. Total heating load, all branches = 25,000 + 40,000 + 35,000 = 100,000 Btuh Determine minimum flow rate from Equation 1 Minimum flow rate = 100,000/(494 x 70) = 2.89 GPM (or 2.9 GPM if taken from Table 1.) The primary loop flow rate must be at least 2.89 GPM to satisfy Rule 1. Assume a flow of 2.89 GPM (from Step 2). Temperature drop due to Branch 1 DT = 25,000/(494 x 2.89) = 17.5 F. T2 = T1 - 17.5 F = 200 F - 17.5 F = 182.5 F. This exceeds the minimum required temperature at branch 2 of 180 F, so the flow rate is acceptable for branches 1 and 2. Continue checking for branch 3. Calculate the temperature drop caused by branch 2 DT = 40,000/(494 x 2.89) = 28.0 F. T3 = T2 - 28 F = 185 F - 28 F = 157 F. This exceeds the minimum temperature required by branch 3, so the flow rate of 3.37 GPM is acceptable for all three branches. Provide a flow rate in the primary circuit of at least 2.89 GPM. Provide a supply water temperature of at least 200 F. Note that, if the load in branch circuit 1 had been 60,000 Btuh, for example, the flow rate of 2.89 GPM would not have been high enough to provide branch circuit 2 with water at 180 F. The temperature drop due to branch 1 would have been 60,000/(494 x 2.89) = 42 F. And the supply temperature, T2, to branch 2 would have been 200 F - 42 F = 158 F. To find the necessary flow rate the maximum allowable temperature drop due to branch 1 is 20 F in order to provide 180 F to branch 2. (Because DT = 200 F - 180 F = 20 F.) So, from equation 1, the minimum flow rate would be 60,000/(494 x 20) = 6.07 GPM. (This would be 6.1 GPM if taken from Table 1.)
Part Number 650-000-240/1098
Step 2
Step 3
Selection
28
LOAD
40,000 Btuh
Secondary pump
2
Flow/check valves
LOAD
25,000 Btuh
Secondary pump
LOAD
35,000 Btuh
1
Flow/check valves
Secondary pump
3
Flow/check valves
180 F min
180 F min
140 F min
T1
T2
T3
T4
Fill
130 F min
Secondary pump
Flow/check valves
Rule 1 T4 no less than 130 F Rule 2 T1, T2 and T3 no less than required at branches 1, 2 and 3, respectively.
Flow/check valves
BOILER
29
VII
Injection pump flow rates
When applying an IPP-150 Injection Pump Panel, ensure that the supply water temperature available at the panel will be no less than the temperatures given in Table 2 If the supply temperature is lower than the number shown, the panel will not be able to deliver enough hot water to the radiant circuit to achieve the heat load required. (Table 2 is based on a full load flow rate in the
injection riser of 4.5 GPM.)
Heat Minimum supply temperature to IPP-150 Injection Pump Panel Load with radiant circuit return temperature ( F) of (MBH) 90 100 110 120 130 140 150 160
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 94 99 103 108 112 117 121 126 130 135 139 144 148 153 157 104 109 113 118 122 127 131 136 140 145 149 154 158 163 167 114 119 123 128 132 137 141 146 150 155 159 164 168 173 177 124 129 133 138 142 147 151 156 160 165 169 174 178 183 187 134 139 143 148 152 157 161 166 170 175 179 184 188 193 197 144 149 153 158 162 167 171 176 180 185 189 194 198 203 207 154 159 163 168 172 177 181 186 190 195 199 204 208 164 169 173 178 182 187 191 196 200 205 209
30
Secondary circuit Domestic water circuits flow rates Determine the flow rate for domestic water heating based on the recommended flow rate given by
the water heater manufacturer. Weil-McLain PLUS and GOLD Plus water heater literature includes this information.
Baseboard circuits
The flow rate for baseboard circuits is usually based on a 20 F drop and can be calculated using Equation 1 or read directly from Table 1.
Radiant circuits
Determine the flow rate for the radiant loops using the AlumiPex Radiant Expert computer program or AlumiPex Design Guide (when available). As a rule of thumb, the flow rate per loop will generally be 1 gpm or less for tubing (higher for larger tubing). The radiant circuit pump must deliver water to all of the circuits piped off of the manifold. So the total flow rate required from the pump is the sum of the flows in all connected circuits. The flow rate may also be determined from the desired temperature drop and heat load, using Equation 1 or Table 1. Estimate the total flow for a radiant heating circuit by assuming some typical conditions Temperature drop = 10 F. Fluid in circuit is water (no glycol).
Heat load = 15 Btuh per square foot. Loop length 300 feet of tubing. Tubing layout at 12 inches on center. Water only (no glycol). Temperature drop = 10 F, from 100 F to 90 F.
To determine how many square feet of floor the 300 feet of tubing will cover, consider that, at 12 inch center to center tube spacing, there will be one linear foot of tubing to each square foot of floor space. (For any other tubing spacing, divide 12 by the tube spacing in INCHES to find the number of feet of tubing per square foot of floor. For example, 6 inch tube centers would require two linear feet of tubing per square foot of floor; i.e., 12/6 = 2.) Since there is 1 linear foot of tubing per square foot for this example of 12 inch centers, the 300 foot tubing loop will cover 300 square feet of floor. The loading is 15 Btuh per square foot of floor, so the total load of the loop is 300 feet times 15 Btuh per square foot, or 4,500 Btuh total.
Use Equation 1 (or Table 1) Flow rate = 4,500/(495 x 10) = 0.91 GPM.
31
VIII
Add to the piping head loss the head losses for boilers, water heaters, baseboard, heat exchangers or any other components of this sort in the circuit. Refer to the instructions or literature on these components for the estimated head loss. TIPS Estimate " baseboard as if it were just a straight length of " pipe. For cast iron boilers estimate a head loss of 1 to 2 feet for residential boilers and 2 to 5 feet for commercial boilers.
The equivalent length depends on pipe size. So begin by estimating the TEL as 1.5 times the length of the piping. In fact, for small systems, this estimate is usually adequate for the head loss calculation. This is because the circuit lengths are relatively simple and short, and the head losses are low. Example: if the circuit contains 130 feet of straight pipe, estimate the TEL as: TEL = 1.5 x 130 = 195 feet.
If the head loss based on the trial pipe size is acceptable (usually between 5 and 15 feet), check the actual equivalent length of the circuit using the pipe size you selected. Obtain the equivalent lengths of all valves and fittings from Table 5. If the TEL is different from your estimate, use the new, calculated, TEL in the head loss formula, Equation 4. If the result is acceptable, use the required flow and calculated head loss to select a pump. If not, increase (or decrease) the pipe size as indicated and redo the calculation.
Glycol/water systems
For systems filled with propylene glycol/water, first do the calculations as if the system were filled with water only. Then apply the correction factors given in Table 4. You will see from the table that the flow rate for glycol/ water must be from 14% to 16% higher than water only to achieve approximately the same heat transfer. The head loss for any give flow rate will be higher for the glycol/ water mixture than for water only.
Procedure
Select a trial pipe size from Table 3 based on the design flow rate, in GPM, for the circuit. For any given copper
32
c
Pipe ID 0.472 0.610 0.787 1.024 Correction @ 100 F 1.095 1.095 1.095 1.095 Correction @ 180 F 0.930 0.930 0.930 0.930
a
3.9087 1.1507 0.3379 0.0865
b
1.750 1.750 1.750 1.750
c
Correction @ 100 F 1.095 1.095 1.095 1.095 1.095 1.095 1.071 1.071 Correction @ 180 F 0.930 0.930 0.930 0.930 0.930 0.930 0.947 0.947
a
1.588 0.295 0.085 0.0324 0.0146 0.00397 0.00113 0.000478
b
1.750 1.750 1.750 1.750 1.750 1.750 1.812 1.812
Velocity @ Min. fps 1.50 1.50 1.50 1.50 1.50 1.50 2.37 2.67
Velocity @ Max. fps 4.00 4.00 4.00 4.00 4.00 4.00 5.98 6.72
1 1 1 2 2 3
c
Correction @ 100 F 1.087 1.087 1.087 1.087 1.087 1.087 1.053 1.053 Correction @ 180 F 0.936 0.936 0.936 0.936 0.936 0.936 0.960 0.960
a
0.378 0.140 0.0595 0.0225 0.0130 0.00538 0.00105 0.000366
b
1.771 1.771 1.771 1.771 1.771 1.771 1.858 1.858
Velocity @ Min. fps 1.50 1.50 1.50 1.50 1.50 1.50 2.30 2.63
Velocity @ Max. fps 4.00 4.00 4.00 4.00 4.00 4.00 5.66 6.47
1 1 1 2 2 3
Table 4 Correction factors when using 50/50 glycol/water in place of water only
33
VIII
Table 5
Equivalent lengths, feet of pipe, for common copper and steel valves and fittings
1.00 0.50 0.30 2.00 n/a 0.20 15.00 3.10 1.90 2.00 n/a 1.10 2.00 0.75 0.40 3.00 70.00 0.25 20.00 4.70 2.20 3.00 83.00 2.00
1
2.50 1.00 0.45 4.50 23.50 0.30 25.00 5.30 4.30 4.50 54.00 2.70
1
3.00 1.20 0.60 5.50 25.00 0.40 36.00 7.80 7.00 5.50 74.00 2.00
1
4.00 1.50 0.80 7.00 23.00 0.50 46.00 9.40 6.60 6.50 57.00 2.70
2
5.50 2.00 1.00 9.00 23.00 0.70 56.00 12.50 14.00 9.00 177.00 4.50
2
7.00 2.50 0.50 12.00 n/a 1.00
3
9.00 3.50 1.00 15.00 n/a 1.50
4
12.50 5.00 1.00 21.00 n/a 2.00
1.55 0.83 1.00 3.10 2.59 2.06 1.10 1.40 4.10 3.43
1
2.62 1.40 1.80 5.30 4.37
1
3.45 1.84 2.30 6.90 5.75
1
4.03 2.15 2.70 8.10 6.71
2
5.17 2.76 3.50 10.30 8.61 2.60 10.30 1.38 58.60 25.80 17.20 7.75
2
6.17 3.29 4.10 12.30 10.30 3.10 12.30 1.65 70.00 30.90 20.60 9.26
3
7.67 4.09 5.10 15.30 12.80 3.80 15.30 2.04 86.90 38.40 25.50 11.50
4
10.10 5.37 6.70 20.10 16.80 5.00 20.10 2.68 114.00 50.30 33.60 15.10
34
(1 or 3) is the same as the pressure drop through branch 2. When the balancing valves are set properly, the head loss across all branches will be approximately 7.0 feet water column. The total flow required of the pump is 5.5 GPM (sum of all three branch design flows). The pump head required of the pump is the sum of the highest branch design head loss plus the head loss in the distribution piping, or 3.0 feet plus 7.0 feet = 10.0 feet.
If the balancing valves were not closed down on branches 1 and 3, they would receive higher than their design flows and branch 2 would receive less than design flow because the fluid flow will always seek the path of least resistance. The balancing valves are closed off until the head loss through the branch
Balancing valves
Distribution piping - Head loss = 3.0 feet Flow = 1.5 + 2 + 2 = 5.5 GPM
The branch with the highest design head loss is number 2, where the head loss at design flow of 2 GPM is 7.0 feet water column.
35
VIII
manifold. The head losses for the other loops must be made equal to this highest head loss by closing down on the manifold valves. This is how the system is balanced. (Glycol data is for propylene glycol/water mixtures in the ratios shown.) Equation 5, Head loss in AlumiPex feet head = K2 x L (feet) x GPM1.75
where L is the total length of tubing in a loop and K2 is a constant from the table 6, below
Tubing 0.0428 0.0391 0.0364 0.0529 0.0466 0.0492 0.0617 0.0547 0.0650
Tubing 0.0126 0.0115 0.0107 0.0154 0.0137 0.0145 0.0181 0.0161 0.0191
Tubing 0.00370 0.00338 0.00314 0.00455 0.00402 0.00425 0.00533 0.00473 0.00562
1 Tubing 0.000947 0.000865 0.000804 0.001164 0.001030 0.001089 0.001365 0.001211 0.001438
Loop 2 185 square feet of floor space; total leader length needed = 20 feet.
Requires 185 x 1.33 = 246 feet of tubing for space plus 20 feet = 266 feet. Add 5% allowance = 13 feet. Total length of loop = 279 feet.
Loop 3 200 square feet of floor space; total leader length needed = 20 feet.
Requires 200 x 1.33 = 266 feet of tubing for space plus 20 feet = 286 feet. Add 5% allowance = 14 feet. Total length of loop = 300 feet.
Loop 4 150 square feet of floor space; total leader length needed = 30 feet
Requires 150 x 1.33 = 200 feet of tubing for space plus 30 feet = 230 feet. Add 5% allowance = 12 feet. Total length of loop = 242 feet.
36
TUBING LOOPS
Supply manifold
Distribution piping - 1 copper tubing, type M Total equivalent length = 175 feet
37
VIII
AlumiPex tubing flow rate calculation example, Figure 24, continued
For the example in Figure 24: Loop 1 Loop 2 Loop 3 Loop 4 Total Heat load = 15 x 175 = 2625 Btuh; Flow rate = 2625/(494 x 13) = 0.41 GPM Heat load = 15 x 185 = 2775 Btuh; Flow rate = 2775/(494 x 13) = 0.43 GPM Heat load = 15 x 200 = 3000 Btuh; Flow rate = 3000/(494 x 13) = 0.47 GPM Heat load = 15 x 150 = 2250 Btuh; Flow rate = 2250/(494 x 13) = 0.35 GPM Total flow rate for pump = 0.41 + 0.43 + 0.47 + 0.35 = 1.66 GPM.
Determine the head loss for each AlumiPex tubing loop at design flow rate using Equation 5 (using the K2 value for tubing and 100 F, since the water ranges from 105 F to 92 F). For these conditions, the K2 value is 0.0428. Loop 1 Head loss = .0428 x 287 x 0.411.75 = 2.58 feet Loop 2 Head loss = .0428 x 279 x 0.431.75 = 2.73 feet Loop 3 Head loss = .0428 x 300 x 0.471.75 = 3.43 feet (highest head loss) Loop 4 Head loss = .0428 x 287 x 0.351.75 = 1.96 feet Note that the manifold valves would have to be partially closed on loops 1, 2 and 4 to cause the head losses for these loops to match that of loop 3, the branch with the highest loss.
Determine the pipe size and head loss in the distribution piping. The flow in the distibution piping will be 1.66 GPM. Find a pipe size in Table 3 which is suitable for this flow. The flow is within the range of copper tubing, so select this as the pipe size. The example system has (12) 90-degree elbows (not shown) and (2) gate valves plus 150 linear feet of piping. Find the equivalent lengths of these fittings for copper from Table 5 (1.00 feet per elbow; 0.20 feet per gate valve). The TEL for the distribution piping is TEL = 150 + (12 x 1.00) + (2 x 0.20) = 162 feet. The head loss for the distribution piping using copper tubing, at 1.66 GPM would be (from Table 3) Head loss = (162/100) x 1.588 x 1.661.75 = 6.25 feet.
Determine total required head for the pump The highest loop head loss for any of the AlumiPex loops is 3.43 feet. Add this to the distribution piping loss of 6.25 feet, for a toal head loss of 9.68 feet.
Solution Select a pump capable of 1.66 GPM at a head loss of 9.68 feet.
Note
If the loading required of a tubing loop requires too high a flow rate (or pressure drop), consider increasing the tube diameter, provided the flow rate in the tubing is within the recommended flow rate range (between the minimum and maximum recommended flow rates).
38
IX
Selecting pumps
Method 1 Calculate flow rate and head loss - select pump from pump curve
The design flow rate and head loss for a circuit are called the design point. Calculate the design point using the procedures given in this guide. Then select a pump whose curve passes close to (preferably slightly above or on the design point). See Figure 25. Figure 26 combines the pump curves for some common Taco, Grundfos and Bell & Gossett pumps. Use Figure 26 or another pump curve to select the pump required. Apply Equation 6 for several flow rates in the desired range. Then draw these points on the pump curve and connect with a line as shown in the pump curve segment in Figure 25, below. The design flow rate for the example circuit is 1.66 GPM and the design head loss is 9.68 feet. The system points used in Figure 25 are: Example The previous example on pages 36 through 38 resulted in a design point of 1.66 GPM at a head loss of 9.68 feet (when using AlumiPex tubing with distribution piping). Find a pump (or pumps) using Figure 26 which could accomplish this design point. The Taco 007 pump could provide 1.7 GPM at a head of approximately 10.5 feet. This is probably an acceptable pump selection. The Taco 0010 pump could provide 1.7 GPM at a head of approximately 11.5 feet. This would probably be an acceptable selection as well. None of the other pump curves passes close to the design point. To determine what each of these selected pumps would actually do on the circuit, draw a system curve on the pump curve. A system curve is a line which represents what the head loss in the system will be as the flow rate changes. Flow rates below the design point will cause lower head losses. Flow rates above the design point will cause higher head losses. The head loss at any flow rate can be estimated from the design point flow rate by Equation 6
Head loss = Design head loss x (Flow rate/Design flow rate)1.75
where Flow rate is the rate at which the head loss is to be estimated Design head loss and Design flow rate are the known Design Point data
1.66 GPM where pressure drop = 9.68 feet (design point) 2 GPM where pressure drop = 9.68 x (2/1.66)1.75 = 13.4 feet 1 GPM where pressure drop = 9.68 x (1/1.66)1.75 = 4.0 feet
The flow rate and head loss for any pump is the point at which the system curve crosses the pump curve. The Taco 007 pump would provide about 1.8 GPM at 10.6 feet. The Taco 0010 pump would provide about 1.9 GPM at 11.5 feet.
0012
System curve
0010 007
Design point
The system curve will always pass through the design point.
39
IX
Figure 26
Pump curves for some typical residential/light commercial circulators (Taco 007, 0010, 0011, 0012 and 0014; Grundfos 15-42, 26-64 and 43-75; B & G NRF-22, PL-30 and PL-50) See Appendix for pump curve equations.
30
0011
25
Feet head
26-64
20
PL-30
15
43-75
10
0010 007
0012
PL-50
5
15-42 NRF-22
0014
0 0 10 20 30 40 50
40
Method 2 Calculate flow rate and select pump from quick selector curves
Figures 27 through 30 are quick selector curves for selecting pumps based on a known flow rate and circuit length. The pumps included in these curves are Taco 007, 0010, 0011, 0012, 0014. Grundfos 15-42, 26-64, 43-75. Bell & Gossett NRF-22, PL-30, PL-50. (See Appendix for pump curve equations.) If you can't find a good pump selection, try another pipe size. You can refine and verify your selection by calculating the actual TEL for your circuit using the equivalent length data in this Guide.
Example:
A circuit with 300 linear feet of piping; heating load 200,000 Btuh; using water from 180 F to 160 F. Estimate the TEL at 1.5 times 300, or 450 feet. Using Equation 1, the required flow rate for a 20 F drop would be: Flow rate = 200000/(494 x 20) = 20.2 GPM
Use these curves only when the pipe diameter is the same throughout the circuit being analyzed. This method will work well for determining both pipe size and pump selection for primary circuits and baseboard heating secondary circuits. To select a pump using this method Calculate the required flow rate based on the heating load (Btuh) and the desired temperature drop using Equation 1: GPM = Btuh/(494 x DT). Select a trial pipe size using Table 3 that is, a pipe size for which the flow rate falls between the minimum and maximum recommended. Determine the linear feet of piping expected for the circuit. Multiply this number by 1.5. The result is your approximate TEL (total equivalent length) for the circuit. Select the Figure from Figures 27 through 30 for the pipe size you have selected. Select the pump which can deliver the flow rate and TEL you need.
From Table 3, either 1 or 2 copper pipe would be usable (though the pressure drop would be higher in 1 pipe). Use 1 copper pipe for the trial size. From Figure 30, with 1" copper pipe at a TEL of 450 feet, a Taco 0011 or 0014 would deliver about 19.5 GPM at 450 feet TEL. Or a B & G model PL-50 would deliver about 21.3 GPM. At 19.5 GPM, the temperature drop would be (from Equation 2) 200000/(494 x 19.5) = 20.8 F. So the Taco 0011 or 0014 would probably be an adequate selection.
Note, from Figure 30, that a model 0010, 0011, PL-30 or 26-64 would be the likely choices if the pipe size were increased to 2 copper pipe. These pumps would deliver about 25 GPM. Verify the pump selection by doing a complete calculation of the TEL, using the data in this Guide.
41
IX
43-75
2.0
PL-30 0014
1.5
1.0
0012
0.5
0 100 200 300 400
007
500 600 700 800 900 1000
6 5 4 3 2 1
0 100 200 300 400
500
600
700
800
900
1000
42
Figure 28 Quick selector pump curves for 1 AlumiPex tubing and copper tubing
43-75 PL-30 0014 26-64 NRF-22 0012 0010 15-42 007 PL-50 0011
10 9 8 7 6 5 4 3
0 100 200 300 400 500
600
700
800
900
1000
NRF-22 PL-50
2 100
200
300
400
500
600
700
800
900
1000
43
IX
0012
0010 007
500
600
700
800
900
1000
16 15 14 13 12 11 10 9 8 7 6 100
44
300
400
500
600
700
800
900
1000
43-75
35
PL-50 0012
30
PL-30 26-64
0014
25
0011 NRF-22
20
15 100
200
300
400
500
600
700
800
900
1000
45
46
Pump location
In the following system examples, the primary circuit pump is shown mounted in the supply piping, with the expansion tank and air separator on the inlet side of the pump (with the exception of GV boiler systems). This is the preferred location for all pumps, and the only recommended location for commercial system pumps. Many packaged residential boilers are supplied with the pump on the return line to the boiler. This is acceptable for residential applications and for multiple boiler systems using residential packaged boilers. See the Caution statement below regarding location of the expansion tank and fill connection. Always connect the fill line at the expansion tank. Locate the expansion tank (diaphragm or bladder type) on the inlet side of the pump, even if the pump is mounted on the boiler return line. When using a compression tank (expansion tank in which air is exposed to the water), mount the compression tank and fill connection in the supply piping, regardless of the location of the pump. Failure to follow these guidelines could result in damage to the boiler and system components.
47
P1
Purging valves
P2
Supply temperature sensor
Manifold location A
Purge valves & air vents Valve actuators optional
Manifold location B
specific example of substituting dual mixing valves for the IPP of Figure 31a.
Prad.cdr
48
Figure 31b is an example of directly substituting a dual mixing valve configuration for the IPP panel. The piping schematics for Systems CP-2 through CP-12 in Radiant heating system examples all indicate how to substitute the mixing valve arrangement. Note the special case of System CP-4, in which two radiant circuits are supplied off of the primary circuit. When substituting mixing valves for the IPP in this case, note that only one boiler protection mixing valve is needed not two. Other piping methods are possible if designed and installed to meet the requirements of the system and the boiler used. Whatever piping method you use, it must provide control of the return water temperature to the boiler if the boiler manufacturer specifies a minimum return water temperature. The mixing valves may be either self-contained, remote bulb or motorized. If motorized, they may be operated by an electronic control, allowing outdoor reset if desired. AlumiPex manifolds are shown in the example diagrams in this Guide with and without manifold valve actuators. Use actuators when you wish to provide zone control. When using actuators and continuous operation of the pump, install a by-pass pressure regulator across the supply and return connections of the circuit. This will protect the pump from cavitation when the zone valves close off. (See Figures 65 and 67 for examples.)
2 to 4 pipe diameters
Purging valves
Manifold location A
Purge valves & air vents Valve actuators optional
When all manifolds in a circuit must receive the same temperature water, use the basic piping shown in Figure 31a or Figure 31b. For applications involving multiple manifolds that require different supply temperatures, use the piping shown in Figure 32 or Figure 33, on the following pages.
Manifold location B
Pradmv.cdr
49
Figure 32 Typical radiant circuit piping - multiple supply temperatures from single injection pump panel
is connected to a crossover bridge containing a balancing valve, item 1. This valve provides a pressure drop in the bridge to match the pressure drop through the loops connected at Manifold location B. Partially close the valve until the required flow is achieved through the Manifold location B loops. Lower temperature water is supplied to the Manifold location A loops by the mixing valve, item 2. This valve mixes cooler return water with the supply water from the crossover bridge to provide the desired temperature. (You can substitute a two-way valve combined with a manual balancing valve for the 3-way mixing valve.) Outdoor reset response If the IPC is operated in reset mode, it will reset the supply temperature at the location of the IPC supply sensor. So, the reset will be based on the supply temperature and reset curve needed for the higher temperature radiant circuit. The low temperature circuit will not be reset until the heating curve drops below the setpoint of the low temperature circuit mixing valve. Example: The high temperature circuit is set for a reset ratio of 1 and a starting point temperature of 70 F. The low temperature circuit mixing valve is set for a temperature of 100 F. The IPC supply temperature to the radiant circuits will be above 100 F except when the outdoor temperature is 40 F or higher. (Since the supply temperature is
Tsupply = Tstarting + reset ratio x (Tstarting - Toutside) = 70 F + 1 x (70 F - 40 F) = 100 F
P1
Purging valves
P2
Supply temperature sensor
Max 4 pipe diameters
2
Mixing valve
H M C
Circulator
At lower outside temperatures, the supply temperature will always be above 100 F, so no reset will be seen in the low temperature circuit.
NOTE: You can substitute dual mixing valves, piped as in Figure 3 of this Guide, for the IPP Injection Pump Panel.
50
Figure 33 Typical radiant circuit piping - multiple supply temperatures from single injection pump panel, using primary/secondary piping in radiant circuits
IPC
Injection pump control
Manifold location A
Valve actuators optional
P1
Purging valves
IPP-150
Injection pump panel
P2
1
Balancing valve Max 4 pipe diameters Max 4 pipe diameters
2
Mixing valve
H M C
Circulator
1
Balancing valve
1
Balancing valve
ing valves, piped as in Figure 3 of this Guide, for the IPP Injection Pump Panel.
Part Number 650-000-240/1098
This diagram is schematic only. It does not indicate vertical placement of components. Flow/check valves are omitted because vertical placement is unspecified. Locate flow/check valves as needed when applying.
Manifold location C
Prad3.cdr
51
XI
Domestic priority
Domestic priority means the indirect water heater receives priority over all other heating functions when the domestic
Override priority relay by connecting the TDR relay contacts across the DHW Priority relay contacts as shown below . . .
boilers only), as shown in Figure 37 and in system CP-8. The diverter valve diverts all heating water flow to the water heater when it calls for heat. The diverter valve method has a slight disadvantage over other methods shown because the pressure drop through the diverter valve reduces flow available to the system.
First-in-line priority (can be used with all boilers),
DHW2
as shown in system CP-6 through CP-7. The piping strategy of Figure 36 always provides this priority option because the supply water is taken directly from the boiler supply piping. For first-in-line priority, the heating water supply to the indirect water heater is taken before it reaches other heating sources. This isn't true priority unless the flow to the other heating applications is temporarily interrupted on a call for heat from the indirect water heater. This can be done using the IPC control and relays as shown in the corresponding wiring diagrams for systems CP-6, CP-7, and CP-9 through CP-11.
Flow interruption priority - can be applied in any of the systems CP-6 through CP-11 by using relays as shown in the wiring diagrams. When the indirect water heater calls for heat, the relay(s) stops the pumps feeding other heating applications.
120 VAC
TDR
Priority override option If the building is frequently unoccupied (weekend house, f or example), consider installing a time delay relay to prevent the possibility of extended no-heat periods should the domestic priority system fail for any reason. This relay, usually selected as a one-hour delay, can be introduced to the DHW relay circuit to allow system heating should the DHW relay remain activated longer than the time period of the relay. See Figure 34.
Part Number 650-000-240/1098
DHW1
call-for-heat disable
52
The following domestic water heating piping alternatives can be applied in most radiant heating applications. They are shown here separated from the remainder of the piping for ease of discussion.
means hot water must flow throughout the primary piping even during the summer.
Figure 36 provides a means of circulating water only
Piping strategies
The indirect water heater can be connected to the primary/secondary piping in several ways, depending on the desired operating characteristics. For conventional boilers we recommend only the methods of Figure 35 and 36. For GV boilers use only the methods of Figures 35 or 37.
Figure 35 shows the water heater connected as a secondary circuit off of the primary. You will find this
through the indirect water heater circuit during the nonheating months. Water is taken from the boiler supply and returned directly to the boiler return. The primary pump does not have to operate during domestic water heating cycles. This eliminates heat loss from the primary piping during non-heating periods. For installations in which the primary piping runs throughout the building, this method can save considerable energy. You will find this method used in systems CP-8 and CP-10.
Note re Figure 36 For systems piped with zone valve
zoning rather than circulator zoning, substitute a zone valve for the pump.
Figure 37 uses a diverting valve to switch water flow
method used in systems CP-6 and CP-7. System CP-12 uses a similar approach, but takes the secondary circuit tees from the boiler supply water before it reaches the primary loop. These systems require water to be flowing in the primary loop (or boiler supply piping for system CP-12) in order to heat the indirect water heater. This Figure 35 Water heater piped as secondary circuit
DHW outlet
flow/check valve
from the heating circuit to the domestic water heater during a DHW heating cycle. It provides domestic priority and prevents flow of hot water through the heating circuits during non-heating periods. This method is used in system CP-9. Figure 37 Diverter valve domestic water heater piping
to system return
DHW outlet
DHW outlet
Circulator
Circulator
53
XII
CP-1 CP-2
Adding a small zone of radiant heating Conventional to an existing baseboard heating system. GV boiler supplying an injection pumping panel Conventional boiler supplying an injection pumping panel Two-temperature radiant heating system using two injection pumping panels Two-temperature radiant heating system using one injection pumping panel and a mixing valve GV boiler
56 - 59
60 - 63
CP-3
Conventional
64 - 67
CP-4
Conventional
68 - 71
CP-5
Conventional
72 - 75
CP-6
Radiant heating and domestic water heating with conventional boiler - DHW Conventional as a secondary circuit Radiant heating and domestic water heating with GV boiler - DHW as a secondary circuit Radiant heating and domestic water heating with conventional boiler independent DHW operation Radiant heating and domestic water heating with GV boiler - DHW through diverting valve Radiant heating, domestic water conventional boiler GV boiler
Radiant heating Domestic hot water heating Radiant heating Domestic hot water heating Radiant heating Domestic hot water heating Radiant heating Domestic hot water heating Radiant heating Domestic hot water heating Baseboard heating Radiant heating Domestic hot water heating Baseboard heating Radiant heating Domestic hot water heating Baseboard heating
76 - 78
CP-7
80 - 83
CP-8
Conventional
84 - 87
CP-9
Conventional
88 - 91
Conventional
92 - 97
98 - 103
Conventional
104 - 109
54
Gate valve
Air separator
Mixing valve
Flow/check valve
Circulator or pump
Pressure gauge
Ball valve
Drain cock
Backflow preventer
Globe valve
Balancing valve
To expansion tank
55
XII
System CP-1 Adding a small zone of radiant heating to an (pages 58 59) existing baseboard heating system
Purpose This system shows two methods of adding a small radiant heating zone to an existing
baseboard heating system. The radiant heating zone must be small and low mass - it cannot be a slab on grade installation. Use only for small zone thin slab or suspended floor radiant plate systems.
This example is the only exception to the requirement for control of the boiler return temperature
(other than high temperature radiant applications for suspended floor heating as discussed on page 46.) Return water temperature regulation is not needed in this example because the radiant load is small and low mass, so the radiant load won't greatly reduce the return temperature.
Two alternatives to piping the radiant zone are illustrated Alternate 1a - "slave" operation The radiant branch must be connected as close to the end of the baseboard loop as possible,
to avoid reducing the water temperature (and output) to baseboards downstream.
Install the radiant branch as a secondary circuit off of the baseboard loop. This piping
method will make no change in the flow of the primary (baseboard) loop.
This piping option is called a "slave" zone because heat can be supplied to the radiant heating
circuit only when the baseboard loop pump operates. Since the baseboard zone thermostat controls the boiler and the baseboard loop pump, the radiant zone can only operate when the baseboard thermostat is calling for heat. Use this piping option when you are sure the baseboard zones will always need heat at the same times as the radiant zone.
Flow of hot water from the baseboard loop into the radiant circuit is controlled by the nonelectric thermostatic valve (mixing valve). This valve may be remote bulb, as shown, or selfcontained.
Operation - Alternate 1a On call for heat from the radiant zone thermostat, a pump relay is activated, powering the
radiant circuit pump, P2.
The boiler and baseboard loop pump will operate only when there is a call for heat from the
baseboard thermostat.
56
System CP-1
Alternate 1b - "independent" operation This option takes the radiant heating water directly across the boiler supply and return,
allowing it to operate independently of the baseboard circuit pump. You must install a flow/ check valve in the baseboard circuit if not already installed when using this option, to prevent short circuiting the flow of the radiant pump.
Use this alternative when you want the radiant zone to be capable of operation even when
there is no demand from the baseboard zones. Do not use alternate 1b with a GV boiler - flow through the boiler can only be controlled by the integral pump.
The non-electric thermostatic valve (mixing valve) regulates flow of hot water from the
baseboard circuit into the radiant circuit. This valve may be remote bulb, as shown, or selfcontained.
Operation - Alternate 1b The baseboard pump operates on call for heat from the baseboard thermostat, powered
through the pump relay. This relay also provides the call for heat signal to the boiler.
A second relay is operated by the radiant zone thermostat. On call for heat from this thermostat,
the radiant circuit pumps are activated pump P2 (boiler pump that circulates water through the crossover bridge from boiler supply to return) and pump P3 (pump that circulates water through the radiant tubing).
57
XII
Figure 39 - System CP-1 Adding a small zone of radiant heating to an existing baseboard heating system
To fill line
P1
P2
Non-electric thermostat valve (set for design water temp.)
Purging valves
Capillary
Sensor bulb
P2
Sensor bulb
P3
Boiler
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel.
58
Figure 40a - System CP-1a Slave floor heating zone schematic wiring - 24 VAC zone valve When using the optional radiant circuit pump relay, inform the owner that the thermostat only controls the pump. It cannot operate the boiler. Heat will be available to the radiant circuit only when the baseboard thermostat(s) is calling for heat. The radiant thermostat only serves the purpose of limiting the heat input to the radiant zone.
L1
H N G
B1 B2
Burner
120 VAC
Transformer 120vac/24vac
24 VAC
Boiler
C1 C2
Baseboard pump
P1
NOTE Floor heating pump, P2, can be operated by wiring in parallel with pump P1. This would eliminate the transformer, pump relay and radiant zone thermostat.
Figure 40b - System CP-1b Independent floor heating zone schematic wiring diagram
Service switch
120 VAC
L1
P3
120 VAC
24 VAC
relay
P2
Baseboard pump
P1
baseboard zone thermostat
relay
Boiler
T T H N G B1 B2
Burner
C1 C2
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. Part Number 650-000-240/1098
59
XII
(pages 62 63)
The Injection Pump Panel (IPP) includes the injection pump and radiant circuit pump. (For
applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
Radiant heating circuits System CP-1 shows two manifold locations. The same piping design can be used for multiple
manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone
thermostat or a dry contact that closes on a call for heat. Alternatively, use an indoor sensor or zone control.
60
System CP-2
The IPC is included with the IPP panel (or purchased separately when using field-constructed
injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor).
You can connect an indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback, allowing heating circuit regulation based on space temperature response.
The IPC controls the injection pump (P2) and radiant circuit pump (P3). The GV boiler
integral pump (P1) operates with the boiler (activated by the GV controls).
Use IPC dip switch 2 to set radiant circuit pump (P3) operation - DOWN for intermittent
operation, UP for continuous pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an
indoor sensor is connected to the IPC.
Operation On call for heat from a radiant zone thermostat or actuator, the IPC activates the injection
pump (P2), the radiant circuit pump (P3), and the boiler. The boiler activates the integral pump (P1), initiating flow in the primary circuit.
The IPC regulates the flow rate of the injection pump (P2), increasing flow to raise the supply
temperature, or lowering flow to reduce it.
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection
flow (reducing the temperature drop in the primary circuit).
61
XII
Figure 41 - System CP2 GV boiler supplying an injection pump panel
Air separator
Primary circuit
IPC
Injection pump control
P2
Purging valves
IPP
Safety controls (as required by local codes)
P3
Supply temperature sensor
Alternate piping
(using mixing valves)
2 to 4 pipe diameters
Cold Mixed Hot Fill Heating system pump Supply to heating system
Manifold location B
Purge valves & air vents
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 3. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
62
Reset On
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
L1
120 VAC
System Pump
Boiler
Service switch
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
These pumps are mounted and pre-wired on the IPP panel.
P3
24 VAC
Room thermostat
Room thermostat
2-wire actuator
T L
N G
P1
GV Boiler
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
63
XII
System CP-3 Conventional boiler supplying an injection pump (pages 66 67) panel
Purpose
Provide heating water to radiant circuits, using a control and injection pump that regulate radiant circuit supply temperature and maintain minimum boiler return temperature.
The primary pump can be as supplied with the boiler or purchased separately. Residential packaged boilers may have the pump mounted on the return piping at the boiler. The pump can be used in this location provided the expansion tank or compression tank and fill line are correctly located.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump. (For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
64
System CP-3
The IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using field-constructed injection mixing systems). The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response. The IPC controls the injection pump (P2) and radiant circuit pump (P3). The primary pump (P1) operates with the boiler (activated by the boiler controls). Use IPC dip switch 2 to set radiant circuit pump (P3) operation - DOWN for intermittent operation, UP for continuous pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close. indoor sensor is connected to the IPC.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an Operation
On call for heat from a radiant zone thermostat or actuator, the IPC activates the injection pump (P2), the radiant circuit pump (P3), and the boiler. The boiler activates the primary pump (P1), initiating primary circuit flow. The IPC regulates the flow rate of the injection pump (P2), increasing flow to raise the supply temperature, or lowering flow to reduce it. If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the temperature drop in the primary circuit).
65
XII
Figure 43 - System CP3 Conventional boiler supplying an injection pump panel
Fill
P1
Primary circuit
IPC
Injection pump control
P2
Purging valves
IPP
Safety controls (as required by local codes)
P3
Supply temperature sensor
Alternate piping
(using mixing valves)
2 to 4 pipe diameters
Manifold location B
Purge valves & air vents
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 3. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
66
Reset On
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
L1
120 VAC
System Pump
Boiler
Service switch
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
These pumps are mounted and pre-wired on the IPP panel.
P3
Oil-fired Boiler
T L N G
24 VAC
Room thermostat
Room thermostat
2-wire actuator
B1 B2
Burner
C1 C2
See note 3 Valve actuator Valve actuator Valve actuator To additional actuators Primary Pump
P1
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
67
XII
System CP-4 Two-temperature radiant heating system using (pages 70 71) two injection pump panels
Purpose Provide heating water to two radiant circuits - each requiring a different temperature. The
controls and injection pumps regulate radiant circuit supply temperature and maintain minimum boiler return temperature.
The primary pump can be as supplied with the boiler or purchased separately. Residential packaged boilers may have the pump mounted on the return piping at the boiler.
The pump can be used in this location provided the expansion tank or compression tank and fill line are correctly located.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
Radiant heating circuits Install the injection pump panel for the higher temperature subsystem upstream of the lower
temperature circuit injection pump panel to assure hotter supply water. This is illustrated in system CP-4, where Circuit #1 is the higher temperature circuit.
System CP-4 shows two manifold locations for Circuit #2 and one for Circuit #1. The same
piping design can be used for multiple manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone
thermostat or a dry contact that closes on a call for heat. Alternatively, use an indoor sensor or zone control.
68
System CP-4
An IPC is included with each IPP panel (or purchased separately when using field-constructed
injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor).
You can connect an indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response.
The IPC's control the injection pumps (P2 and P4) and radiant circuit pumps (P3 and P5).
The primary pump (P1) operates with the boiler (activated by the boiler controls).
On each IPC, use dip switch 2 to set radiant pump operation - DOWN for intermittent
operation, UP for continuous pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an
indoor sensor is connected to the IPC.
Operation
On call for heat from a radiant zone thermostat or actuator, the corresponding IPC activates
its injection pump, radiant circuit pump and the boiler. The boiler activates the primary pump (P1), initiating primary circuit flow.
The IPC's regulate the injection pump flow rates, increasing flow to raise the supply temperature,
or lowering flow to reduce it.
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection
flow (reducing the temperature drop in the primary circuit).
69
XII
Fill
P1
Primary circuit
H C M Primary circuit return Note 2 Note 2 Primary circuit supply
#2
C M H Heating system pump
#1
C M H Heating system pump Return from heating system Supply to heating system
IPC
Injection pump control
IPC
Injection pump control
P2
Safety controls (as required by local codes) Purging valves Outdoor sensor
P4
Purging valves
IPP
Injection pump panel #2
#2
P3
Supply temperature sensor
IPP
Injection pump panel #1
#1
P5
Supply temperature sensor
No valve actuators are shown here in order to provide for continuous circulation.
Manifold location A
Manifold location A
Boiler
No valve actuators are shown here in order to provide for continuous circulation.
Manifold location B
Purge valves & air vents
NOTICE IPP #1, with HIGHER supply temperature requirement, is installed upstream on the primary circuit (in order to receive the highest water temperature).
Figure 45 - System CP4 Two-temperature radiant heating system using two injection pump panels
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 3. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
70
Reset On
Reset On
Reset Off
Reset Off
Supply Temp.
Injection Pump Speed
Supply Temp.
L1
120 VAC
N
120 V (ac)
IPC #2
Power
120 V (ac)
Power
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
P3
P3 and P4 are mounted and pre-wired on the IPP panel.
P4
Supply & return sensors
P5
P3 and P4 are mounted and pre-wired on the IPP panel.
NOTE that IPC #1 is set up for thermostat operation. IPC #2 is set up for use with indoor sensor and continuous operation circulator. This configuration does not require a voltage applied to terminals 15 and 16.
Oil-fired Boiler
T L N G
24 VAC
Room thermostat
Room thermostat
2-wire actuator
B1 B2
Burner
C1 C2
See note 3 Valve actuator Valve actuator Valve actuator To additional actuators
P1
Primary pump
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
71
XII
System CP-5 Two-temperature radiant heating system using (pages 74 75) one injection pump panel and a mixing valve
Purpose Provide heating water to two radiant circuits - each requiring a different water supply
temperature. The control and injection pump provide water hot enough for the higher temperature radiant circuit, and maintain a minimum boiler return temperature. A mixing valve regulates the supply water to the lower temperature circuit.
The primary pump can be as supplied with the boiler or purchased separately. Residential packaged boilers may have the pump mounted on the return piping at the boiler.
The pump can be used in this location provided the expansion tank or compression tank and fill line are correctly located.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
Pipe the radiant circuit requiring the higher water temperature (Circuit #2 in system CP-5)
directly off of the radiant supply line as shown.
Install a bridge for connection of the lower temperature radiant circuit (Circuit #1 in system
CP-5). Install a balancing valve in the bridge as shown. Throttle the valve enough to push the required water through radiant Circuit #2.
Provide a pump and a three-way mixing valve for the lower temperature circuit (Circuit #1 in
CP-5). Assure that the pump is sized to handle the mixing valve pressure drop.
System CP-5 shows one manifold location for each of the radiant circuits. The same piping
design can be used for multiple manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone
thermostat or a dry contact that closes on a call for heat. Alternatively, use an indoor sensor or zone control.
72
System CP-5
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately
when using field-constructed injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor).
You can connect an indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response.
The IPC controls the injection pump (P2) and radiant circuit pump (P3). The primary pump
(P1) operates with the boiler (activated by the boiler controls).
The low temperature radiant circuit pump (P4) operates when the low temperature circuit
relay is activated through the actuator end switches.
On each IPC, use dip switch 2 to set radiant pump operation - DOWN for intermittent
operation, UP for continuous pump operation. Because of the bridge in the radiant circuit piping, the radiant circuit pump always has a flow path, even if manifold valve actuators are used. This eliminates the need for a differential pressure by-pass valve when using manifold valve actuators with continuous pump operation.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an
indoor sensor is connected to the IPC.
Operation On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection
pump, radiant circuit pump and the boiler. The boiler activates the primary pump (P1), initiating primary circuit flow.
On call for heat from one of the low temperature circuit actuator end switches, the low
temperature circuit relay is activated. This activates pump P4 and signals the IPC for heat.
The IPC regulates injection pump flow rate, increasing flow to raise supply temperature - or
lowering flow to reduce it. Set the IPC supply temperature as needed for the higher temperature circuit (Circuit #2 in CP-5). The mixing valve will automatically regulate the supply temperature to the lower temperature circuit (Circuit #1 in CP-5).
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection
flow (reducing the temperature drop in the primary circuit).
73
XII
Figure 47 - System CP5 Two-temperature radiant heating system using one injection pump panel and a mixing valve
Fill
P1
Primary circuit
IPC
Injection pump control
P2
Purging valves
IPP
Injection pump panel
Safety controls (as required by local codes)
Note 2
P3
Supply temperature sensor
Balancing valve
Alternate piping
(using mixing valves)
2
Mixing valve
H M C
P4
Pump
2 to 4 pipe diameters
Boiler
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
74
Reset On
Reset Off
Supply Temp.
IPC #2
L1
120 VAC
N
120 V (ac)
Power
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
P3
P4
Low temp circuit pump
24 VAC
Room thermostat
Room thermostat
2-wire actuator
Oil-fired Boiler
T L N
Room thermostat
Room thermostat
B1 B2 C1 C2
P1
Primary pump
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
75
XII
System CP-6 Radiant heating and domestic water heating with (pages 78 79) conventional boiler - DHW as a secondary circuit
Purpose Provide radiant heating and domestic water heating (with optional domestic priority). The
control and injection pump regulate radiant circuit supply temperature and maintain minimum boiler return temperature.
The primary pump can be as supplied with the boiler or purchased separately. Residential packaged boilers may have the pump mounted on the return piping at the boiler.
The pump can be used in this location provided the expansion tank or compression tank and fill line are correctly located.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
System CP-6 shows two manifolds location for the radiant circuits. The same piping design
can be used for multiple manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone
thermostat or a dry contact that closes on a call for heat. Alternatively, use an indoor sensor or zone control.
Water heater circuit
Provide a pump with the domestic water heater, sized to give the required flow through the
heater for the supply water temperature available.
Pipe the domestic water circuit as the first branch off the primary circuit. This assures the
hottest possible supply water temperature.
76
System CP-6
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using fieldconstructed injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an
indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response.
The IPC controls the injection pump (P2) and radiant circuit pump (P3). The primary pump (P1) operates with
the boiler (activated by the boiler controls).
Use IPC dip switch 2 to set radiant circuit pump operation - DOWN for intermittent operation, UP for continuous
pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an indoor sensor is
connected to the IPC.
DHW controls
The primary pump must operate to provide heating water to the domestic water heater. Heating water must flow
through the primary piping during any domestic water heating cycle, including non-heating season periods. This approach is best used on systems with short primary circuit piping, to minimize non-heating season piping losses. See systems CP-7 and CP-8 for alternate designs that do not require primary circuit operation during domestic water heating cycles.
On call for heat from the water heater tank aquastat, the DHW relay is activated. This relay activates the boiler and
the DHW pump (P2). The boiler, in turn, activates the primary pump, P1. If wired for domestic priority, the DHW relay interrupts the heating signal to the IPC, causing the IPC to turn off the injection pump (P3). The radiant circuit pump (P4) will turn off as well unless IPC dip switch #2 is set for continuous pump operation.
Radiant heating
On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection pump, radiant circuit
pump and the boiler. The boiler activates the primary pump (P1), initiating flow in the primary circuit. If the DHW relay is wired for domestic priority, the IPC will not sense the call for heat until the domestic water heating cycle is completed.
The IPC regulates injection pump flow rate, increasing flow to raise the supply temperature, or lowering flow to
reduce it.
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the
temperature drop in the primary circuit).
Part Number 650-000-240/1098
77
XII
Figure 49 - System CP6 Radiant heating and domestic water heating with conventional boiler - DHW as a secondary circuit
Fill
Primary pump
P1
Primary circuit
DHW outlet
flow/check valve
IPC P3
Return temperature sensor Purging valves
note 2
P4
Supply temperature sensor
Manifold location A
2 to 4 pipe diameters
Boiler
Valve actuators optional
Manifold location B
Purge valves & air vents
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 3. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
78
Reset On
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
L1
120 VAC
System Pump
Boiler
Service switch
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P3
These pumps are mounted and pre-wired on the IPP panel.
P4
T T
L N
Oil-fired Boiler
DHW relay Safety controls, if required by local codes
24 VAC
G B1
Room thermostat
To additional actuators
Room thermostat
B2
Burner
C1 C2
Valve actuator
Relay shown wired for domestic priority. Add jumper, shown in red above, to remove priority.
P2
DHW pump
P1
Primary pump
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
79
XII
System CP-7 Radiant heating and domestic water heating with (pages 82 83) GV boiler - DHW as a secondary circuit
Purpose Provide radiant heating and domestic water heating (with optional domestic priority). The
control and injection pump regulate radiant circuit supply temperature and maintain minimum boiler return temperature.
System CP-7 uses the integral pump in the GV boiler for primary loop circulation. If a higher
flow rate is required, pipe the GV boiler and water heater on a secondary circuit and provide a separate pump for the primary circuit.
Radiant heating circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
System CP-7 shows two manifold locations for the radiant circuits. The same piping design
can be used for multiple manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone thermostat or a dry contact that closes on a call for heat. Alternatively, use an indoor sensor or zone control. Water heater circuit
Provide a pump with the domestic water heater, sized to give the required flow through the
heater for the supply water temperature available.
Pipe the domestic water circuit as the first branch off of the primary. This assures the hottest
possible supply water temperature.
80
System CP-7
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using fieldconstructed injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an
indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response.
The IPC controls the injection pump (P2) and radiant circuit pump (P3). The primary pump (P1) is integral to the
GV boiler, and is activated by the boiler controls.
Use IPC dip switch 2 to set radiant circuit pump operation - DOWN for intermittent operation, UP for continuous
pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an indoor sensor is
connected to the IPC.
DHW controls
The primary pump (P1, integral to the GV boiler) must operate to provide heating water to the domestic water
heater. Heating water must flow through the primary piping during any domestic water heating cycle, including non-heating season periods. This approach is best used on systems with short primary circuit piping, to minimize non-heating season piping losses. See systems CP-7 and CP-8 for alternate designs that do not require primary circuit operation during domestic water heating cycles.
On call for heat from the water heater tank aquastat, the DHW relay is activated. This relay activates the boiler and
the DHW pump (P2). The boiler, in turn, activates the primary pump (P1). If wired for domestic priority, the DHW relay interrupts the heating signal to the IPC, causing the IPC to turn off the injection pump (P3). The radiant circuit pump (P4) will turn off as well unless IPC dip switch #2 is set for continuous pump operation.
Radiant heating
On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection pump (P3), radiant
circuit pump (P4) and the boiler. The boiler activates the primary pump (P1), initiating flow in the primary. If the DHW relay is wired for domestic priority, the IPC will not sense the call for heat until the domestic water heating cycle is completed.
The IPC regulates injection pump flow rate, increasing flow to raise the supply temperature, or lowering flow to
reduce it.
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the
temperature drop in the primary circuit).
Part Number 650-000-240/1098
81
XII
Figure 51 - System CP7 Radiant heating and domestic water heating with GV boiler DHW as a secondary circuit
Primary circuit
DHW outlet
flow/check valve
IPC
Injection pump control
P3
note 2
Purging valves
IPP P2
Alternate piping
(using mixing valves)
P4
Supply temperature sensor
2 to 4 pipe diameters
Cold Mixed Hot Fill Heating system pump Supply to heating system
Manifold location B
Purge valves & air vents
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
82
Reset On
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
L1
120 VAC
System Pump
Boiler
Service switch
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
24 VAC
DHW relay
Room thermostat
To additional actuators
Room thermostat
T
Relay shown wired for DHW priority. To remove priority, add red jumper where shown above.
T L N
P2
DHW pump
G GV Boiler
P1
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
83
XII
System CP-8 Radiant heating and domestic water heating with (pages 86 87) conventional boiler - independent DHW operation
Purpose Provide radiant heating and domestic water heating (with optional domestic priority). The
control and injection pump regulate radiant circuit supply temperature and maintain minimum boiler return temperature.
This system allows domestic water heating without flow in the primary circuit, reducing
piping losses during non-heating season periods.
The primary pump can be as supplied with the boiler or purchased separately. Residential packaged boilers may have the pump mounted on the return piping at the boiler.
The pump can be used in this location provided the expansion tank or compression tank and fill line are correctly located.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
System CP-8 shows two manifold locations for the radiant circuits. The same piping design
can be used for multiple manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone
thermostat or a dry contact that closes on a call for heat. Alternatively, use an indoor sensor or zone control.
Water heater circuit
Provide a pump with the domestic water heater, sized to give the required flow through the
heater for the supply water temperature available.
Include a flow/check valve in the primary and water heater circuits, as illustrated, to prevent
flow short circuiting.
Connect the DHW supply directly off of the boiler supply piping. This assures the hottest
possible supply water temperature. Connect the DHW return to the boiler return piping.
84
System CP-8
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using fieldconstructed injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an
indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response.
The IPC controls the injection pump (P3) and radiant circuit pump (P4). The primary pump (P1) operates with
the boiler (activated by the boiler controls).
Use IPC dip switch 2 to set radiant circuit pump operation - DOWN for intermittent operation, UP for continuous
pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an indoor sensor is
connected to the IPC.
DHW controls
On call for heat from the water heater tank aquastat, the DHW relay is activated. This relay activates the boiler and
the DHW pump (P2). The boiler, in turn, activates the primary pump, P1. If wired for domestic priority, the DHW relay turns off the primary pump (P1) and interrupts the heating signal to the IPC, causing the IPC to turn off the injection pump (P3).
The radiant circuit pump (P4) will turn off as well unless IPC dip switch 2 is set for continuous pump operation.
Radiant heating
On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection pump (P3), radiant
circuit pump (P4) and the boiler. The boiler activates the primary pump (P1), initiating flow in the primary circuit. If the DHW relay is wired for domestic priority, the primary pump will not be powered and the IPC will not sense the call for heat until the domestic water heating cycle is completed.
The IPC regulates injection pump flow rate, increasing flow to raise the supply temperature, or lowering flow to
reduce it.
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the
temperature drop in the primary circuit).
85
XII
Figure 53 - System CP8 Radiant heating and domestic water heating with conventional boiler independent DHW operation
Primary pump
P1
DHW outlet
Primary circuit
IPC P3
Return temperature sensor Purging valves
IPP
DHW pump
P4
Supply temperature sensor
Alternate piping
(using mixing valves)
P2
Valve actuators optional
Manifold location A
2 to 4 pipe diameters
Boiler
Valve actuators optional
Manifold location B
Purge valves & air vents
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 3. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
86
Reset On
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
L1
120 VAC
System Pump
Boiler
Service switch
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P3
These pumps are mounted and pre-wired on the IPP panel.
P4
T T
L N
Oil-fired Boiler
DHW relay Safety controls, if required by local codes
24 VAC
G B1
Room thermostat
To additional actuators
Room thermostat
B2
Burner
C1 C2
Valve actuator Valve actuator Relay shown wired for domestic priority. Add (2) jumpers, shown in red above, to remove priority.
P2
DHW pump
P1
Primary pump
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
87
XII
System CP-9 Radiant heating and priority domestic water heating (pages 90 91) with GV boiler DHW through diverting valve
Purpose Provide radiant heating and domestic water heating with domestic priority. The control and
injection pump regulate radiant circuit supply temperature and maintain minimum boiler return temperature.
This system provides domestic water heating without flow in the primary circuit, reducing
piping losses during non-heating season periods.
The GV boiler integral pump must provide flow for the water heater and primary circuits.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.)
System CP-9 shows two manifold location for the radiant circuits. The same piping design
can be used for multiple manifolds.
Manifold valve actuators are optional, but recommended as discussed in Zoning radiant
heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone
The 3-way diverting valve is normally open to the radiant heating circuit (primary). It directs
flow through either the primary or domestic water circuit.
88
System CP-9
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using fieldconstructed injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an
indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response.
The IPC controls the injection pump (P2) and radiant circuit pump (P3). The primary pump (P1) operates with
the boiler (activated by the boiler controls).
Use IPC dip switch 2 to set radiant circuit pump operation - DOWN for intermittent operation, UP for continuous
pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close.
Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an indoor sensor is
connected to the IPC.
DHW controls
On call for heat from the water heater tank aquastat, the diverting valve directs flow to the water heater and the
DHW relay is activated. This relay activates the boiler. The boiler, in turn, activates the primary pump, P1. The DHW relay interrupts the heating signal to the IPC, causing the IPC to turn off the injection pump (P2). The radiant circuit pump (P3) will turn off as well unless IPC dip switch 2 is set for continuous pump operation.
Radiant heating
On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection pump (P2), radiant
circuit pump (P3) and the boiler. The boiler activates the primary pump (P1), initiating flow in the primary circuit. When the DHW relay is activated, the IPC will not sense the call for heat until the domestic water heating cycle is completed.
The IPC regulates injection pump flow rate, increasing flow to raise the supply temperature, or lowering flow to
reduce it.
If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the
temperature drop in the primary circuit).
89
XII
Figure 55 - System CP9 Radiant heating and domestic water heating with GV boiler DHW through diverting valve
DHW outlet
Primary circuit
IPC
Injection pump control
P2
Purging valves
IPP
Injection pump panel
P3
Supply temperature sensor
Alternate piping
(using mixing valves)
2 to 4 pipe diameters
Cold Mixed Hot Fill Heating system pump Supply to heating system
Manifold location B
Purge valves & air vents
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 3. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
90
Reset On
123
140 F
F O R R E S E T O N L Y
Reset Off
140 F
L1
120 VAC
System Pump
Boiler
Service switch
NRTL/C LR 58223
Made in Canada
RESET INPUTS
Zone or Outdoor Indoor Sensor
REQUIRED SENSORS
Boiler Radiant Signal wiring Return Supply must be rated
at least 300V
To Boiler T-T
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
These pumps are mounted and pre-wired on the IPP panel.
P3
24 VAC
DHW relay
Room thermostat
To additional actuators
Room thermostat
T H
N
24VAC DHW diverter valve (energized on call for DHW)
G
P1
GV Boiler
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
91
XII
System CP-10 Radiant heating, domestic water heating and (pages 94 97) baseboard heating with conventional boiler
Purpose Provide multiple heating functions - radiant heating and baseboard heating plus domestic
water heating (with optional domestic priority). The control and injection pump regulate radiant circuit supply temperature and help maintain minimum boiler return temperature. This system provides domestic water heating without flow in the primary circuit, reducing piping losses during non-heating season periods. Two versions are shown one for baseboard zoning with zone valves (CP-10a) and the other for baseboard zoning with pumps (CP-10b).
The primary pump can be as supplied with the boiler or purchased separately. Residential packaged boilers may have the pump mounted on the return piping at the boiler.
The pump can be used in this location provided the expansion tank or compression tank and fill line are correctly located.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.) System CP-10 shows two manifold locations for the radiant circuits. The same piping design can be used for multiple manifolds. Manifold valve actuators are optional, but recommended as discussed in Zoning radiant heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone thermostat or a dry contact that closes on a call for heat.
Provide a pump with the domestic water heater, sized to give the required flow through the
heater for the supply water temperature available. Connect the DHW supply directly off of the boiler supply piping. This assures the hottest possible supply water temperature. Connect the DHW return to the boiler return piping. Include a flow/check valve in the primary and water heater circuits, as illustrated, to prevent flow short circuiting.
Baseboard circuits
The system illustration shows several options for baseboard circuit piping. Provide the
pumps needed for the baseboards. Each baseboard branch circuit off of the primary will require at least one pump, even if zoning with zone valves. Use flow/check valves in the baseboard circuits as illustrated. A flow/check is required in every loop when zoning with pumps. A flow/check is required on the return piping when the piping is above the primary unless a thermal trap is provided as shown.
92
System CP-10
Baseboard heating and domestic water heating are operated through a Multi-zone relay center, illustrated based
on zoning the baseboard heating with pumps. If zoning with zone valves, replace the thermostats shown connected to the relay center with the zone valve end switches. If domestic water heating priority is desired, add the DHW relay.
Radiant heating controls
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using fieldconstructed injection mixing systems).
The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an
indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response. The IPC controls the injection pump (P10) and radiant circuit pump (P11). The primary pump (P1) operates with the boiler (activated by the boiler controls). Use IPC dip switch 2 to set radiant circuit pump operation - DOWN for intermittent operation, UP for continuous pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close. Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an indoor sensor is connected to the IPC.
Operation
Domestic water heating
On call for heat from the water heater tank aquastat, the DHW circulator is activated by the relay center and the
DHW relay (optional) is activated. If wired for domestic priority, the DHW relay turns off the primary pump (P1) and interrupts the heating signal to the IPC, causing the IPC to turn off the injection pump (P10). The radiant circuit pump (P11) will turn off as well unless IPC dip switch 2 is set for continuous pump operation.
Baseboard heating
On call for heat from a baseboard zone, the relay center activates the zone pump and turns on the boiler. The
boiler, in turn, activates the primary pump (P1). If domestic water priority is installed, the primary pump will not operate during a water heating cycle.
Radiant heating
On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection pump (P10), radiant
circuit pump (P11) and the boiler. The boiler activates the primary pump (P1), initiating flow in the primary. If domestic water priority is installed, the primary pump will not be powered and the IPC will not sense the call for heat until the domestic water heating cycle is completed. The IPC regulates injection pump flow rate, increasing flow to raise the supply temperature, or lowering flow to reduce it. If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the temperature drop in the primary circuit).
93
XII
P1
flow/check valve
P3
P3
Alternate piping to circuit at left, using flow/check valve on return line in place of thermal trap
Fill
Purging valves
P3
Primary circuit
Baseboard zones
(when below primary)
IPC P10
Injection pump control
Zone valves
Use minimum 18" thermal trap as alternate to flow/check valve
IPP Injection
pump panel
Purging valves Supply temperature sensor
P11
Alternate piping
(using mixing valves)
P2
Safety controls (as required by local codes)
Manifold location A
Valve actuators optional
Boiler
2 to 4 pipe diameters
Cold
Manifold location B
Purge valves & air vents
Mixed
Hot
Figure 57 - System CP10a Radiant heating, domestic water heating and baseboard heating with conventional boiler - baseboard zoning with zone valves
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative. Part Number 650-000-240/1098
94
Reset On
Reset Off
Supply Temp.
Injection Pump Speed
Baseboard thermostats
Zone valves
N
120 V (ac)
Power
Baseboard relay
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P3
Baseboard pump
P10
P11
P10 and P11 are mounted and pre-wired on the IPP panel.
DHW relay
Relay shown wired for domestic priority. Add (2) jumpers, shown in red, to remove priority.
C1 C2
24 VAC
P1
DHW pump
P2
L N
Room thermostat To additional actuators Room thermostat 4-wire actuator See note 3 2-wire actuator
Oil-fired Boiler
G
Safety controls, if required by local codes
B1
See note 3 Valve actuator Valve actuator Valve actuator Burner
B2
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel.
95
XII
P1
flow/check valve
Baseboard zones
(when above primary)
P4 P5 P6
Flow/check valves
P3
note 2
Alternate piping to circuit at left, using flow/check valve on return line in place of thermal trap
Fill
Purging valves
Primary circuit
Baseboard zones
(when below primary)
P4 P5
Purging valves
P6
Flow/check valves
DHW outlet
flow/check valve
IPC P10
Injection pump control
IPP Injection
pump panel
Purging valves Supply temperature sensor
P11
Alternate piping
(using mixing valves)
P2
Safety controls (as required by local codes)
Manifold location A
Valve actuators optional
Boiler
2 to 4 pipe diameters
Cold
Manifold location B
Purge valves & air vents
Mixed
Hot
Figure 59 - System CP10b Radiant heating, domestic water heating and baseboard heating with conventional boiler - baseboard zoning with pumps
Notes 1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative.
96
Reset On
Reset Off
Supply Temp.
Injection Pump Speed
N
120 V (ac)
T1 T1 T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
Power
T N
T T
PR PR C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 C6 C6
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
P4
P5
P6
P10 P11
DHW pump
DHW relay - use if DHW priority reqd 120 VAC coil (supplied by installer)
P10 and P11 are mounted and pre-wired on the IPP panel.
P1
Primary pump
24 VAC
T
4-wire actuator See note 3
To additional actuators
T
L
C1 C2
Room thermostat
Room thermostat
2-wire actuator
N
Safety controls, if required by local codes
G B1
B2 Oil-fired Boiler
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
97
XII
System CP-11 Radiant heating, domestic water heating and (pages 100 103) baseboard heating with GV boiler
Purpose Provide multiple heating functions - radiant heating and baseboard heating plus domestic
water heating (with optional domestic priority). The control and injection pump regulate radiant circuit supply temperature and help maintain minimum boiler return temperature. Two versions are shown - one for baseboard zoning with zone valves (CP-11a) and the other for baseboard zoning with pumps (CP-11b).
The GV integral pump provides flow in the primary circuit. If more flow is required, install
the GV boiler as a secondary circuit off the primary and provide an appropriately sized primary pump.
Radiant circuits
The Injection Pump Panel (IPP) includes the injection pump and the radiant circuit pump.
(For applications larger than the capacity of the IPP, use multiple IPP panels or use an IPC Injection Pump Control with an injection pump and radiant circuit pump sized for the flow rates and pressure drops needed.) System CP-11 shows two manifold locations for the radiant circuits. The same piping design can be used for multiple manifolds. Manifold valve actuators are optional, but recommended as discussed in Zoning radiant heating systems, section IV of this Guide. When actuators are not used, provide the call for heat signal to the IPC (24 volt or 120 volt signal to terminals 15 and 16) through a zone thermostat or a dry contact that closes on a call for heat.
Provide a pump with the domestic water heater, sized to give the required flow through the
heater for the supply water temperature available. Connect the water heater in the first secondary circuit off of the primary. This assures the hottest available supply water.
Baseboard circuits
The system illustration shows several options for baseboard circuit piping. Provide the pumps
needed for the baseboards. Each baseboard branch circuit off of the primary will require at least one pump, even if zoning with zone valves. Use flow/check valves in the baseboard circuits as illustrated. A flow/check is required in every loop when zoning with pumps. A flow/ check is required on the return piping when the piping is above the primary unless a thermal trap is provided as shown.
98
System CP-11
Baseboard heating and domestic water heating are operated through a Multi-zone relay center, illustrated based
on zoning the baseboard heating with pumps. If zoning with zone valves, replace the thermostats shown connected to the relay center with the zone valve end switches. If domestic water heating priority is desired, add the DHW relay.
Radiant heating controls
An IPC (Injection Pump Control) is included with the IPP panel (or purchased separately when using field
constructed injection mixing systems). The IPC can be set for fixed supply temperature or outdoor reset (requires outdoor sensor). You can connect an indoor temperature sensor or tekmar zone control to the IPC to provide room temperature feedback to the control, allowing heating circuit regulation based on space temperature response. The IPC controls the injection pump (P10) and radiant circuit pump (P11). The primary pump (P1) is integral to the GV boiler (activated by the boiler controls). Use IPC dip switch 2 to set radiant circuit pump operation - DOWN for intermittent operation, UP for continuous pump operation. With continuous radiant pump operation, either use no manifold valve actuators or install a differential pressure by-pass valve (as shown in system CP-12) to protect the pump from dead heading when the manifold valve actuators close. Do not connect a 24 volt or 120 volt signal to terminals 15 and 16 if either a zone control or an indoor sensor is connected to the IPC.
Operation
Domestic water heating
On call for heat from the water heater tank aquastat, the DHW circulator is activated by the relay center and the
DHW relay (optional) is activated. If wired for domestic priority, the DHW relay interrupts the heating signal to the IPC, causing the IPC to turn off the injection pump (P10). The radiant circuit pump (P11) will turn off as well unless IPC dip switch 2 is set for continuous pump operation.
Baseboard heating
On call for heat from a baseboard zone, the relay center activates the zone pump and turns on the boiler. The
boiler, in turn, activates the primary pump (P1).
Radiant heating
On call for heat from a radiant zone thermostat or actuator, the IPC activates its injection pump (P10), radiant
circuit pump (P11) and the boiler. The boiler activates the primary pump (P1), initiating flow in the primary. If domestic water priority is installed, the IPC will not sense the call for heat until the domestic water heating cycle is completed. The IPC regulates injection pump flow rate, increasing flow to raise the supply temperature, or lowering flow to reduce it. If boiler return temperature drops below the preset limit (130 F), the IPC reduces injection flow (reducing the temperature drop in the primary circuit).
99
XII
P3
P3
Alternate piping to circuit at left, using flow/check valve on return line in place of thermal trap
Purging valves
P3
Primary circuit
DHW outlet
flow/check valve
Baseboard zones
(when below primary)
Purging valves
IPC P10
Injection pump control
Zone valves
Use minimum 18" thermal trap as alternate to flow/check valve
note 2
IPP Injection
pump panel
Purging valves Supply temperature sensor
P11
Alternate piping
(using mixing valves)
2 to 4 pipe diameters
Cold
Fill
Manifold location B
Purge valves & air vents
Mixed
Hot
Figure 61 - System CP11a Radiant heating, domestic water heating and baseboard heating with GV boiler baseboard zoning with zone valves
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative. Part Number 650-000-240/1098
100
Reset On
Reset Off
Supply Temp.
Injection Pump Speed
Zone valves
N
120 V (ac)
Power
Baseboard relay
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P3
Baseboard pump
P10
P11
Baseboard thermostats
P10 and P11 are mounted and pre-wired on the IPP panel.
24 VAC
P2
Room thermostat
To additional actuators
Room thermostat
L N GV Boiler G
P1
Integral pump
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel.
101
XII
Baseboard zones
(when above primary)
P4 P5 P6
Flow/check valves
P3
note 2
Alternate piping to circuit at left, using flow/check valve on return line in place of thermal trap
Purging valves
Primary circuit
DHW outlet
flow/check valve
Baseboard zones
(when below primary)
P4 P5
Purging valves
P6
Flow/check valves
IPC P10
Injection pump control
note 2
IPP Injection
pump panel
Purging valves Supply temperature sensor
P11
Alternate piping
(using mixing valves)
2 to 4 pipe diameters
Cold
Fill
Manifold location B
Purge valves & air vents
Mixed
Hot
Figure 63 - System CP11b Radiant heating, domestic water heating and baseboard heating with GV boiler baseboard zoning with pumps
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel.
102
Reset On
Reset Off
Supply Temp.
Injection Pump Speed
N
120 V (ac)
T1 T1 T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
Power
T N
T T
PR PR C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 C6 C6
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P2
P4
P5
P6
P10 P11
DHW pump
DHW relay - use if DHW priority reqd 120 VAC coil (supplied by installer)
P10 and P11 are mounted and pre-wired on the IPP panel.
24 VAC
Room thermostat
To additional actuators
Room thermostat
2-wire actuator
T L
N G GV Boiler
P1
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel. Part Number 650-000-240/1098
103
XII
(p.106 109)
System Radiant heating, domestic water heating and baseboard CP-12 heating with multiple boilers
Purpose Use a multiple boiler system to provide multiple
heating functions - radiant heating and baseboard heating plus domestic water heating (with optional domestic priority). The control and injection pump regulate radiant circuit supply temperature and help maintain minimum boiler return temperature.
104
System CP-12
thermostats shown connected to the relay center with the zone valve end switches.
Radiant controls
Operation
Domestic water heating
105
XII
Baseboard zones
P5 P5
flow/check valve
Alternate piping to circuit at left, using flow/check valve on return line in place of thermal trap
note 2
Primary circuit
System pump
P4
flow/check valve
note 2
Fill
Return temperature sensor
P12
Purging valves
Expansion tank
Heating system pump Return from heating system Supply to heating system
P13
Valve actuators optional
P3
To additional boilers
Manifold location A
Valve actuators optional
DHW outlet
Differential pressure by-pass valve - required if using manifold valves and continuous pump operation
PB1 Boiler
PB2
Manifold location B
Valve actuators optional
Boiler
Manifold location C
Purge valves & air vents
Figure 65 - System CP12a Radiant heating, domestic water heating and baseboard heating with multiple boilers baseboard zoning with zone valves
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative. Part Number 650-000-240/1098
106
Reset On
Reset Off
Supply Temp.
Injection Pump Speed
Baseboard thermostats
Zone valves
N
120 V (ac)
Power
Baseboard relay
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
Baseboard pump
P12 P13
P3
Supply & return sensors
DHW pump
P12 and P13 are mounted and pre-wired on the IPP panel.
DHW circulator
24 VAC
Relay shown wired for domestic priority. Add (2) jumpers, shown in red above, to remove priority.
P4
L N
Safety controls, if required by local codes
Room thermostat Room thermostat
T
Safety controls, if required by local codes
N G B1 B2
Burner
G B1 B2
4-wire actuator
See note 3
To additional actuators
C1 C2
Valve actuator Valve actuator Valve actuator
C1 C2
Boiler #2
PB2
Boiler Circulator
Boiler #1
PB1
Boiler Circulator
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel.
107
XII
Baseboard zones
P6 P7
Alternate piping to circuit at left, using flow/check valve on return line in place of thermal trap.
note 2
Primary circuit
System pump
P4
flow/check valve
note 2
Fill
Return temperature sensor
P12
Purging valves
Expansion tank
Heating system pump Return from heating system Supply to heating system
P13
Valve actuators optional
P3
To additional boilers
Manifold location A
Valve actuators optional
DHW outlet
Differential pressure by-pass valve - required if using manifold valves and continuous pump operation
PB1 Boiler
PB2
Manifold location B
Valve actuators optional
Boiler
Manifold location C
Purge valves & air vents
Figure 67 - System CP12b Radiant heating, domestic water heating and baseboard heating with multiple boilers baseboard zoning with pumps
Notes
1. This drawing is conceptual only. It shows representative piping components and layout. Weil-McLain does not represent that this drawing meets any particular mechanical or building codes. The installer is responsible for inclusion of all required safety devices, or other miscellaneous piping hardware not shown on drawing. The installer is responsible for proper sizing/selection of all hardware shown on this diagram. 2. Space branch tees no more than 4 pipe diameters apart. Ream the pipe or tube stub between the tees thoroughly to prevent turbulence. The pipe or tubing connected to the first tee should be at least 8 pipe diameters long. 3. See Weil-McLain installation instructions for specific details on installing the boiler and injection pump panel. 4. Alternate piping shown for use of two mixing valves, piped as shown, in lieu of using injection pump panel. See separate publication for suggested wiring for this piping alternative. Part Number 650-000-240/1098
108
Reset On
Baseboard thermostats
Reset Off
Supply Temp.
Injection Pump Speed
N
120 V (ac)
T1 T1 T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
Power
L N
T T
Service switch
1 2
3 4 5 6
7 8 9 10
11 12 13 14
15 16 17 18
P4
P5
P6
P12
P13
P3
Supply & return sensors
DHW pump
P12 and P13 are mounted and pre-wired on the IPP panel.
DHW circulator
24 VAC
Relay shown wired for domestic priority. Add (2) jumpers, shown in red above, to remove priority.
P4
L N
Safety controls, if required by local codes
Room thermostat Room thermostat
T
Safety controls, if required by local codes
N G B1 B2
Burner
G B1 B2
4-wire actuator
See note 3
To additional actuators
C1 C2
Valve actuator Valve actuator Valve actuator
C1 C2
Boiler #2
PB2
Boiler Circulator
Boiler #1
PB1
Boiler Circulator
Notes
1. This drawing is conceptual only. It shows representative system wiring. Weil-McLain does not represent that this drawing meets any particular mechanical, electrical, or building codes. All wiring must be installed in accordance with: In the USA - the latest version of the National Electrical Code (N.E.C.), as well as any other National, State or Local code requirements having jurisdiction. In Canada - CSA C22.1 (C.E.C.) Part 1, as well as any other National, Provincial or Local code requirements having jurisdiction. The installer is responsible for inclusion of all required safety devices, or other miscellaneous hardware not shown on drawing. 2. The minimum wire gauge used for all low voltage circuits shall be 18 AWG unless otherwise required by code(s) having jurisdiction. 3. Multiple valve actuators may be powered through a common thermostat for rooms/zones having multiple radiant circuits. End switches are optional on all but one valve actuator wired in this manner. 4. See Weil-McLain installation instructions for specific details on installing the boiler, and injection pump panel.
109
XIII
Appendix
Pump curve equations
To calculate the Feet head for any flow rate for the pump curves given in Figure 26, you can use the following polynomial equations. Use only for the flow rate range shown in the curves.
Taco 007 Taco 0010 Taco 0011 Taco 0012 Taco 0014 Grundfos 15-42 Grundfos 26-64 Grundfos 43-75 B & G NRF-22 B & G PL-30 B & G PL-50
Feet head = 10.932555 - 0.16875578xGPM - 0.01521757xGPM2 + 0.00020748122xGPM3
110
GPM = a
TEL
TEL
Tube size a " AlumiPex b c a " AlumiPex b c a 1" AlumiPex b c a " Copper b c a 1" Copper b c a 1" Copper b c a 1 " Copper b c a 2" Copper b c
-0.546243 -0.566845 -0.568391 -0.553786 -0.539398 -0.54395 -0.558151 -0.53630256 -0.549257 -0.567042 47.282097 83.654266 98.227686 93.893487 56.91038 32.513578 115.98578 51.346672 90.532778 112.76368 0.9995437 0.999942 0.9999694 0.9999269 0.9998195 0.9999679 0.9999606 0.99979985 0.9999122 0.9999824 -0.426158 -0.539835 -0.551448 -0.505463 -0.443727 -0.543695 -0.524145 -0.43772596 -0.488098 -0.554712 75.153462 124.66566 172.66094 132.81573 44.919189 102.76405 175.50699 51.754916 106.20044 201.74157 0.9997386 0.9998432 0.9999264 0.9998754 0.9995672 0.9998416 0.9999229 0.99965195 0.9998299 0.999942 -0.396225 -0.473094 -0.515583 -0.441545 -0.274307 -0.392628 -0.471034 -0.31668162 -0.394699 -0.522198 71.379514 97.515613 112.68287 109.82208 64.567699 100.35663 131.28224 61.643267 105.56214 128.15213 0.9998936 0.9999686 0.9999806 0.9999566 0.9998539 0.9999435 0.9999674 0.99987245 0.9999436 0.9999854 -0.499304 -0.546292 -0.553938 -0.513679 -0.448395 -0.488876 -0.524849 -0.4548061 -0.496315 -0.555043 79.99001 138.55373 192.92987 154.57651 57.748169 122.83323 192.50008 64.069652 129.29073 226.29686 0.9997583 0.999878 0.9999562 0.9999245 0.9997203 0.999904 0.9999398 0.9997766 0.9998997 0.9999686 -0.39971 -0.483946 -0.526506 -0.461537 -0.320622 -0.41861 -0.478421 -0.35422024 -0.424158 -0.533449 64.967808 126.50711 228.88302 152.62247 37.056987 106.04502 204.08838 48.05632 106.69447 295.9619
0.9996432 0.9997491 0.9998911 0.9998716 0.9995942 0.9998456 0.9998984 0.99965962 0.999835 0.9999352 -0.281352 -0.376797 -0.46497 -0.380913 -0.173726 -0.321963 -0.408756 -0.23103054 -0.318881 -0.490197 58.008279 83.121812 225.94646 99.75135 27.252814 65.834312 168.76916 36.458671 59.002982 281.5639 0.9996916 0.9996014 0.9998454 0.99976 0.9996179 0.9997318 0.9998486 0.99963654 0.9997032 0.9998785
-0.214147 -0.23636 -0.394833 -0.249847 -0.084596 -0.188388 -0.318849 -0.13868336 -0.165534 -0.413095 51.44484 62.224837 113.27687 53.9907 22.343917 40.881309 61.072713 25.510536 36.801943 91.875092
0.9998399 0.9997454 0.9996836 0.9997668 0.9998137 0.9997681 0.9996566 0.99973669 0.9997716 0.9996731 -0.145029 -0.12866 -0.182626 -0.089707 -0.027987 -0.061195 -0.070971 -0.03819045 -0.044815 -0.132512
111
Price $20
112