Diagnostics

Overview of contents

This chapter shows you the meaning of the LED displays on your DP/DP Coupler. The tables provide information on error states indicated by the LEDs, the possible causes and suggested corrective measures. In the next section, you are made familiar with the diagnostic system of the DP/DP Coupler. An example is used to illustrate the evaluation of a diagnostic frame.
Section 6.1 6.2 6.3 Diagnostics by means of LEDs Diagnostics Using the User Program Example of a diagnosis Topic Page 6-2 6-4 6-11

DP/DP Coupler A5E00244669-03

6-1

Diagnostics

6.1

Diagnostics by means of LED indication

SF 1 SF 2 BF 1 BF 2 ON 1 ON 2

SF 1: SF 2: BF 1: BF 2: ON 1: ON 2:

Group error on PROFIBUS DP network 1 (red) Group error on PROFIBUS DP network 2 (red) Bus error on PROFIBUS DP network 1 (red) Bus error on PROFIBUS DP network 1 (red) 24 V power supply DP/DP Coupler network 1 (green) 24 V power supply DP/DP Coupler network 2 (green)

Figure 6-1

Status / error displays of the DP/DP Coupler

Table 6-1 ON 1 Off

Meaning of the LEDs ON 1 and ON 2 ON 2 Off Coupler, Meaning What to do module on.

Voltage not present at DP/DP Switch the power supply Applied supply voltage is not
within permissible range. Coupler

Check the applied voltage. Replace the DP/DP Coupler.


Hardware fault on the DP/DP


On Off On Off On On The DP/DP Coupler is supplied with power from network 1. The DP/DP Coupler is supplied with power from network 2. The DP/DP Coupler is supplied with power from network 1 and 2.

6-2

DP/DP Coupler A5E00244669-03

Diagnostics

Table 6-2

Status / error messages of the DP/DP Coupler LEDs Meaning BF 1 BF 2 What to do

ON 1 and/o r ON 2 On

SF 1

SF 2

On

On

On

On

All LEDs come on for approximately 1 second. DP/DP Coupler in startup mode. Diagnostic message on PROFIBUS DP network 1 Diagnostic message on PROFIBUS DP network 2 No connection to DP master on PROFIBUS DP network 1. Possible causes: Analyze the diagnostic data. Analyze the diagnostic data.

On On On

On * *

* On *

* * On

* * *

Verify the correct seating


of the bus connector.

Bus communication to the


DP/DP Coupler is down. operation.

Check whether the bus


cable to the DP master has been interrupted. switch on the power s ppl module supply mod le off and then on again.

The DP master is not in


On * * * On No connection to DP master on PROFIBUS DP network 2. Possible causes:

Switch the 24V DC

Bus communication to the


DP/DP Coupler is down. operation.

The DP master is not in


On * * Flashes * * No data exchange between the DP master and DP/DP Coupler on PROFIBUS DP network 1. No data exchange between the DP master and DP/DP Coupler on PROFIBUS DP network 2. Internal DP/DP Coupler error Get in touch with your Siemens partner.

Check the configuration. Check the PROFIBUS


address.

On

Flashes Flashes

Flashes
*:

Flashes

Flashes

Flashes

Not relevant

DP/DP Coupler A5E00244669-03

6-3