You are on page 1of 3

Company name: Created by: Phone: Fax: Date:

96623802 CR 64-2-2 60 Hz
H [ft] 200 CR 64-2-2, 60Hz Q = 321 US gpm H = 139 ft Pumped liquid = Heating water Liquid temperature = 180 F Density = 60.55 lb/ft eta [%]

180

160

140

120

100

100

80

80

60

60

40

40

20

20

0 0 P2 [HP] 50 100 150 200 250 300 350 400

Eff pump = 76.3 % Q [US gpm]

0 NPSH [ft]

14 12 10 8 6 4 2 0

70 60 50 40 30 20 10 0
1/3

P2 = 14.4 HP NPSH = 9.43 ft

Printed from Grundfos CAPS [2012.05.065]

Company name: Created by: Phone: Fax: Date:


Description Product name: Product Number: EAN number: Technical: Speed for pump data: Actual calculated flow: Resulting head of the pump: Head max: Impellers: Impeller reduc.: Shaft seal: Stages: Pump version: Model: Cooling: Materials: Pump housing: Value CR 64-2-2 A-G-A-E-KUBE A-G-A-E KUBE 96623802 5700835063311
H [ft]

CR 64-2-2, 60Hz Q = 321 US gpm H = 139 ft Pumped liquid = Heating water Liquid temperature = 180 F Density = 60.55 lb/ft eta [%]

180 160 140

3444 rpm 321 US gpm 139 ft 194 ft 2 2 KUBE 2 A A ODP

120 100 80 60 40 20 0 0 50 100 150 200 250 300 Eff pump = 76.3 % 350 Q [US gpm] NPSH [ft] 60 100 80 60 40 20 0

Impeller:

Material code: Code for rubber: Installation: Maximum ambient temperature: Max pressure at stated temperature: Flange standard: Connect code: Pipe connection: Pressure stage: Flange size for motor: Liquid: Pumped liquid: Liquid temperature range: Liquid temp: Density: Kinematic viscosity: Electrical data: Motor type: Rated power - P2: Main frequency: Rated voltage: Service factor: Motor protection: Motor Number: Others: Net weight: Gross weight: Sales region:

Cast iron EN-JS1050 ASTM 80-55-06 Stainless steel DIN W.-Nr. 1.4301 AISI 304 A E

P2 [HP] 15

10

40

5 P2 = 14.4 HP NPSH = 9.43 ft


10 5/8" " 7 3/8" "

20

104 F 232 psi / 250 F ANSI G 4" 125 Lb. 254TC


16 1/8" "

PRIMING PORT (G 1/2)

G 1/2" 4" ANSI 125 LB R.F. 8x 3/4"

29 3/4" "

Heating water 32 .. 248 F 180 F 60.55 lb/ft 0.0388 ft/h

G 1/2 PLUG WITH 1/4"TAP FOR GAUGE/ SENSOR

1 3/4"

5 7/8"

7 1/2"

5 1/2"

7 1/2" 9 7/8" 14 3/8" 10 1/2" 4x 9/16" 13"

3 15/16"

BALDOR 20 HP 60 Hz 3 x 230/460 V 1,15 None 84Z03374

338 lb 356 lb Namreg

9"

Printed from Grundfos CAPS [2012.05.065]

2/3

Company name: Created by: Phone: Fax: Date:

96623802 CR 64-2-2 60 Hz
Input Select Application Overview mode Input overview: Installation Type Replacement Flow (Q) Head (H) More Pumped liquid Minimum liquid temperature Liquid temperature during operation Maximum liquid temperature Ambient temperature Minimum inlet pressure Allowed flow undersize Maximum operation pressure Control mode Select type of hydraulic Heating season Energy price Increase of energy price Calculation period Evaluation criterion Pumps per product proup Maximum number of results Frequency Phase Starting method 3-phase In-line canned rotor Inline Multistage Inline single stage End-suction long-coupled End-suction close-coupled End-suction close-coupled horizontal multi-stage Horizontal splitcase Load profile Flow Head P1 Eff total Time Consumption Quantity 1 2 3 4 100 75 50 25 122 142 152 153 15.9 14.4 12.1 9.79 68.8 66.5 56.4 35.0 410 1026 2394 3010 4862 11023 21520 21967 1 1 1 1 % % kW % h/Year kWh/Year Yes Heating Circulation No 300 US gpm 122 ft Yes Heating water 68 F 180 F 200 F 68 F 21.8 psi 2% All psi Uncontrolled Single 285 days 0.20 $ 6% 15 years Electricity consumption 2 8 60 Hz 1 or 3 DOL Yes Yes Yes Yes Yes Yes Yes Sizing result Type CR 64-2-2 Quantity 1 Motor 20.1 HP Flow Head Min.inlet pressure Power P1 Power P2 Eff pump Eff motor Eff pump+mtr Eff total Consumption CO2 emission Price Total costs
H [ft] 200

321 US gpm ( +7%) 139 ft ( +14%) 0.73 psi ( 199.4 F, against atmosphere) 12.1 kW 14.4 HP 76.3 % 89.0 % 67.9 % =Eta pump * Eta motor 67.9 % =Eff relative to the duty point 59373 kWh/Year 74800 lb/Year On request On request /15Years
CR 64-2-2, 60Hz Q = 321 US gpm H = 139 ft Pumped liquid = Heating water Liquid temperature = 180 F Density = 60.55 lb/ft eta [%]

180

160

140

120

100

100

80

80

60

60

40

40

20 Eff pump = 76.3 % 0 P2 [HP] 50 100 150 200 250 300 350 400 Q [US gpm]

20

0 NPSH [ft]

15

60

10

40

5 P2 = 14.4 HP NPSH = 9.43 ft

20

Printed from Grundfos CAPS [2012.05.065]

3/3

You might also like