Objective : 1) To enhance the security control on petroleum and flammable materials and 2) To ensure they are safely managed and handled at all times
Control Measures
IMPORT TRANSPORT STORAGE SALE & SUPPLY
TRANSPORT
STORAGE
CONSIGNEE
WAREHOUSE
CONSIGNOR
CONSIGNEE
Registration with Singapore Customs Dept Application for SCDF Storage licence Application for SCDF import licence Declaration to Customs Tradenet System Verification at Customs checkpoint Verification at storage premises
Application for transportation licence Checks by approved inspection bodies Transportation hours Transportation routes Orange plate, tracking device & immobilizer Transport emergency response plan HazMat Transport Driver Permit Responsibility of vehicle owners Responsibility of vehicle drivers
Application for storage licence Construction of licensed premises Register for P&FM stored Material Safety Data Sheets Emergency Response Plan Company Emergency Response Team (CERT)
Ensure purchaser or recipient holds valid license to transport and store; Keep and maintain transaction records for 2 years Produce the records for inspection
Definition
Petroleum
(i) Class 0 : Liquefied Petroleum Gas; (ii) Class 1 : Flash point less than 23 degree C (iii) Class II : Flash point between 23- 61 degree C (iv) Class III : Flash point between 61-93 degree C
Petroleum
Class 0, I & II petroleum - all regulated Class III petroleum - diesel only
Exemption quantity for import license Type of Quantity Flammable Material Solid 10 kg Liquid Gaseous 20 liters 130 kg (gross weight) in not more than 2 cylinders
Medicine & Pharmaceutical products Cigarette lighters and portable gas lighters Cosmetic and beauty products including hair styling products Food and beverages including beer, wine and liquor Adhesives Insecticides and pesticides Paints & Varnishes Lubricants
Storage License number (FS12342006) Import license number (FI12342006) Importer CR number (12345670000A) HS codes (12345678) Product codes (SCDABC1234L1)
Rejection messages
1. 2. 3. 4.
Pls provide a valid SCDF header import license Pls check trader CR no. Pls contact CA for clarification if reqd. Pls provide correct product code Pls check product quantity unit item
Import below the exemption quantity Import of mixture Import of other P&FM not included in the license Import of other P&FM not included in the storage license
Penalty
FSA, Section 56 A fine not exceeding $10,000 or imprisonment for a term not exceeding 6 months or both.
Questions?
Rejection Messages
1. Pls provide a valid SCDF header import license i) To key in valid Import license (FI12342006)
BACK
Rejection Messages
2. Pls check trader CR no. Pls contact CA for clarification if reqd i) The importer need a valid import licence from SCDF.
BACK
Rejection Messages
3. Pls provide correct HS code / product code i) The importer or the declarant needs to enter correct SCDF HS code or product code.
BACK
Rejection Messages
4. Pls check product quantity unit item The importer or the declarant needs to enter correct U.O.M (unit of measure) eg. Kgm, Ltr or Tne
BACK
i)
Import below the exemption quantity The applicant is required to request for a temporary license number from SCDF.
BACK
2.
BACK
Click E-Services
New Application
New HS Code
Questions?
Minor Storage
Ref: SS 532 Table 2
Location Category 1 & 2 (i) 5 L or (ii) 0.2 L/m2 Storage: (e.g. Warehouses) Laboratories: And not more than 20L per minor storage area Category 3 (i) 10 L or (ii) 0.5 L/m2 And not more than 50L per minor storage area Category 4 Mixed Category (i) 20 L or (ii) 1.0 L/m2 And not more than 100L per minor storage area
Factories:
(i) 10 L or (ii) 0.5 L/m2 And not more than 50L per minor storage area
(i) 20 L or (ii) 1.0 L/m2 And not more than 100L per minor storage area
(i) 50 L or (ii) 20 L/m2 And not more than 200L per minor storage area
A liquid having a flash point < 230C and initial boiling point 350C A liquid having a flash point < 230C and initial boiling point > 350C A liquid having a flash point 230C and 600C A liquid having a flash point > 600C and 930C
Ref: SS 532 Clause 3.12.1
Category 2
Category 3
Category 4
Separation Distance
a) The minimum separation distance between two indoor minor storages:
10m for a non-sprinkler protected area 7.5m for a sprinkler protected area
Separation Distance
b) The minimum separation distance between an indoor minor storage and a safety cabinet:
Separation Distance
c) The minimum separation distance between an outdoor minor storage and the boundary/on-site facility/protected places shall be 1.5m. Separation distance between two outdoor minor storages shall be 7.5m.
Note: Placing more than one outdoor minor storage is not encouraged as they pose higher fire risk.
Separation Distance
d) The minimum separation distance between an indoor and outdoor minor storages shall be 5m. If they are separated by a 2-hr fire rated wall capable of preventing the spread of fire, the separation distance may be measured in a horizontal plan around the end of the wall which intervenes.
1. Max capacity 2L/m2 2. Can be at any level except basement 3. Sprinkler building 10 m separation distance between two groups (3 cabinets) of cabinets. 4. Non-Sprinkler building 10 m separation distance between two groups (2 cabinets) of cabinets. Quantity of storage per fire safety cabinet < 250L
THANK YOU