You are on page 1of 15

Dynamic Effects Produced on Transmission Towers due to Line Cable Rupture

1 2

Neftal Rodrguez- Cuevas , Roger Morales- Hernndez


1

Investigador, Instituto de Ingeniera, Universidad Nacional Autnoma de Mxico, Apdo. Postal 70-472, 04510, Mxico, D.F., Tel. (55)5622-3472; nroc@pumas.iingen.unam.mx. 2 Graduate student. Consejo Nacional de Ciencia y Tecnologa (CONACYT). Universidad Nacional Autnoma de Mxico, Apdo. Postal 70-472, 04510, Mxico, D.F., Tel. (55) 56 23 35 00 ext. 1015.
ABSTRACT

In the analyses of aerial lines of electric energy, is common the use of models, in which the support towers are considered as isolated structures, without any consideration of their interaction with isolators chains, hardware and cables. On the other hand, wind loads are applied as static forces on the structure, as its own weight and accessories, but there exist other type of actions, with dynamic characteristics, as those produced by cable rupture. On this paper are presented the results obtained from a mathematical model, on which were considered all the elements that form a portion of a transmission line, with support towers, hardware, isolator chains and cables; it was used to analyze the dynamic effects produced by the accessories on the support towers. A method was developed to simulate cable breakage, by the use of a time dependant function by which the dynamic effects were evaluated, on two support tower, with different foundation conditions.
INTRODUCTION Technical norms for structural design usually take in consideration the possible line rupture on transmission towers, assuming amplified static loads that induce an internal disequilibrium on the support towers; it is an oversimplification of the phenomenon of what happens in the line. The rupture acts as a longitudinal impact load, transferred through the line to the tower hardware and isolation chains, producing torsional moments on the supporting towers, inducing important amplification on the acting forces on each member of the tower. This is the main reason to study these dynamic effects Clear evidence in Mxico is found on the collapse of a great number of supporting towers on electric transmission lines all over the country, produced by meteorological events, strong hurricanes, or severe down pour storms (ref. 3); the last type of event differs on the air velocity profile, as compared with a hurricane event; design recommendations on our country do not specified design procedures for strong down pour events. On ref. 6 velocity profiles only correspond to velocity profiles observed when a hurricane occurs on the coastal zones. 1. CHARACTERSTICS OF PART OF A TRASSMISION LINE UNDER ANALYSIS The analysis and design of a transmission line was reviewed; it is located near Ciudad del Carmen, Campeche, with support towers type 68T10, whose height is equal to 67.53 m., and carries two circuits and six phases (one at each cross arm), originally design with Mexican specifications (ref. 9).

The part of the line under analyses is formed by two support towers, of the type previously mentioned, which support three 450 m. spans, (see fig.1); on each tower were considered six isolator chains; they support the six lines, on each cross arm; besides, two ground lines were on top of the tower directly connected to hardware on top of the towers.

Fig.1 Portion of the line selected for the dynamic analyses

Support towers are formed by angular steel members, type L1, (ref.7). Some of them have yield stress equal to Fy = 2530 Kg/cm2 (A36), and others with Fy = 3515 Kg/cm2 (Grade 50 steel). Line conductors and the ground lines were design to satisfy common specifications (ref. 9), and their properties are mentioned on the following paragraphs. a) Line conductor ACSR 1113 kCM Bluejay,
Table 1. (ref. 9) Concept Exterior diameter Cross area Weight per unit length Rupture force Initial Young modulus Final Young modulus Initial thermal coefficient Final thermal coefficient Number of wires (aluminum/steel) Properties 32 mm 2 603 mm 1.870 Kg/m 14,030 Kg 2 5,483 Kg/mm 2 6,587 Kg/mm -6 20.53 x 10 /C -6 20.80 x 10 /C 45/7

b) Extra galvanized high strength ground line:


Table 2. (ref. 9) Concept Exterior Diameter Cross area Own weight per unit length Rupture force Initial Young modulus Final Young modulus Thermal coefficient Number of wires (steel) Properties 9.5 mm 2 51.2 mm 0.406 Kg/m 4,900 Kg 2 15,747 Kg/mm 2 18,137 Kg/mm -6 11.52 x 10 /C 7

Fig.2 Support tower selected for analyses WIND ACTION ASSESSMENT Two different wind conditions were considered: a) Regional wind speed obtained from isotacs (ref 2) produced by hurricanes acting on coastal areas. b) Wind speed generated during a down-pour storm. Wind action was assessed by three different design codes, in order to compare their values, assuming on all of them a 144 km/h. as regional velocity at 10 m a) CFE Wind Design Handbook (ref. 6). b) British Standards 2005 (ref. 2). c) Eurocode 2005 (ref. 5).

TYPE OF FOUNDATION AT THE BASE OF THE SUPPORT TOWERS In order to know the effect of different subsoil conditions on the structural behavior of the towers, two different subsoil conditions were selected for them; under one tower it was assumed it was supported by a slab, to which it was connected. It was assumed that the slab might rotate around three different centroidal axes, but displacements were restricted; with these restrictions it was expected to simulate the condition of a foundation over subsoil with low compressibility (high strength capacity). Under the other tower it was considered a foundation formed by a horizontal slab to which the tower was connected. On the four sides of the slab, four vertical metallic sheet piling walls were connected, to form a cofferdam, to transmit vertical loads by friction, to the surrounding low capacity soil. The horizontal concrete slab was 20 cm thick, and the vertical sheet piling was considered 12m deep, to confine the subsoil and increase its load capacity. For this foundation it was assumed the possibility of translations on three orthogonal directions, and rotations around those axes; their magnitudes were dependant on the foundation stiffness in contact with low capacity subsoil. VERTICAL VARIATION OF WIND VELOCITY WITH HEIGTH, DURING A DOWN BURST STORM. As mentioned by Kim y Hangan (ref. 8), a down burst storm is a natural phenomenon produced by a sudden vertical flow of air, that creates vortex rings when strikes the ground, generating strong winds in short time; ground wind speed may increase from 37 to 185 km/h. on two minutes interval. Maximum wind speed appears at an altitude close to 5% the storm diameter. The wind velocity profile near the ground is shown on Fig. 3; from it, expressions to asses wind velocity variation with height were represented by a power law, in two intervals. In order to define the exponent of the power law at each interval, the approach mentioned by Benjamin and Cornell (ref. 1) was selected, by adjusting the wind data in a logarithmic space to a straight line; it is equivalent to adjust a power law to data in that space. The procedure to adjust the data was based on the following scheme:
Z Vz = V10 En donde: 10

Vz Z = V10 10

Ln

Vz Z = Ln V10 10

Vz V1
0

= = =

Average wind speed at height Z over ground level, Km/h. Average wind speed at10 m over ground level, Km/h. Exponent that defines wind velocity, v z at height z

Fig.3 Downburst wind speed profile a) By the following change of variables: Vz Z y = Ln x = Ln V10 10 b) Representing variables x and y in a logarithmic plane of reference. c) Data was represented on the logarithmic space, and a straight line y = Ax + B was adjusted. d) Coefficient A represents exponent for the power law On following paragraphs are presented expressions to evaluate average wind velocity for design purposes at different height over ground level, for the following intervals: a) From 0 to 10 m; b) from 10 to 50 m, being the upper value the height at which maximum velocity appears; c) from 50 to 280.90 m, maximum height at which the effects of the down-burst is felt. 1. For Z 10 m: VD = FrZ FC FT V10 ..... (1) FrZ = 1.00, assuming wind velocity is kept constant between 0 to 10 m. 2. For 10 m < Z 50 m:
FrZ = (z / 10) ,

being = 0.1732

VD = (z / 10) (FC FT V10 )

..... (2)

Fig. 4 Parameter for height 10m Z 50m

3. For 50 m < Z 280.90 m:


FrZ = 2.725 (z / 10) , being = -0.4137

VD = 2.725 (z / 10 ) (FC FT V10 )

..... (3)

y = - 0.4137x + 1.076

Fig. 5 Parameter for height 50m Z 280.9m DESCRIPTION OF THE MATHEMATICAL MODEL SELECTED TO REPRESENT THE TOWER Elements selected for the support tower SAP program was used and the tower elements were represented as bar elements with three degrees of freedom, i.e. displacements on three orthogonal directions were allowed at each node, (Ux0, Uy0, and Uz0). Due to the small value of the moment of inertia of their sections, flexural moments were rather small; it was considered that the angular rotations were close to cero, (Rx0, Ry0, and Rz0).

Line conductors Program SAP2000 has a command to generate these types of elements, once data for the acting tension is given, and the maximum vertical value at the span center is also given, (defined from a static analysis). Conductors were divided in 180 portions for integration purposes, according to what is mentioned on ref. 10; hence fore tension forces on all the portions were kept constant along its whole length. Hardware and isolator chains Hardware was modeled according criteria mentioned on what follows: a) Bar elements with equal stiffness and weight to hardware properties mentioned on ref. 13. b) Hinged on its upper end to cross arm end, allowing lineal displacements, (Ux0, Uy0, Uz0), and its lower end free to move without any restriction. c) Line conductors were attached to the lower end, and their actions were considered as concentrated loads, due to conductor own weight, wind action on them and priestesses tension. d) Suspended isolators properties were taken from ref. 4: Young modulus: E = 3,110,000 Kg/cm2. Tensile strength = 2700 Kg. Lineal elastic behavior was considered for them. Every isolator chain was assumed formed by twenty porcelain units (for a 400 KV line); its length was made equal to 2.95 m. Isolator chain weight: 250 Kg (ref. 13). Mass distribution and damping considered for the elements During a dynamic analysis, SAP2000 program considers half of the mass of each element, concentrated on its connection to other elements; therefore half of its mass is concentrated on one end, and the other half, to the other end. This assumption was considered for all the tower elements, conductor lines and isolator chains. As far as damping is concerned for dynamic analyses, for elements of the tower, a value 0.01 was used (as fraction of their critical damping) as mentioned on ref. 11. For line conductors, hardware and isolator chains, a value 0.02 were selected, as obtained from numerical models mentioned on ref. 10. Geometric non linearity (P effect) Two different type of analysis were carried out: a) Linear analyses, and b) Non-linear geometric analyses.Non linear geometric analysis is needed when P effects appear, due to eccentricity of axial load on compression members of the support tower; secondary flexural moments appear and produce increase on internal forces on the tower elements (see fig. 6.)

Fig. 6 P effect on compression members

TIME INTEGRATION FUNCTION SELECTED TO REPRESENT RUPTURE OF A LINE CONDUCTOR In order to simulate conductor rupture on the analyzed models, it was necessary to develop a time integration function, to represent the progressive relaxation of prestressed tension on one conductor that produces rupture on it, (see fig. 7). In what follows, is mentioned each time interval selected, its duration and the effect produced on the line conductor: a) First stage. On this 3 second interval (0.00 s. t1 3.00 s.), it is assumed a progressive conductor tensioning, to reach the design tension, (50% of the ultimate strength of the line conductor). b) Second stage. During 7 seconds, (3.00 s. < t2 10.00 s.), it was assumed the conductor tension was kept constant; during this stage it was assumed a stable behavior of the system, under design conditions, i.e. no damage appeared on any element of the line. c) Third stage. On this stage, lasting 0.5 s, (10.00 s. < t3 10.50 s.), the tension force on the conductor is lost, in a lineal decrease, reaching at the end of the stage a zero magnitude at t = 10.5 s, reproducing the line conductor fracture, and generating an unstable behavior on the tower. d) Fourth stage. In order to review the effects produced by the fracture on the system elements, a final stage was selected (10.50 s. < t4 25.5.), to observe the dynamic effects produced by the loss of line conductor tension.

Fig. 7 Time integration function to represent line rupture

Fig. 8 Time integration function for constant load On Fig. 8 is shown the time integration function selected to represent constant load application, during an interval equal to 25.5 s.

Those time integration functions were introduced at SAP 2000 program, and used for analyses as Time History Linear. For the dynamic analyses, Newmarks time integration method was used, as recommended by ref. 10. DYNANIC LOADS CONSIDERED On the dynamic analyses carried out, only one line conductor failure was considered on the load combinations used; a concentrated load at hardware free end was considered, with the time integration function shown on Fig. 7, when a line conductor failed, or on the cross arm node, when a ground conductor broke. All the other loads were kept constant for each combination selected, following the time integration function shown on Fig. 8. Several dynamic analyses were performed, under the following load combinations: a) Support own weight, assumed constant during the analysis. b) Line conductor weight, assumed constant during the analysis c) Wind load on tower elements, assumed constant during the analysis d) Wind load on line conductor, assumed constant during analysis. e) Tensile force produced by unbroken line conductor, assumed constant during analysis. f) Variable tensile force, produce by broken line conductor. g) Variable broken line conductor load. h) Variable wind load over one broken line conductor. SOIL-STRUCTURE INTERACTION A previous result mentioned on ref. 12, indicated that soil shear modulus, G, is an important parameter to define the dynamic properties of the support tower and the displacements at all the points of the tower above ground. Also the type of foundation defines the soil-structure interaction. On ref 12 are given nomograms to asses the foundation stiffness, when the tower bears on top of a square concrete slab with sides whose length is equal to B, surrounded on its four sides by sheet piling walls, with a depth equal to D. In order to define foundation stiffnesses, the following parameters were used: D/B, soil shear Young modulus (G); D was sheet piling depth, and B, width of the upper slab forming the foundation. Selected foundation A slab, with dimension B=7,18m was selected to cover all the tower base, with four reinforced concrete edge beams ( 40cm x 45cm), to support metallic sheet piling walls,1.30 cm thick and 12 m deep; Fy = 3,500 Kg/cm2 y E = 2.10 x 106 Kg/cm2. Sheet piling walls were selected to confine the subsoil inside them to reduce its compressibility, in order to decrease both displacements and rotations around three orthogonal directions at the tower base. Concrete slab strength was equal to fc = 500 Kg/cm2, selected to reduce excessive cracking produced by tension developed on top of the slab. Soil shear modulus of elasticity was assumed equal to G = 90 Ton/m2, to represent a low capacity subsoil. It should be mentioned that shear modulus G, for low capacity soils, have values on the range 60 to 300 Ton/m2.

Foundation stiffnesses. From nomograms obtained from finite element analysis, it was possible to represent the results through adjusted equations. In what follows, are given the functions to obtain the vertical, horizontal, angular and torsional foundation stiffness, in terms of soil shear modulus G, and the geometrical dimensions: D, depth; and B, side length; RLV, vertical lineal stiffness; RLH, horizontal lineal stiffness; RLA, angular rotational stiffness, and RLT, torsional stiffness:

RLV D D D = 2.3266 3.1895 + 4.5773 + 0.4346 ....................... (4) GB B B B


RLH D D D = 96 .2037 126 .491 + 68 .2813 + 30 .9014 ...... (5) GB B B B
3 2

RLA D D D = 7 .1085 + 5.5871 + 0 .1745 + 0.0607 ....... (6) 3 GB B B B


RLT D D D D = 106.4499 167.9178 + 84.3957 + 27.0207 + 6.0273 .................... (7) 3 GB B B B B
4 3 2

By use of these equations, foundation stiffnesses were evaluated.


Table 3. Foundation stiffnesses selected for the tower B (m) 7.183 D (m) 12.00 G 2 (Ton/m ) 90 RLV (Ton/m)
6,482.63

RLH (Ton/m) 155,476.801

RLA (Ton-m/Rad)

RLT (Ton-m/Rad)

1,637,374.776 11,105,794.980

For the second support tower, a concrete slab was selected, assuming the subsoil had high capacity. It was modeled by four finite elements, with 6 springs to represent the stiffness on the nine nodes; Fig. 9 shows the mathematical model selected for the slab foundation under the second support tower.

Fig. 9 Stiffness springs used to model soil structure interaction

SUPPORT TOWER DESIGN REVIEW All members forming the support towers, under axial load, were reviewed by the use of the recommendations mentioned on the Complementary Technical Norms for Steel Structures Design and Construction, contained on the Federal District Building Code-2004 (ref. 11): those norms were also used to check all joints design found on construction drawings. These check up was done in order to observe the effects of down burst appearance or line conductor rupture, on the original tower design, based in other recommendations, (ref. 9), commonly used on the normal design practice for the original tower design, based on isolated tower under static loads; line conductor rupture also assumes static loads to represent the rupture, on the traditional norms. COMMENTS ON RESULTS OBTAINED Comments on wind load assessment A comparison of wind loads obtained by the use of Mexican Norms, (ref. 6), British Standards. (ref. 2) and Eurocode 2005 (ref. 5) was done; on Fig. 10 are shown the differences obtained; it may be noted that wind loads evaluated by Mexican norms, were always higher than those obtained from the other two codes already mentioned.

Fig. 10 Wind forces variation with height for 45 angle of attack The differences shown are explained, by the assessment of design pressures defined by the norms used. Both the British Standards and the Eurocode, select design wind velocities that correspond to average values on 10 min. intervals, whereas the Mexican Norm, recommends design velocities, based on average values recorded on a 3 sec interval. Also it should be mentioned that the British Standard, accepts an increment factor associated to wind direction, and a reduction factor due to minimum temperature; it produces that the wind loads recommended by the British Standard are the smaller loads shown on Fig. 10. The Eurocode 2005(ref

5), recommends a reduction factor for ultimate axial strength in all members, in order to consider structure slenderness effects. On Fig. 11a, comparison is made for the design pressures recommended by each of the methodologies under analysis, which explains the differences observed on the assessment of wind forces acting on different heights above ground level

Fig. 11 Computed design pressure used on each studied methodology On Fig.12 are shown the wind loads produced at different angle of attack, which varied from 0 , 90 and 45 ; the last angle resulted the one that produced maximum loads, because the exposed areas are the highest of all the angles analyzed. Loads shown on Fig. 12 correspond to wind actions produced by application of recommendations mentioned on ref.6. From the above mentioned results, it is advisable to perform wind action analyses, when wind direction forms a 45 angle of attack, with respect to the line direction, and assess the loads by recommendations given on ref. 6.

Fig. 12 Computed wind loads for different angles for attack, evaluated by CFE handbook Torsional moments produce by line conductor rupture

Evolution of the torsional moment around the vertical axis of both analyzed towers, is shown on Fig. 13, at the cross section of the tower near the first cross arm, portion of the tower on which failure has been detected, according information given by the Federal Commission on Electricity, (ref. 3). Curves on Fig. 13 represent the evolution on the range 10.5 to 15 sec; on the first 4.5 s, after line conductor failure; it shows four peaks on the torsional moment value, the second gives the maximum computed values for both support towers. For the tower on low capacity sub soil, the first peaks shows an increased value equal to 64.39 %, whereas for the second peak 102.78 % increased was obtained; these results suggest that the tower failure appears at the first peak, after the line conductor failure, that is, when t= 11 s. For the tower with high capacity subsoil, the first maximum on torsional moment value represents a 28.6 percent increase respect to its value with static equilibrium; this increased value, might be supported without failure by the tower, due to the security factors commonly used on steel design. However, for the second maximum, there is a 93.36 % increase on torsional moment, condition that necessarily produces the tower collapse, when t = 12.5 s.

Fig. 13 Torsional moment evolution for towers over different soils These results clearly indicate the need to consider dynamic effects on the structural analyses of support tower on electric transmission lines, as well as to consider soil structure interaction, as an important factor on the design of these types of structures. Usual analyses of isolated towers, under static equivalent loads, do not take into consideration amplification factors due to the impact loads produced by cable rupture. FINAL COMMENTS a) On structural analyses considerations As result of the analyses carried out, it is possible to mention that translations and rotations at the tower base; displacements atop of the tower and total stresses at the tower members did not showed great differences when a linear or a non-linear analyses were carried out; nevertheless, it is advisable to rely on non linear analyses, (differences observed indicated 7 percent variations with respect to the linear approach), because there is always the possibility of failure of two or more line conductors at the same time. For this situation, geometrical effects produced by P- effect, may be quite important, as compared with a linear approach. As a result of the study carried out, it should be recommended that analyses of transmission lines should consider structural models on which interaction between support towers and line conductors is

reproduced, in order to consider dynamic effects produced by wind action on conductors, and on its rupture. The study presented in this paper showed the appearance of impact loads on cross arms. It became evident that the analysis of the isolated support tower produced a design, on which all the members supported axial loads with allowable code stresses. When a second analysis was carried out on the design, with due consideration of a complete portion of the line, and the possible rupture of line conductors, more than 150 members of the tower did not satisfy code requirements. Also, the structural model of the line should consider soil structure interaction at the tower base, with due consideration of foundation stiffness. The analysis carried out indicated that for towers over soft soil, the displacements at its top became 46 percent higher than those computed for the same tower over a rigid foundation, in orthogonal direction of the line. This result indicates that the tower on rigid foundation is stiffer than the one on soft soil. Therefore, stability conditions of the line are highly dependant on subsoil conditions. b) On cable rupture effects Eight models were reviewed in order to seek for all the possibilities of cables rupture between the two towers selected as a general structural model, On each model, one cable on different position was assumed to fail, looking for the worst condition for failure. It was found that when a cable supported by the lower cross arm fails, its effects become the critical condition for the support tower. This type of failure produced buckling on diagonals close to the cross arm; they had the longest lengths as compared with the ones close to the second, third or fourth cross arms, they were the most susceptible to the torsional effects produce by the cable rupture. For the tower diagonal members, the dynamic amplification factor became higher as its position became closer to the failed cable. This study showed that the tower members close to the cross arm where the cable failed, had dynamic amplifications of its axial load, which became 130 percent on panel 17, while on panel 1, the dynamic amplification factor was only 80 percent. c) Effects induced by soil structure interaction On the tower on top a soft soil, axial loads on diagonal members had higher values , as compared to those of the tower on stiff subsoil; by contrast, axial loads on compression members near the foundation, had higher values on the tower on top of a stiff foundation, as compared to those on the tower on top of soft soil. As far as the fail condition on the compression member near the foundation, it was not produced by buckling of the members; it was produced by premature failure of the connections. When the connection design was reviewed, it was found that the number of bolts and their diameter were good enough to support shear forces induced at the connection. Finite element analyses of the connection plates indicated strong stress concentrations on the holes at the plates, with values over the elastic limit. This effect was considered the cause of the premature failure of the connection. Therefore, it seems that there is an absolute need to make finite element analyses of plates and angles close to connections, to identified stress concentration zones, as well as failure lines on them, in order to make a better plate thickness selection, to avoid premature connection failure. REFERENCES [1] Benjamin, Jack R.; Cornell, C. Allin; Probability, Statistics, and Decision for Civil Engineers; McGraw-Hill Book Company; New York, U.S.A.; 1970. [2] British Standard; Guide to: Loading and Strength of Overhead Transmission Lines; 2005.

[3] Comisin Federal de Electricidad. Personal communication.. [4] Electrotecnia: Curso elemental, H. Huvscher, Editorial Reverte, Barcelona, 1987. Sitio de Internet: www.electrini_inc.com. [5] European Committee for Standardization; Eurocode 1: Actions on Structures; Part 1-4: General Actions-Wind Actions; April, 2005. [6] Instituto de Investigaciones Elctricas; Manual de Diseo de Obras Civiles - Diseo por Viento; CFE; Cuernavaca, Morelos; 1993. [7] Instituto Mexicano de la Construccin en Acero, A. C.; Manual de Construccin en Acero Diseo por Esfuerzos Permisibles; 4a. Edicin; Mxico, D.F.; Editorial LIMUSA; 2005. [8] Kim, Jongdae; Hangan, Horia; Numerical Simulations of Impinging Jets with Application to Downbursts; Journal of Wind Engineering and Industrial Aerodynamics; April, 2007. [9] Luz y Fuerza del Centro; Datos del proyecto: Diseo de una torre tipo 68T10 para una lnea de 400 KV; Mxico, D.F.; Mayo, 2006. [10]McClure, G.; Lapointe M.; Modeling the Structural Dynamic Response of Overhead Transmission Lines. [11]Normas Tcnicas Complementarias del Reglamento de Construcciones para el Distrito Federal; Gaceta Oficial del Departamento del Distrito Federal; Mxico, D. F.; Octubre, 2004. [12]Rodrguez Cuevas, Neftal; Lpez Gonzlez, Jorge; Flores Vera, Rafael; Estabilidad de Torres de Transmisin Cimentadas sobre Terrenos de Baja Capacidad; Instituto de Ingeniera, UNAM; 2002. [13]The Ohio Brass Company; Catalog 61: Transmission and Distribution Hardware; Ohio, U.S.A.; 1974.

You might also like