(1) Door alarm The cable for the door sensor of the IBBS should be in serial connection with that of the APM30H cabinet.
(2) Smoke alarm The smoke sensor of the IBBS should be in parallel connection with the existing smoke sensor of the APM30H. Both the smoke sensors should be connected to the SMOKE socket of HMPI.
(3) Battery temperature alarm The battery temperature alarm cable should be connected to the Bat1 Tmp socket, which is a 2-pin straight socket (detection signal port for the temperature sensor of built-in battery) for Boolean input, on the HMPI board at the top of the BTS3900A cabinet. On the BSC LMT, set the type of battery to external battery.