B7 I.S. Cables shall enter the cabinet through cable entries completely separate and opposite from the non-intrinsically safe connecting cables to the control system. SAES-J -903, Sec 8.3. SAIC-J-6904 1-oct-05 INST REFERENCE PASS FAIL SAUDI ARAMCO ID / PID - 3 / 01 / 05 - REV 0 (Standards Cutoff - August 2004)
B7 I.S. Cables shall enter the cabinet through cable entries completely separate and opposite from the non-intrinsically safe connecting cables to the control system. SAES-J -903, Sec 8.3. SAIC-J-6904 1-oct-05 INST REFERENCE PASS FAIL SAUDI ARAMCO ID / PID - 3 / 01 / 05 - REV 0 (Standards Cutoff - August 2004)
B7 I.S. Cables shall enter the cabinet through cable entries completely separate and opposite from the non-intrinsically safe connecting cables to the control system. SAES-J -903, Sec 8.3. SAIC-J-6904 1-oct-05 INST REFERENCE PASS FAIL SAUDI ARAMCO ID / PID - 3 / 01 / 05 - REV 0 (Standards Cutoff - August 2004)
I.S. system wiring shall be terminated in dedicated marshalling cabinets
or compartments within marshalling cabinets that house the associated apparatus. I.S. cables shall enter the cabinet through cable entries completely separate and opposite from the non-intrinsically safe connecting cables to the control system. SAES-J -903, Sec 8.3.1 SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED? SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL TRAVEL TIME SAUDI ARAMCO USE ONLY SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO. PLANT NO. EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR Intrinsically Safe Circuit-Instrumentation, Box, and Barrier Installation and Pre-Commissioning SAIC-J-6904 1-Oct-05 INST REFERENCE PASS FAIL SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE N/A A General Requirements A1 The use of Intrinsic Safety as a protection method is required for all instruments located within Class I, Zone 0 areas SAES-J -903, Sec 1.4 RE-INSP DATE ITEM No. ACCEPTANCE CRITERIA A2 Equipment Installation: (A) Control Drawing. Intrinsically safe apparatus, associated apparatus, and other equipment shall be installed in accordance with the control drawing (s). Exception: A simple apparatus that does not interconnect intrinsically safe circuits. NEC Article 504.10 (A) Conductors of intrinsically safe circuits shall not be placed in any raceway, cable tray, or cable with conductors of any non-intrinsically safe circuit. SAES-J -903, Sec 8.2.1 A3 I.S. systems shall only be used where other methods of protection are impractical (e.g., ship loading arms and inline analyzers). SAES-J -903, Sec 1.4 A4 SAES-J -903, Sec 8.1 B6 Field termination cabinets (junction boxes) shall be NEMA Type 4X or IP 65 (reference NEMA Standards Publication No. 250). SAES-J -903, Sec 8.2.3 The field termination cabinet will serve as a transition point from individual pair/triad to a multi-pair/triad cable. SAES-J -903, Sec 8.2.3 B5 Multi-core cables shall not combine intrinsically safe and non-intrinsically safe signals. SAES-J -903, Sec 8.2.3 SAES-J -903, Sec 8.2.3 B4 B2 Dedicated intrinsically safe field termination cabinets (junction boxes) shall be provided to maintain positive separation of intrinsically safe from non-intrinsically safe wiring. SAES-J -903, Sec 8.2.3 B3 Where several intrinsically safe instrumentation loops are involved, individual pair/triad from each instrument located in the field may be routed to a common field termination cabinet. B1 JB Requirements: The intrinsically safe instrument enclosure shall be sealed to provide adequate ingress protection (NEMA 4X or IP 65). A5 Care shall be taken to avoid locating interconnecting cables containing intrinsically safe circuits close to overhead power distribution lines or heavy current carrying cables. Refer to SAES-J -902 for minimum spacing requirements between parallel cable runs of different signal types.( Attachment 1) B. Installation Requirements SAES-J -903, Sec 8.2.5 Page 1 of 5 C6 When zener diode type barriers are used, the maximum resistance between the farthest point on the intrinsic safety barrier ground and the plant grounding system (the point at which the incoming electricity supply neutral is grounded) shall not exceed 1 Ohm. SAES-J -903, Sec 8.4.3 C5 Where screens/shields are used, they shall be covered by an outer insulating sheath. They shall be grounded at the associated apparatus intrinsic safety ground point and insulated at the hazardous area end. Where screened multipair / multitriad cables interconnect within field junction boxes with individual screened pair/triad cables, insulated terminals shall be provided for the ongoing continuity of the screens/shields. SAES-J -903, Sec 8.4.2 In cabinets housing the associated apparatus, the intrinsic safety ground bus shall be connected to a node in the overall plant ground grid by dedicated, redundant, insulated copper cables not smaller than #4 AWG. To identify the intrinsically safe grounding conductors as being different from other ground connections, the grounding conductor insulation color shall be green with blue tracer (or banded with blue tape) SAES-J -903, Sec 8.4.2 B10 B11 Multi-pair/triad cables shall be routed from the field termination cabinets (junction boxes) to the control room or process interface building in cable trays, in conduits, or by direct burial cable provided the cable is approved for cable tray use or for direct burial. SAES-J -903, Sec 8.2.4 Cables: shall be sealed against the passage of gas and vapors as required by the National Electrical Code NFPA 70, SAES-B-008, and SAES-O-126. SAES-J -903, Sec 8.2.4 C2 All spare wires shall be terminated at terminal blocks and grounded to the intrinsic safety ground bus. Unused wires shall also be insulated at their hazardous area ends. SAES-J -903, Sec 8.3.3 C1 I.S. system vendor recommended grounding method to be completed SAES-J -903, Sec 7.6.2 C3 The minimum clearances between terminals of intrinsically safe circuits and any grounded metal shall be 3 mm ( inch), unless that terminal is intended to be grounded. The clearance between two terminals of different intrinsically safe circuits shall be at least 6 mm ( inch). C4 B9 Cabinets that contain the associated apparatus shall be located within air- conditioned analyzer shelters, process interface buildings, or control rooms. SAES-J -903, Sec 8.3.1 CONTRACTOR / SUBCONTRACTOR Intrinsically Safe Circuit-Instrumentation, Box, and Barrier Installation and Pre-Commissioning SAIC-J-6904 1-Oct-05 INST SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER B12 The I.S. cables from the field instrument shall be terminated on the "hazardous area" terminations of the associated apparatus and shall be secured or tie-wrapped separately from the non-intrinsically safe cables terminated on the opposite end "safe area" terminals of the associated apparatus. A minimum of 2 inches (50 mm) shall be maintained between the I.S. and non-I.S. cables within the cabinet that contains the associated apparatus. SAES-J -903, Sec 8.3.2 SAES-J -903, Sec 8.3.4 SAES-J -903, Sec 8.2.5 N/A RE-INSP DATE ITEM No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL B10 Signal Segregation: The standard practice of separating thermocouple, 4-20 milliamp, and digital alarm signals shall be observed. This segregation shall be maintained in the field via dedicated, intrinsically safe field junction boxes. Signal segregation shall be maintained up to the marshalling panels, where signals may be consolidated to the extent specified in SAES-J -902. C. Grounding and Identification Requirements B8 I.S. cables shall enter the cabinet through cable entries completely separate and opposite from the non-intrinsically safe connecting cables to the control system. SAES-J -903, Sec 8.3.1 Page 2 of 5 CONTRACTOR / SUBCONTRACTOR Intrinsically Safe Circuit-Instrumentation, Box, and Barrier Installation and Pre-Commissioning SAIC-J-6904 1-Oct-05 INST SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER N/A RE-INSP DATE ITEM No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL NEC Article 504.80 (A) C12 Light blue color coding shall be used to identify intrinsically safe wiring. The preferred practice is to specify intrinsically safe interconnecting cables with a blue outer jacket. Alternatively, blue sleeves slipped over the jacket at all points of termination may be used to identify I.S. wiring. SAES-J -903, Sec 8.5.3 C13 Terminals: Intrinsically safe circuits shall be identified at terminal and junction locations in a manner that will prevent unintentional interference with the circuits during testing and servicing. C11 All junction boxes, cable trays, conduits, cables, cabinets, and instrument housings shall be labeled as containing intrinsically safe circuits or equipment. The means of identification shall be visible after installation. Label spacing on cable tray, conduit, and interconnecting cables shall not exceed 25 feet (8 meters). SAES-J -903, Sec 8.5.2 C10 All intrinsically safe system components shall be so identified. SAES-J -903, Sec 8.5.1 C9 Cable protective armor, if used, shall be grounded to plant grounding system at the field junction box. SAES-J -903, Sec 8.4.6 C8 All metal cable trays used for intrinsically safe wiring shall be grounded to the plant grounding system with a minimum of #4 AWG copper wire with green insulation. SAES-J -903, Sec 8.4.5 C7 All metal enclosures for intrinsically safe circuits shall be grounded to the plant grounding system with a minimum of #4 AWG copper wire with green insulation. SAES-J -903, Sec 8.4.4 SAES-J -903, Sec 10.2 D. Testing 4. SAES-J -902, Electrical Systems for Instrumentation, 31 J uly 2004 1. Schedule G -- Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), J uly 1993 2. Schedule Q -- Quality Requirements (Pro Forma Contract), November 2003 REFERENCE DOCUMENTS: 3. ISA-RP 12.2.02-1996 Recommendations for the Preparation , Content and Orga. Of Intrinsic Safety Control Drawings, 15 May 1996 6. NEC 2002- National Electric Code 2002 5. SAES-J -903 Intrinsically Safe System, 28 November, 2001. SAES-J -903, Sec 10.3 Any changes, additions/deletions of components to/from a loop, shall be recorded at the operating facility in the appropriate Saudi Aramco drawings. SAES-J -903, Sec 10.4 D2 Only safety barriers/isolators of the same type, make, or catalog number shall be used to replace defective safety barriers/isolators. D1 An I.S. system may be tested and maintained under live (working) conditions provided the portable test equipment used has been certified and approved as intrinsically safe for the particular atmospheric hazard. Otherwise, a hot work permit shall be issued. REMARKS: D4 D3 Only devices of the same make, type, and catalog number or replacement recommended by the manufacturer shall be used to replace any device in the system. SAES-J -903, Sec 10.1 ATTACHMENTS: Attachment -1 Circuit Segregation and Minimum Separation (Millimeters) Page 3 of 5 CONTRACTOR / SUBCONTRACTOR Intrinsically Safe Circuit-Instrumentation, Box, and Barrier Installation and Pre-Commissioning SAIC-J-6904 1-Oct-05 INST SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER N/A RE-INSP DATE ITEM No. ACCEPTANCE CRITERIA REFERENCE PASS FAIL QC Record Reviewed Work Verified Name, Sign and Date: Quality Record Approved: Name, Organization, Initials and Date: T&I Witnessed QC Supervisor Proponent and Others Name, Initials and Date: Performed Inspection or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified Work Verified T&I Witnessed QC Record Reviewed QC Inspector PID Representative indicates compliance with appropriate standards or performance in a specified manner. Construction Representative* Name, Initials and Date: 2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling). 3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products NOTES: 1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID). Saudi Aramco with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the f PMT Representative T&I Witnessed Work is Complete and Ready for Inspection: Name, Initials and Date: Contractor / Third-Party QC Record Reviewed *Person Responsible for Completion of Quality Work / Test Y =YES N =NO F =FAILED Work / Rework May Proceed Name, Initials and Date: 4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization Work Verified Page 4 of 5 SAUDI ARAMCO ID/PID - 3/01/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER Intrinsically Safe Circuit-Instrumentation, Box, and Barrier Installation and Pre-Commissioning SAIC-J-6904 1-Oct-05 INST Attachment -1 Circuit Segregation and Minimum Separation (Millimeters) Page 5 of 5