Siemens Aktiengesellschaft Page 1 of 2 Copyrights Siemens AG 2011 All Rights Reserved SICAM PAS/PQS V7.00 SP2 and later 2011-05 Technical Note Installation on SICAM Station Unit V2.00/V2.10
Siemens Aktiengesellschaft Page 2 of 2 Copyrights Siemens AG 2011 All Rights Reserved 1 Contents
This document describes the installation of SICAM PAS/PQS V7.00 SP2 on a SICAM Station Unit V2.00 and V2.10.
2 Preparation
Since SICAM PAS/PQS V7.00 SP2 and later cannot be installed on a SICAM Station Unit V2.00/V2.10, you must upgrade the hardware on 4GB CF cards and the image on SICAM Station Unit V2.20.
To this end you require the upgrade package (MLFB: 6MD9922-0AH10-0AA0)
3 Hardware Upgrade Proceed as follows to perform the upgrade:
1. Archive your project and back up all important data.
2. Shut down the operating system and switch off the SICAM Station Unit.
3. Replace the CF cards as described in the SICAM Station Unit V2.20 manual, Chapter 6.3.1, The CF Cards Are Defective.
Note The BIOS of the SICAM Station Unit does not need to be upgraded! BIOS-relevant topics/actions described in the manual can therefore be neglected.
4 Installing SICAM PAS/PQS
To install SICAM PAS/PQS V7.00 SP2 or later:
1. Install the SICAM Station Unit V2.20 image. For a description of the procedure, refer to the SICAM Station Unit V2.20 manual, Chapter 6.2, System Restore.
2. Install SICAM PAS/PQS as described in the SICAM Station Unit V2.20 manual, Chapter 5.2, Commissioning, and adhere to the notes in this chapter.
3. Enable all required features in the Feature Enabler.
4. Unarchive the project in SICAM PAS/PQS UI Configuration and enable it in SICAM PAS/PQS UI Operation.
The installation is now complete and you can continue to work with the SICAM Station Unit and SICAM PAS/PQS as usual.