A total of 96 cooling towers of public buildings were registered and inspected. Of the 69 isolates identified, 55 strains (79.7%) were L pneumophila. Colonization was positively associated with the absence of training on Legionella control.
A total of 96 cooling towers of public buildings were registered and inspected. Of the 69 isolates identified, 55 strains (79.7%) were L pneumophila. Colonization was positively associated with the absence of training on Legionella control.
A total of 96 cooling towers of public buildings were registered and inspected. Of the 69 isolates identified, 55 strains (79.7%) were L pneumophila. Colonization was positively associated with the absence of training on Legionella control.
and assessment of control measures Varvara A. Mouchtouri, BSc, PhD, a,b Georgia Goutziana, MD, a Jenny Kremastinou, MD, PhD, b and Christos Hadjichristodoulou, MD, PhD a Larissa and Athens, Greece Background: Cooling towers can be colonized by Legionella spp, and inhalation of aerosols generated by their operation may cause Legionnaires disease in susceptible hosts. Environmental investigations of Legionnaires disease outbreaks linked with cooling towers have revealedpoorlymaintainedsystems, lackof control measures, andfailure of systemequipment. The purposeof this study was toidentify Legionella-contaminatedcooling towers, identify risk factors for contamination, and assess the effectiveness of control measures. Methods: A total of 96 cooling towers of public buildings were registered and inspected, and 130 samples were collected and mi- crobiologically tested. Microbiological test results were associated with characteristics of cooling towers, water samples, inspection results, and maintenance practices. Results: Of the total 96 cooling towers examined, 47(48.9%) were colonizedby Legionella spp, and22 (22.9%) requiredremedial action. Atotal of 65 samples (50.0%) were positive ($500 cfu L 21 ), and 30 (23%) were heavily contaminated ($10 4 cfu L 21 ). Of the 69 isolates identied, 55 strains (79.7.%) were L pneumophila. Legionella colonization was positively associated with the absence of training on Legionella control (relative risk [RR] 51.66; P 5.02), absence of regular Legionella testing (RR52.07: P 5.002), absence of sunlight protection (RR51.63: P 5.02), with samples in which the free residual chlorine level in the water sample was ,0.5 mg/L (RR52.23; P 5.01), and with total plate count (P 5.001). Colonization was negatively associated with chemical disinfection (RR50.2; P 5.0003) andwiththe presence of a risk assessment andmanagement plan (RR50.12; P 5.0005). Astatistically signicant higher age (P 5.01) was found in legionellae-positive cooling towers (median, 17 years; interquartile range [IQR] 55.0 to 26.0 years) compared with noncolonized cooling towers (median age, 6 years; IQR51.0 to 13.5 years). After the 22 legionellae-positive cooling towers were disinfected with chlorine, 2 (9%) of them remained positive for Legionella spp with a concentration $1000 cfu L 21 . Conclusions: Cooling towers can be heavily colonized by Legionella spp and thus present a potential risk for infection. This study demonstrates the importance of a risk assessment and management plan. Water chlorination effectively reduces legionellae contamination. Proper training of cooling tower operators is paramount. Key Words: Legionella; cooling tower; factor; disinfection; risk assessment. Copyright 2010 by the Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved. (Am J Infect Control 2010;38:50-5.) Cooling towers, devices used to cool warm water by evaporation in atmospheric air, can be found in air-con- ditioning systems of buildings such as hotels and hospi- tals. 1 Legionella spp colonization in cooling towers is well documented. 2-5 Aerosols generated by the operation of cooling towers can transmit legionellae to susceptible hosts. 1 Many epidemiologic and environ- mental investigations have linked outbreaks of Legion- naires disease with contaminated water in cooling towers by matching the molecular subtyping ndings betweenwater andpatient isolates. 6-8 Environmental in- vestigations of Legionnaires disease outbreaks linked with cooling towers have revealed poorly maintained systems, 9 lack of control measures and failure of system equipment; 10 consequently, investigators recommend regular maintenance of cooling towers. 7,11-13 Public health authorities in some countries have introduced recommendations, mandatory guidelines, and even legislation for the registration of cooling towers and application of control measures. 9,10,14 The European Surveillance Scheme for Travel-Associated Legionnaires Disease and the European Working Group for Legionella Infections (EWGLI) have published guidelines aimed at controlling and preventing travel- associated Legionnaires disease. These guidelines From the Department of Hygiene and Epidemiology, Medical School, University of Thessaly, Larissa, Greece a ; and Department of Public and Administrative Health, National School of Public Health, Athens, Greece. b Address correspondence to Christos Hadjichristodoulou, MD, PhD, Department of Hygiene and Epidemiology, Medical School, University of Thessaly, Papakiriazi Str, 22, 41222, Larissa, Greece. E-mail: xhatzi@ med.uth.gr. Conicts of interest: none to report. 0196-6553/$36.00 Copyright 2010 by the Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved. doi:10.1016/j.ajic.2009.04.285 50 include design, operational, and management mea- sures for controlling the risk of legionellae proliferation in cooling towers. 15 The World Health Organization (WHO) suggests a hazard analysis approach by imple- menting water safety plans to control the risk of infec- tion from cooling towers. 1 Such a water safety plan species measures for the water source, heat exchanger, distribution system, and the cooling tower, including disinfection, monitoring, and maintenance. But although maintenance of cooling towers and appli- cation of control measures is reasonable and many guidelines make such recommendations, no data exist to support the claim that maintenance minimizes colo- nization by Legionella. 16 Accordingly, the present study was conducted to identify Legionella-contaminated cooling towers, identify risk factors for contamination, and assess the effectiveness of control measures. METHODS Cooling towers of public buildings (eg, hotels, hospi- tals, athletic venues, shopping centers) located inAthens, Thessaloniki, Patra, Volos, and Irakliowere registered, in- spected, and microbiologically tested. Legionella- contaminated cooling towers were disinfected using chlorine compounds according to the EWGLI technical guidelines. 15 Prefecture Department of Public Health personnel conducted the registrations, inspections, and sampling. Microbiological test results were examined to- gether with characteristics of cooling towers, water sam- ples, inspection results, and maintenance practices. Registration and inspection Cooling towers were registered by completing a stan- dardized registry form, including information on name of building, unique registration code, address and typical characteristics such as age, location in the building (eg, rooftop, courtyard), responsible person, methods and means for disinfection and chemical control of fouling, presence of drift eliminators, record keeping, existence of a riskassessment plan, water capacity, and daily water loss. The cooling tower inspections were performed us- ing a standardized inspection report that included 39 scored items. These inspection items were classied into 6 categories: construction, operation, cleaning-dis- infection, personnel, record keeping and onsite manu- ally conducted tests. 17 Data included in the inspection and the registration forms were used to evaluate risk fac- tors possibly associated with Legionella colonization. Sample collection and microbiological analysis methods Methods used for sample collection, storage condi- tions, and microbiological analysis have been described elsewhere. 17 Microbiological analyses for Le- gionella spp were performed by the National Legionella Reference Laboratory of Southern Greece in Athens and the National Legionella Reference Laboratory of Northern Greece in Thessaloniki. The lower limit of detection of the microbiological analysis was 500 cfu L 21 . Remedial actions were un- dertaken in any cooling tower with a Legionella bacte- ria count $10,000 cfu L 21 in one sample or and aerobic count .100,000 cfu mL 21 in one sample. Disinfection procedure Chlorine disinfection was applied to all Legionella- postitive cooling towers according to the following pro- cedure. First, the cooling tower water was chlorinated. The chlorinated water containing 5 mg/L of free chlo- rine, was circulated through the system for 5 hours with the fan off. If the system pH value was .8.0, then the recommended measured residual was in the range of 15 to 20 mg/L of free chlorine to achieve the required disinfection level. All areas of the tower were then cleaned. Cleaning staff wore suitable respira- tory protective equipment. After the cleaning opera- tions, the system was relled and chlorinated to maintain a minimum level of 5 mg/L of free chlorine for a period of 5 hours with the fan off and checked hourly. An alternative cleaning method involved increasing the free chlorine level to, for example, 50 mg/L for 1 hour or 25 mg/L for 2 hours, followed by dechlorination, draining, ushing, relling with fresh water, and adding appropriate startup doses of treatment chemicals, including biocides. 15 Between 2 and 7 days after disinfection, 1 sample was collected from each cooling tower. Disinfection was considered successful when the sample exhibited a Legionella spp concentration ,1000 cfu L 21 and an aerobic count ,100,000 cfu mL 21 . The standardized disinfection guidelines were printed and distributed by the public health personnel in the Prefecture Departments to the persons responsi- ble for the various buildings. Hoteliers, hospital staff, or other responsible persons applied the disinfection procedure, supervised by public health personnel when feasible. Data analysis Data were analyzed with Epi-Info 2000 (Centers for Disease Control and Prevention, Atlanta, GA) and SPSS for Windows release 15.0 (SPSS Inc, Chicago, IL) by the t-test or Mann-Whitney test for quantitative data and by the x 2 test or Fishers exact test for qualitative data. The median and the interquartile range (IQR) were used to delineate the dispersion of quantitative data. Relative risk (RR) and 95% condence interval www.ajicjournal.org Vol. 38 No. 1 Mouchtouri et al. 51 (CI) were calculated to assess categorical risk variables associated with legionellae-positive test results. Varia- bles that were signicant inunivariate analysis were en- tered into a backward conditional logistic regression model. By using conditional logistic regression models, independent predictors of colonization were estab- lished. Variables were retained in the model if the likeli- hood ratio test result was signicant (P # .05). RESULTS A total of 96 cooling towers were examined, and 130 samples were collected. Forty-seven (48.9%) of the cooling towers were Legionella-postitive, and 22 (22.9%) of these required remedial action. Table 1 pre- sents a descriptive analysis of the cooling towers and maintenance and water treatment practices applied during the study period. Of the 130 samples evaluated, 65 (50.0%) were from systems colonized by Legionella spp ($ 500 cfu L 21 ). Thirty samples (23%) had a Legionella concen- tration $10 4 cfu L 21 , and 10 samples (7.7%) had a con- centration .10 5 cfu L 21 . Of the 69 isolates, 55 strains (79.7.%) were L pneumophila, including 52 serogroup 1 (75.4% of total strains) and 3 serogroup 2 to 14 (4.3%), and 14 strains (20.3%) were nonL pneumo- phila (Table 2). Table 3 characterizes the association between cool- ing tower system and operational characteristics with Legionella spp contamination using univariate analysis. Legionella colonization was positively associated with cooling towers in which the responsible person was not trained on Legionella control and Legionella testing was not done regularly (ie, every 3 months). Characteristics of cooling towers that were treated with chlorine or not treated were associated with the concentration of free chlorine measured in the sam- ples. A positive association was found with cooling towers in which the free-residual chlorine of the water sample was ,0.5 mg/L and that were not protected fromsunlight. There was negative association with col- onization and chemical disinfection of cooling towers. In addition, cooling towers with a risk assessment and management plan were negatively associated with colonization. Tables 4 and 5 present the median and IQR of char- acteristics of cooling towers and water samples in asso- ciation with contamination with Legionella spp. A statistically signicant higher age (P 5.01) was found in the legionellae-positive cooling towers (median, 17 years; IQR 55.0 to 26.0 years) comparison with the noncolonized cooling towers (median, 6 years; IQR 51.0 to 13.5 years). The median total plate count was signicantly higher in the legionellae-positive samples than in the legionellae-negative samples (4200 cfu/mL vs 422 cfu/mL; P 5.001). The statistically signicant association between legionellae-positive samples and cooling tower age (odds ratio [OR] 53.00; 95% CI 51.04 to 8.62; P 5.04), system chlorination (OR 52.27; 95% CI 50.08 to 0.89; P 5.03), and microbiological monitoring (OR 54.88; 95% CI 51.33 to 17.86; P 5.01) persisted after strati- ed and logistic regression analysis. After chlorine dis- infection of the cooling towers, legionellae-positive samples with a concentration $1000 cfu L 21 were found in 2 of the 22 cooling towers resampled (9%). DISCUSSION Our results indicate that about half of the cooling towers examined were contaminated with Legionella spp, and 23% of the collected samples were highly contaminated with a concentration $10 4 cfu L 21 . In another study conducted in 15 cooling towers in Spain, about 15% of the collected samples were positive with a concentration .10 4 cfu L 21 . 18,19 The great majority of the systems examined were contaminated with L pneumophila serogroup 1, whereas the primary legion- ellae associated with outbreaks of Legionnaires dis- ease from cooling towers appear to be L pneumophila serogroup 1 MAb2-reactive strains. 1 The fact that only 11.4% of the cooling towers had a water system operational manual available, 24.1% had a risk assessment and management plan in place, and 41.8% had a cleaning and maintenance log indicates that cooling tower operation is not systematically mon- itored in the majority of the devices. No methodical Table 1. Results of descriptive analysis: cooling tower system characteristics, maintenance, and water treatment practices applied Characteristics Number of cooling towers/total (%) Presence of water system operational manual 9/79 (11.4) Presence of risk assessment and management plan 14/58 (24.1) Presence of CT cleaning and maintenance log 33/79 (41.8) Microbiological results record keeping 38/59 (64.4) Application of chemical disinfection 24/60 (40.0) Application of chlorine disinfection 21/94 (22.3) CT located near windows or air inlet conduit 18/79 (22.8) Protection of CT from sunlight 28/79 (35.4) Water source: municipality 48/94 (51.0) Water source: well 1/94 (1.0) Presence of drift eliminators 53/68 (77.9) Presence of automatic chlorinator 13/60 (21.7) System cleaning at least every 6 months 10/79 (12.6) Application of disinfection before CT cleaning 30/79 (37.9) Evidence of system water leakage 8/79 (10.1) Responsible person is trained 24/79 (30.4) Water examination for Legionella 38/79 (48.1) CT, cooling tower. 52 Mouchtouri et al. American Journal of Infection Control February 2010 hazard analysis has been conducted to assess the risks and dene control measures. Only a small number of cooling towers were cleaned (12.6%) and disinfected (22.3%) at least every 6 months. About 30% of the re- sponding cooling tower operators had received training regarding the application of control measures and maintenance of the system. Awareness and instruc- tions regarding prevention of Legionnaires disease are necessary not only for operators, but also for con- tractors and persons who install and clean the devices. This is crucial, considering that many cooling towers are located near windows or air inlet conduits and that 60% of them were not disinfected before cleaning, to limit the risk of inhaling contaminated water. The Hellenic Ministry of Health has enacted manda- tory guidelines for the prevention and control of Legionnaires disease, which include provisions for cooling tower maintenance and application of control measures. Our ndings show that only a small propor- tion of cooling tower operators adhere to these guide- lines, however. An ofcial registry of cooling towers would help identify target groups, provide training, and conduct routine inspections. Another study of 175 cooling towers in Glasgow, Scotland yielded simi- lar ndings, with inadequate drift control, failure to use chemicals, and absence of a log book and guide- lines. 20 Cooling tower maintenance standards should be published and information campaigns directed at those responsible for cooling tower maintenance established. 20 Cooling towers have not yet been linked to incidents of legionellosis in Greece, but the disease is likely underdiagnosed and underreported. No pub- lished data on investigations of outbreaks or incidents in Greece have implicated cooling towers, however. WHO 1 and EWGLI 15 guidelines recommend regular maintenance of cooling tower systems based on the control of fouling due to scale, salt, and microbial growth and maintenance of mechanical components of the system. In addition, regular inspection and appli- cation of corrective measures to eliminate parts of the system that facilitate stagnant water are recommen- ded. Further measures include cleaning all internal parts, including the heat exchanger, to remove dirt, dust, dissolved solids, and organic material. Finally, Table 2. Legionella spp. contamination in cooling towers water samples examined Number of samples/total (%) Organisms Positive With 500 to 999 cfu L 21 With 10 3 to 9999 cfu L 21 With 10 4 to 10 5 cfu L 21 With .10 5 cfu L 21 Legionella spp. 65/130 (50.0) 7/130 (5.4) 28/130 (21.5) 20/130 (15.4) 10/130 (7.7) L. pneumophila serogroup 1 52/65 (80.0) 6/7 (85.7) 23/28 (82.1) 15/20 (75.0) 8/10 (80.0) L. pneumophila serogroups 2 to 14 3/65 (4.6) 1/7 (14.3) 2/20 (10.0) Legionella spp. other than L. pneumophila 14/65 (21.5) 9/28 (32.1) 3/20 (15.0) 2/10 (20.0) Table 3. Association of cooling towers system and operational characteristics with Legionella spp contamination (univariate analysis) Number of positive cooling towers for Legionella spp Characteristics With characteristic (%) Without characteristic (%) RR (95% CI) P Algaecide water treatment 3 (60.0) 14 (58.3) 1.02 (0.46-2.26) .60 Antiscale water treatment 19 (51.4) 8 (57.1) 0.89 (0.51-1.55) .40 Chemical disinfection 4 (16.7) 23 (63.9) 0.2 (0.10-0.65) .0003 Cleaning every .6 months 3 (75.0) 35 (46.7) 1.60 (0.86-2.97) .20 Heterotrophic colony count tests not conducted 26 (60.5) 32 (42.1) 1.43 (1.00-2.05) .04 Legionella spp. tests every 3 months not conducted 25 (65.8) 13 (31.7) 2.07 (1.25-3.43) .002 Sprinklers not properly operated 0 (0.0) 38 (48.1) System components damaged 2 (50.0) 36 (48.0) 1.04 (0.38-2.85) .60 Responsible person not trained 16 (66.7) 22 (40.0) 1.66 (1.08-2.56) .02 Free-residual chlorine ,0.5 mg/L 33 (55.9) 5 (25.0) 2.23 (1.01-4.94) .01 Presence of risk assessment and management plan 1 (7.1) 26 (59.1) 0.12 (0.01-0.81) .0005 Chlorine disinfection 6 (28.6) 41 (56.2) 0.50 (0.25-1.03) .02 Cooling tower not protected from sunlight 18 (64.3) 20 (39.2) 1.63 (1.05-2.54) .02 www.ajicjournal.org Vol. 38 No. 1 Mouchtouri et al. 53 water treatment with corrosion inhibitors to minimize scaling and corrosion and with disinfectants is suggested. In this study, we associated legionellae col- onization with practices applied in cooling towers to identify the factors that can effectively contribute to re- duced legionellae proliferation. Our results demon- strate less colonization in cooling towers with a risk assessment and management plan. This plan includes an integrated approach based on hazard assessment, identication and monitoring of control measures, application of management procedures, and establish- ment of a verication program. 1,15 Biocidal treatment of cooling tower water reduces the density of legionellae. 21,22 According to our results, chemical water disinfection, including chlorination seems to be more effective than other measures imple- mented to maintain the system in good condition and operation, suchas cleaning, repair of constructiondam- ages, and antiscale treatment. These measures did not inhibit contamination signicantly. As indicated in another study, L pneumophila occurs even in well-main- tained cooling towers. 23 However, ndings of other studies are contradictory, because the presence of deposits or aggregates, biolm, and algae seemed to be related to viable counts of legionellae. 18,24 Our ndings suggest that old cooling towers are at greater risk for colonization. Thus, control measures should be applied more rigorously as towers age. The risk assessment and management plan should be re- viewed regularly, and special measures should be taken as necessary, such as frequent application of control measures and monitoring of old devices. The lower colonization in cooling towers that were periodically monitored for the presence of heterotro- phic colony counts or Legionella spp may be attributed to the fact that possible changes to the microbiological quality of the water were identied and corrective actions were taken when necessary. Contrarily, cooling towers with no verication plan in place could not track trends and changes in the water microbial load, which is necessary to implementation of corrective ac- tions and validation of implemented prevention and control measures. Microbiological monitoring is part of the verication and surveillance system of a water safety plan, which can be applied to assess and manage the risks associated with legionellae in cooling towers. 1 In a small proportion of the legionellae-positive cool- ing towers (9%), the disinfection procedure was not ef- fective in reducing the bacteria to acceptable levels. In those cases, the chlorine disinfection procedure proba- bly was not done properly. Measurement of pH and free chlorine concentration and proper timing are es- sential to ensure an efcient disinfection procedure. The cooling tower system also should be reassessed Table 4. Median (IQR) of cooling tower characteristics in association with Legionella spp contamination Characteristics Legionella-positive cooling tower Legionella-negative cooling tower P Water temperature, o C 26.8 (23.4-29.1) 25.1 (20.2-29.2) .30 Cooling tower age, years 17 (5.0-26.0) 6 (1.0-13.5) .01 Water loss, L 100 (0.0-6,000) 29 (0.25-80) .40 Total plate count 4,200 (450-22,600) 422 (14-9,600) .001 pH 8.1 (7.9-8.4) 8.0 (7.6-8.5) .40 Table 5. Association of Legionella spp colonization of cooling tower water samples with pH values, total plate counts, and free chlorine concentrations Legionella contamination of samples and water characteristics, cfu L 21 , 500 500 to 999 10 3 to 9999 10 4 to 10 5 . 10 5 P pH Number of samples 59 4 23 16 8 Median (IQR) 8 (7.6-8.5) 7.8 (7.5-7.9) 8.1 (8.0-8.5) 8.1 (7.9-8.4) 8.2 (7.7-8.3) .40 Total plate count, cfu mL 21 Number of samples 61 7 26 19 9 Median (IQR) 422 (14-9600) 170 (10-40,900) 7,006 (1700-20,000) 2,279 (679-11,580) 30,160 (402-137,840) .005 Free chlorine, mg L 21 Number of samples 49 3 22 16 7 Median (IQR) 0.22 (0.10-0.57) 2.52 (0.33-3.85) 0.12 (0.02-0.15) 0.09 (0.01-0.16) 0.16 (0.06-0.72) .002 54 Mouchtouri et al. American Journal of Infection Control February 2010 for hazards, such as areas of standing water, with correc- tive actions taken as necessary. Continuous water treat- ment with chlorine will limit the risk of recolonization. Cooling towers can be heavily colonized by Legion- ella spp and thus present a potential infection risk. Our study demonstrates the importance of a risk assessment and management plan aimed at reducing legionellae populations in cooling towers. Water chlori- nation effectively reduces legionellae contamination. Training of cooling tower operators is paramount. Older cooling towers are at greater risk for legionellae proliferation and thus require frequent, rigorous preventive and control measures. References 1. World Health Organization. Legionella and the prevention of legionel- losis. Geneva: World Health Organization; 2007. 2. Shelton BG, Flanders WD, Morris GK. Legionnaires disease out- breaks and cooling towers with amplied Legionella concentrations. Curr Microbiol 1994;28:359-63. 3. Bentham RH. Routine sampling and the control of Legionella spp in cooling tower water systems. Curr Microbiol 2000;41:271-5. 4. Ishimatsu S, Miyamoto H, Hori H, Tanaka I, Yoshida S. Sampling and de- tection of Legionella pneumophila aerosols generated from an industrial cooling tower. Ann Occup Hyg 2001;45:421-7. 5. Lu HF, Tsou MF, Huang SY, Tsai WC, Chung JG, Cheng KS. Factors af- fecting the recovery of Legionella pneumophila serogroup 1 fromcooling tower water systems. J Microbiol Immunol Infect 2001;34:161-6. 6. Engelhart S, Pleischl S, Luck C, Marklein G, Fischnaller E, Martin S, et al. Hospital-acquired legionellosis originating from a cooling tower during a period of thermal inversion. Int J Hyg Environ Health 2008; 211:235-40. 7. Gilmour MW, Bernard K, Tracz DM, Olson AB, Corbett CR, Burdz T, et al. Molecular typing of a Legionella pneumophila outbreak in Ontario, Canada. J Med Microbiol 2007;56:336-41. 8. Kirrage D, Reynolds G, Smith GE, Olowokure B. Investigation of an outbreak of Legionnaires disease: Hereford, UK 2003. Respir Med 2007;101:1639-44. 9. Garcia-Fulgueiras A, Navarro C, Fenoll D, Garcia J, Gonzalez-Diego P, Jimenez-Bunuales T, et al. Legionnaires disease outbreak in Murcia, Spain. Emerg Infect Dis 2003;9:915-21. 10. Greig JE, Carnie JA, Tallis GF, Ryan NJ, Tan AG, Gordon IR, et al. An outbreak of Legionnaires disease at the Melbourne Aquarium, April 2000: investigation and case-control studies. Med J Aust 2004;180: 566-72. 11. Rota MC, Pontrelli G, Scaturro M, Bella A, Bellomo AR, Trinito MO, et al. Legionnaires disease outbreak in Rome, Italy. Epidemiol Infect 2005;133:853-9. 12. Phares CR, Russell E, Thigpen MC, Service W, Crist MB, Salyers M, et al. Legionnaires disease among residents of a long-term care facility: the sentinel event in a community outbreak. Am J Infect Control 2007; 35:319-23. 13. Nguyen TM, Ilef D, Jarraud S, Rouil L, Campese C, Che D, et al. A community-wide outbreak of Legionnaires disease linked to industrial cooling towers: how far can contaminated aerosols spread? J Infect Dis 2006;193:102-11. 14. Isakbaeva E, Blystad H. New legislation in Norway targets prevention of Legionnaires disease. Eur Surveill 2005;10:E050714. 15. EuropeanWorking Group for Legionella Infections. European guidelines for control and prevention of travel-associated Legionnaires disease. London: European Working Group for Legionella Infections; 2005. 16. Yu VL. Cooling towers and legionellosis: a conundrum with proposed solutions. Int J Hyg Environ Health 2008;211:229-34. 17. Hadjichristodoulou C, Goutziana G, Mouchtouri V, Kapoula C, Kon- stantinidis A, Velonakis E, et al. Evaluation of standardized scored in- spections for Legionnaires disease prevention, during the Athens 2004 Olympics. Epidemiol Infect 2006;134:1074-81. 18. Yamamoto H, Sugiura M, Kusunoki S, Ezaki T, Ikedo M, Yabuuchi E. Factors stimulating propagation of legionellae in cooling tower water. Appl Environ Microbiol 1992;58:1394-7. 19. Ragull S, Garcia-Nunez M, Pedro-Botet ML, Sopena N, Esteve M, Mon- tenegro R, et al. Legionella pneumophila in cooling towers: uctuations in counts, determination of genetic variability by pulsed-eld gel elec- trophoresis (PFGE), and persistence of PFGE patterns. Appl Environ Microbiol 2007;73:5382-4. 20. Bhopal RS, Barr G. Maintenance of cooling towers following two out- breaks of Legionnaires disease in a city. Epidemiol Infect 1990;104: 29-38. 21. Negron-Alvira A, Perez-Suarez I, Hazen TC. Legionella spp in Puerto Rico cooling towers. Appl Environ Microbiol 1988;54:2331-4. 22. Wery N, Bru-Adan V, Minervini C, Delgenes JP, Garrelly L, Godon JJ. Dynamics of Legionella spp and bacterial populations during the prolifer- ation of L pneumophila in a cooling tower facility. Appl Environ Microbiol 2008;74:3030-7. 23. Turetgen I, Sungur EI, Cotuk A. Enumeration of Legionella pneumophila in cooling tower water systems. Environ Monit Assess 2005;100:53-8. 24. Yamamoto H, Ezaki T, Ikedo M, Yabuuchi E. Effects of biocidal treat- ments to inhibit the growth of legionellae and other microorganisms in cooling towers. Microbiol Immunol 1991;35:795-802. www.ajicjournal.org Vol. 38 No. 1 Mouchtouri et al. 55