Professional Documents
Culture Documents
No
1
Description
Capacity of the system
STG
Water Cooled condenser
Cooling tower
MCW pump
Continuous Intermittent
1815 Cum/hr
ACW pump
1815 Cum/hr
Remarks
100 Cum/hr
100 Cum/hr
Generator cooler
100 Cum/hr
100 Cum/hr
5 Cum/hr
8 Cum/hr
2 Cum/hr
5 Cum/hr
8 Cum/hr
2 Cum/hr
0 Cum/hr
0 Cum/hr
Compressor
10 Cum/hr
10 Cum/hr
10 Cum/hr
10 Cum/hr
5
6
75 Cum/hr
75 Cum/hr
106 Cum/hr
1
2
3
4
5
6
7
8
9
Boiler
Boiler feed water pump
SWAS
Coal spreader
Ash Handling System
Eco & APH ash hoppers
Total
No. of working
Total capacity per unit
Margin available
Selected capacity
2125 Cum/hr
2 Nos.
1063 Cum/hr
4%
1100 Cum/hr
43 Deg C
35 Deg C
8 Deg C
5
1.45 %
0.05 %
0.31 %
1.8 %
38.52 Cum/hr
1815 Cum/hr
1 No.
1815 Cum/hr
5%
1900 Cum/hr
416 Cum/hr
1 No.
416 Cum/hr
3%
430 Cum/hr As per contract,
CT - 1100 cum/hr per cell
MCWP - 1800 Cum/hr
ACWP - 250 Cum/hr