You are on page 1of 26

01/2010

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

1.

INTRODUCTION

2.

AIR FLOW LEAKAGE

3.

PERFORATED TILES: NUMBER AND OPENING FACTOR

4.

PERFORATED TILES: WITH ADJUSTABLE DAMPER

5.

PERFORATED TILES: PLACEMENT

6.

CLOSE UNUSED UNITS IN THE RACKS WITH BLANKING PANELS TO


AVOID AIRFLOW SHORT CIRCUIT INSIDE THE RACK

7.

AIRFLOW PHILOSOPHIES

8.

RAISED FLOOR HEIGHT

9.

RETURN AIR CONDITIONS

10. CHILLED WATER SYSTEM WATER CONDITIONS


11. STANDBY UNIT OPERATION
12. USE CRAC UNITS WITH STATE-OF-THE-ART COMPRESSOR AND FAN
TECHNOLOGY

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

1. Introduction
This presentation summarises todays Best Practise for data-centre cooling
systems.
It will give you a rough overview about all concerned parts of the data-centre.
This list is not exhaustive, but it will impart the most important matters how to
design, build and run an as energy efficient as possible data-centre.

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

2. Airflow Leakage
Airflow leakages (short air circuit) leads to dramatic inefficiencies
due to air circulation back to the CRAC unit without taking heat from
the computer equipment.

Close all unwanted openings in the raised floor


Close all unwanted openings below the racks
Close all cable cut outs use cable sealings
All gaps (near walls and CRAC units) have to be sealed

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

2. Airflow Leakage
The target is to create an overpressure under the raised floor to
realize an even air supply to all areas of the data-centre.

This overpressure can only be achieved with an as low as possible


amount of unwanted airflow leakage.

A maximum loss of 2 6% of the total


airflow of the data-centre is acceptable.

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

3. Perforated Tiles: Number and Opening Factor


The number of perforated tiles must be in line with:
A) the design
b) the actual / real airflow

Example (Data-centre):
Design airflow: 50.000 m/h, ESP 20Pa
Chosen tile: airflow: 500m/h, 20Pa
Tile number

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

100 tiles are required

Actual aiflow: 30.000 m/h,

Tile number to be reduced to 60

Only a raised floor with sufficient


height and perforated tiles
with limited openings allow an
even air distribution !!!
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

4. Perforated Tiles: With Adjustable Damper

Perforated tiles with integral adjustable


dampers can be used to avoid having to
replace perforated tiles with solid tiles.

In this case the number of perforated


tiles can remain unchanged but all tiles
need to be adjusted according to the
actual requirements in the room.
It is also possible to work with different adjustments to vary the amount of
air in different areas of the data-centre.

In any case the static pressure under the raised floor has to be kept at the
design level.

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

5. Perforated Tiles: Placement

Perforated tiles should only be


placed at positions, where cold
air is really required to cool
equipment.

Do not place perforated tiles directly near the CRAC unit; a distance of minimum
2m has to be kept. Perforated tiles near CRAC units can induce warm room air into
the raised floor (negative airflow).

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

6. Close Unused Units in the Racks with Blanking Panels

Recirculation of cooling air


inside the rack leads to
overheating of servers.

Blanking panels installed


in unused areas or slots of
a rack eliminate a possible
internal recirculation of the
hot air.

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

01/2010

7. Airflow philosophies
A) The old/traditional way:

Uncontrolled placement of

perforated supply air tiles


anywhere in the room
Cold air is supplied in an
uncontrolled way to the low
density equipment
Uncontrolled recirculation
Supply and return air mixing
takes place
NOT RECOMMMENDED
ANYMORE
Very inefficient

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

10

01/2010

7. Airflow philosophies
B) Hot Aisle, Cold Aisle Concept:

Hot/Cold Aisle
Concept

Cold supply air distribution only in the cold aisles


Warm return air only in the hot aisles
Open tiles only in the cold aisle
Risk of mixing cold and hot air is high
This risk can be reduced by using suspended
ceilings
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

11

01/2010

7. Airflow philosophies
C) Hot Aisle Containment:

Hot Aisle
Containment

Hot Aisle between the racks will be covered on the top and the end of

rack rows
Cold supply will be delivered into the room
Open tiles only in the room
Full separation between supply and return air
The room itself will be at low temperature level

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

12

01/2010

7. Airflow philosophies
D) Cold Aisle Containment:

Cold Aisle
Containment

Cold supply air distribution only in the cold aisles


The cold aisle is separated from the hot aisle
Warm return air only in the hot aisles
Open tiles only in the cold aisle
No risk of mixing cold and hot air
The room itself will be at high temperatures
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

13

01/2010

7. Airflow philosophies
Debate: Hot aisle or cold aisle containment ???

Keeps the hot air in a confined area.

Keeps the cold air in a confined area, no need


to cool the entire space.

The room outside is cold.

Floor space around the cold aisle is warm.

Servers are stable and can be operated


for an extended period in case of loss
of airflow.

Disadvantages:

Overall stability can be increased.

Air balancing can be difficult if CRACs are


sequencing and the raised floor pressure is
changing.

Disadavantage:

In case of power outage the cold aisle is


exposed to high threat due to loss of airflow .

Hot Spots in the cold aisle disappear.

CRACs have to be calculated carefully


to deal with the high return air
temperatures.
STULZ THE NATURAL CHOICE

Control of supply air temperature with DX-units


only possible to a certain extend.

Best Practice - Data Centre Cooling

14

01/2010

7. Airflow philosophies
E) Room Supply, Direct Rack-Out Return Concept:

Room supply,
Ducted return air

Cold supply air enters the rack through the room


Open tiles only in the cold aisle
Warm return air leaves the rack through a duct and suspended ceiling
Full seperation of hot and cold air
The room itself will be at low temperature level
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

15

01/2010

7. Airflow philosophies
F) Close Coupling of CRAC units and Racks on Supply and Return Side:

Ducted Supply and


Return Air Concept

Cold supply air into ducts fitted to the supply air side of the racks
Warm return air through ducts fitted to the exhaust side of the racks
Open tiles only in the area of supply air ducts
No risk of mixing cold and hot air

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

16

01/2010

7. Airflow philosophies
Summary:

Target of all these various possibilities is the complete separation of warm

return air and cold supply air


This separation leads to an increased temperature difference between
return and supply air temperature of the CRAC unit
A high temperature difference increases the efficiency of the CRAC unit
and therefore the efficiency of the data-centre in general
What kind of separation can be used in a data-centre is depending on the
situation and used equipment
The highest level of efficiency is reached if each m of circulating air takes
the design amount of heat from the IT-euipment

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

17

01/2010

8. Raised floor height

The raised floor height has got a


major influence on the efficiency
of the whole data-centre !
Tile number

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

The required free height is


depending on room size, heat
density and number and position
of instaled CRAC units.
A certain obstacle free area is
required for a proper supply of
cold air to any area of the room !

Rule of thumb:
The higher, the better !
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

18

01/2010

9. Return Air Conditions


The leading and most important temperature
is the air entering the IT equipment (server).
According to the new ASHRAE environmental
envelope supply air temperatures up to 27C
are possible. That would lead to return air
temperatures of approx. 37C.

35C

8K

27C

STULZ THE NATURAL CHOICE

Please note: A low return air set-point does not


cure problems with heat load. It is the other
way around: The lower the return air set-point
the lower the usable cooling capacity of the
unit. Furthermore the operating costs are
increasing.

High return air temperatures and lower return


air humidity do not change the content of
water in the room. The risk of ESD is as low.
Best Practice - Data Centre Cooling

19

01/2010

9. Return Air Conditions


Advantages of high return air temperatures:
(1) CW-units: High return air temperatures are leading towards higher
water temperatures (with same sensible cooling capacity). The
starting temperature of the free-cooling is much higher.
(2) CW-units: To get the same cooling capacity with high return air
temperatures and high water temperatures the airflow of the unit can
be reduced. Lower airflow leads to lower fan power consumption and
a lower noise level.
(3) DX-units: Higher return air temperatures are leading towards higher
evaporating pressure. With constant condensing pressure the delta
between evaporating and condensation pressure is reduced. The
compressor power consumption is decreasing. Furthermore the fan
speed also can be reduced.
But please be aware that too high evaporating pressure can damage
the compressor.
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

20

01/2010

10. Chilled Water System Water Conditions


Heat loads in data-centres are nearly all
sensible cooling load with only a small latent
cooling load due to fresh air ventilation.
In accordance to the increased return air
temperatures the chilled water temperatures
can be increased as well.

Chiller efficiency will be increased due to increased evaporating temperature.


The higher the chilled water temperature the earlier the starting temperature
of the chiller free-cooling.

The balance between cooling capacity of the CRAC unit and chiller efficiency
has to be evaluated.

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

21

01/2010

11. Standby Unit Operation


Fan laws dictate that air volume is directly proportional to fan speed and that fan
power is a cube of the fan speed.

100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%

100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
Airflow

Absorbed Power

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

1/2
Airflow

Airflow

1/8
Absorbed
Power

Absorbed Power

22

01/2010

11. Standby Unit Operation


Therefore, by running the stand-by CRACunit at reduced air volume the overall
fan power is greatly reduced.
Example:

4x ASD1900CW at 26C/40%
Water 10/15C

Airflow: 3x 39.000 m/h


Fan power = 3x 12,6 kW = 37,8 kW
Lpa,2m = 3x 71,6 dB(A) = 76,4 db(A)

Standby

3x 146,8 kW = 440,4 kW net sensible

Airflow: 4x 29.000 m/h


Fan power = 4x 5,3 kW = 21,2 kW
Lpa,2m = 4x 62,7 dB(A) = 68,7 db(A)
4x 114,6 kW = 458,6 kW net sensible

=> Energy savings:


16,6 kW x 8760h x 0,13 = 18.904 /year @ 0,13 /kWh
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

23

01/2010

11. Standby Unit Operation


Advantages of Standby-Management:

Reduction of fan power consumption


Reduction of noise level
Increase of net sensible cooling capacity
And: even more energy can be saved if net sensible cooling
capacity is kept constant:
Airflow: 4x 27.800 m/h
Fan power = 4x 4,7 kW = 18,8 kW
Lpa,2m = 4x 61,5 dB(A) = 67,5 db(A)
4x 110,3 kW = 441,2 kW net sensible

=> Energy savings:


19,0 kW x 8760h x 0,13 = 21.637 /year @ 0,13 /kWh
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

24

01/2010

12. Use CRAC Units with state-of-the-art Technology


EC fan technology:

Advantages:
1.

Lower power consumption due to better overall degree of efficiency

2.

No in-rush current, speed is ramped up, never draws more than full load amps

3.

Low vibration reduced sound level

4.

Long maintanance free operation due to direct drive technology

5.

Scalable air flow easy adaptation on requirements on site

STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

25

01/2010

Example:
Munich airport data centre, source:

600 m data centre, 75 server cabinets arranged in 3 rows


5 CRAC units (4+1), each 32 kW cooling capacity
Changes (Best practise only):

installation of hot aisle/cold aisle containment


re-routing cables inside the racks
reconfiguring of floor tile layout, sealing of raised floor
installation of 1U blanking panels at the front of the racks
installation of ventilated front doors
increasing of room temperature to 28C (supply air = 22C)
=> Due to these changes the power consumption of the CRAC units are reduced by 35%.
=> Cabinet temperatures are reduced by 4C extended lifetime of servers and more reliability.
STULZ THE NATURAL CHOICE

Best Practice - Data Centre Cooling

26

You might also like