Professional Documents
Culture Documents
SCR/Generator Control
Rig/Plant
Mobile Modular Workover Unit
st
1 MMWU
Customer
Project Manager
N/A
J301270002
Document Number
D257272-1200-FDD-002
www.nov.com
01
Table of Contents
This manual may consist of several volumes, chapters and sections and is housed in a number of
different binders as necessary to adequately document the equipment presented. Each binder or
volume is provided with a Table of Contents.
- Section
Title Page ......................................................... Front Matter
Table of Contents............................................................... ii
www.nov.com
Chapter 1.0
SCR/Generator Control
Package
www.nov.com
Table of Contents
SCR / Generator Control Unit
REFERENCE
7272 C00,01,02,04
REFERENCE DESCRIPTION
www.nov.com
DOCUMENT NUMBER
REV
D257272-1200-TOC-001
01
Section 1.1
www.nov.com
Technical Manual
50 Hz SCR Drive System
RIG/PLANT
ADDITIONAL CODE
SDRL CODE
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
TOTAL PGS
44
DISCIPLINE
REFERENCE
20605-44
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Dr
Houston, TX 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-001
01
Section 1.2
Generator Unit
www.nov.com
Technical Manual
Generator Unit
RIG/PLANT
ADDITIONAL CODE
SDRL CODE
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
TOTAL PGS
57
DISCIPLINE
REFERENCE
20605-46
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Drive
Houston, Texas 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-002
01
Document number
Revision 01
Page 2
D257272-1200-MAN-002
REVISION HISTORY
01
17.12.2008
Rev Date
(dd.mm.yyyy)
CHANGE DESCRIPTION
Revision Change
Description
www.nov.com
01
BKF
NEG
KM
Prepared
Checked
Approved
Document number
Revision 01
Page 3
D257272-1200-MAN-002
TABLE OF CONTENTS
1
1.2
Specifications ......................................................................................................... 6
MAINTENANCE................................................................................................................ 8
2.1
Testing.................................................................................................................... 8
2.2
Servicing................................................................................................................. 8
2.3
Theory of Operation.............................................................................................. 23
2.4
2.5
2.6
TROUBLESHOOTING.......................................................................................... 46
Model 1000........................................................................................................... 54
4.2
Model 1400........................................................................................................... 55
4.3
Model 1861........................................................................................................... 56
www.nov.com
Document number
Revision 01
Page 4
1 GENERAT
OR UNIT
1.1 Operation
Description
D257272-1200-MAN-002
The Generator Unit controls the engine/ generator set to develop a constant AC supply.
The output of several generators are fed to a common AC bus (refer to Figure 2-1).
Each Generator Unit's AC Control Module has an electronic engine governor; a voltage
regulator and a circuit breaker (refer to Figure 2-2). The circuit breaker is interlocked with a
Protection circuit which automatically trips the breaker for malfunctions such as overcurrent, over-voltage, under/over-frequency and reverses power. In addition, a
Synchronization Panel is provided with each system to match individual generator
frequency and voltage to the bus frequency and voltage.
Document number
Revision 01
Page 5
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 6
D257272-1200-MAN-002
1.2 Specifications
1.2.1 Electrical
Table 2-1 lists the electrical specifications of the AC Control Module.
1.2.2 Mechanical
They are mounted in a sheet steel cubicle. Dimensions vary from model to model. A typical
Generator Cubicle is 90" H. x 36" D. x 24" W. and weighs 2,000 pounds.
www.nov.com
Document number
Revision 01
Page 7
D257272-1200-MAN-002
ELECTRICAL POWER
AC Supply
Overvoltage
Overfrequency
55 - 56 Hz.
Underfrequency 42
Reverse Power
Hz.
ENGINE GOVERNOR
Regulation
Second.
5% rated load.
maximum.
Second.
Load Unbalance
Exciter Power
Document number
Revision 01
Page 8
D257272-1200-MAN-002
2 MAINTENANCE
This section contains testing and servicing information to assure proper operation of the
Generator Unit. TROUBLESHOOTING (later in this chapter) has an explanation of the
various Generator Unit circuits. REMOVAL AND REPAIR (also later in this chapter)
identifies the various generator assemblies.
2.1 Testing
Perform the functional tests given in Tables 2-2 through 2-6 after repairing/replacing any
assembly. Perform the Reverse Power Trip and Engine Mechanical Over-speed tests listed
in Table 2-4 once a month.
SERIOUS DAMAGE TO THE ENGINE CAN RESULT IF REVERSE POWER AND
ENGINE OVERSPEED FUNCTIONS DO NOT FUNCTION PROPERLY.
These are the tables and their titles:
2-2 Engine/Generator Unit Functional Test
2-3 AC Module Functional Tests
2-4 Protection Circuit Functional Test
2-5 Calibration Procedure for Woodward EG-3P and EG-10P Actuators
2-6 Calibration Procedure for Woodward EG-B 10P Actuators Used on EMD Engines
The TEST switch allows a quick check of the systems vital signals. The TEST switch and
the TEST METER are color coded. For example, if the TEST switch is set to the yellow
BREAKER TRIP VOLTAGE position, normal condition is indicated by the TEST METER
needle deflecting to the yellow.
2.2 Servicing
Servicing consists of oil change and calibration procedure of the throttle actuator terminal
shaft.
2.2.1 Oil Change
The Woodward EG-3P and EG-10P Actuators receive oil from the engine oil supply, so
regular engine oil change intervals are sufficient.
The Woodward EG-B 10P Actuator has its own oil supply. Change it every six months
under favorable operating conditions. The oil sump holds one U.S. Quart. Refer to the
following and the manufacturer's literature.
www.nov.com
Document number
Revision 01
Page 9
D257272-1200-MAN-002
The main difference between these models: the EG-B has a Ball Speed governor and
self-contained oil supply.
Changing the Oil in the EG-B 10P
1. To drain the oil, unscrew the Drain Cock located in the lower left-hand corner of the front
panel.
2. To flush the actuator, add one quart of diesel fuel or kerosene through the Oil Cup
located on the top. Run the engine speed up and down by switching the Engine Control
switch between IDLE and RUN. After a few minutes, shut the engine off and drain the fluid.
Repeat flushing until the Drain Cock fluid is clean.
3. Drain all the fluid and screw in the Drain Cock. Fill the actuator with one quart of the
recommended lubricating oil. Woodward recommends Mobil 1.
IF THE OIL IN THE EG-B 10P ACTUATOR IS NOT CHANGED REGULARLY, IT WILL
BECOME CLOGGED WITH GUM AND FAIL.
www.nov.com
Document number
Revision 01
Page 10
D257272-1200-MAN-002
ACTION
RESULTS
A.
A.
A.
B.
C.
B.
A.
B.
www.nov.com
Document number
Revision 01
Page 11
ACTION
RESULTS
D257272-1200-MAN-002
A.
B.
Document number
Revision 01
Page 12
D257272-1200-MAN-002
ACTION
RESULTS
CONTROL CIRCUIT TEST (CONCLUDED)
D. Close fuses F30, F3 1, F32, F35, F36,
D. There are no measurable result s from thi s
and F37 on the input of the AC Regulator
step.
Transformer.
On most models, these fuses will
be F30 F31, F32, F33, F34, and
F35.
E. Check the phase rotation at the AC
Control Module pins 512 through 517.
Document number
Revision 01
Page 13
ACTION
ENGINE GOVERNOR TEST
A. Determine the model of your Throttle Actuator. If
it is a Wo odward Mo del EG-B 10P, perform
Steps B through D. If it is a Wood ward Model
EG-3P or EG-10P, skip to Step E.
D257272-1200-MAN-002
RESULTS
A. There are no measurable results from this step.
www.nov.com
Document number
Revision 01
Page 14
D257272-1200-MAN-002
RESULTS
A. There are no measurab le resu lts from this
step.
GENERATOR CIRCUIT BREAKERS
WILL NOT CLOSE UNTIL
SYNCHRONIZED WITH THE MAIN AC
BUS. DO NOT CLOSE ANOTHER
GENERATORS CIRCUIT BREAKER
UNTIL THE SYNCHROSCOPE AND
SYNC LIGHTS HAVE BEEN CHECKED
FOR PROPER OPERATION.
www.nov.com
Document number
Revision 01
Page 15
D257272-1200-MAN-002
RESULTS
60% KW
www.nov.com
Document number
Revision 01
Page 16
D257272-1200-MAN-002
RESULTS
B. Put the ENGINE CONTROL switch to RUN B. The generator voltage and frequency should
increase as the engine goes from IDLE to
and adjust the
SPEED ADJUST
RUN speed.
potentiometer to 50 Hz.
C. Put the ENGINE CONTROL switch to IDLE.
D. Put the ENGINE CONTROL switch to RUN.
Load Testing Engine/Generator Test
A. After performing the Engine/Generator IdleRun test, connect the engine/generator to
the Main AC Bus.
B. Connect a load (such as a tank of salt
water) to the Main AC Bus.
www.nov.com
Document number
Revision 01
Page 17
D257272-1200-MAN-002
RESULTS
PRELIMINARY
A. Inspect the AC
Control Module wiring
A. Fix any incorrect or loose connections.
harness for incorrect and/or loos
e
connections.
B. Turn on the Generator unit.
POWER SUPPLY CHECK
A. Measure the voltage at the following points:
Terminal Pin 502
Terminal Pin 503
Terminal Pin 507
Terminal Pin 508
Terminal Pin 546
Auxiliary Board Pin 24
www.nov.com
Document number
Revision 01
Page 18
D257272-1200-MAN-002
MODULATOR TE
RESULTS
ST
LOCATION
Document number
Revision 01
Page 19
D257272-1200-MAN-002
RESULTS
A. Rotate the SPEED ADJUST control knob t o A. There are no measurab le resu lts from this
its center position.
step.
B. Monitor the SPEED REFERENCE signal at
AC Control Module Pin 547.
C. Monitor the engine/generator's speed.
www.nov.com
Document number
Revision 01
Page 20
D257272-1200-MAN-002
RESULTS
This test applies only to systems
equipped with a Tachometer Pulse
Pickup circuit.
NO PULSE TRIP
www.nov.com
Document number
Revision 01
Page 21
D257272-1200-MAN-002
Table 2-5. Calibration Procedure for Woodward EG-3P and EG-10P Actuators
ACTION
RESULTS
SETUP
A. Connect an Ammeter in series with one of A. There are no measurab le resu lts from this
the throttle leads which are connected to the
step.
Actuator receptacle.
B. Set the Ammeter scale to 100 mA.
B. There are no measurable results from this
step.
C. Open the Generator Circuit Breaker.
C. There are no measurable results from this
step.
D. There are no measurable results from this
D. Start the engine, and bring it up to RUN.
step.
TERMINAL SHAFT ADJUSTMENT
A. Disconnect the coupling from the actuator
shaft (refer to Figure 2-9). Adjust the actuator
so that it draws 30 to 60 mA. Monitor the
Ammeter of all actuators, in RUN, Off-line, with
engine warmed up.
For each 2.5 mA of change desired,
rotate the coupling on the threaded
rod connected to the actuator shaft
to 1 turn.
Actuators and linkages must also be
set to conform with the engine
manufacturer's specifications. A
compromise between the engine
manufacturer's specifications and the
30 to 60 mA figure may be necessary.
A. On
actuators produced beginning in
1980 Ammeter readings on all units should be
within 10 mA of each other. On older units, the
Ammeter readings may have to be the same for
good load sharing. If you have questions, call
the Ross Hill Field Service Office.
ACTUATOR SHAFT
LOCK
NUT
THREADED
ROD
www.nov.com
ACTUATOR
Document number
Revision 01
Page 22
D257272-1200-MAN-002
Table 2-6. Calibration Procedure for Woodward EG-B 10P Actuators Used on EMD
Engines
ACTION
RESULTS
ACTUATOR CURRENT CHECK
A.
B.
C.
A. Loosen the Spring Se at lock nut. Rotate th e A. Note that the actuator current changes.
Spring Seat 1/4 turn or less in either direction.
B. Adjust the Spring Seat until the A mmeter rea ds
the same as other recorder actuator currents.
B. All actuators should dra w 30 to 60 mA when th e
engines ar e at RUN RPM, Off -line, and at
normal operating temperature.
C. Tighten the Spring Seat lock nut.
REASSEMBLY
www.nov.com
Document number
Revision 01
Page 23
2.3 Theor
D257272-1200-MAN-002
y of Operation
The Generator Unit controls the engine/generator set to deliver a constant AC supply to the
Main AC Bus (refer to Figures 2-10 and Figure 2-11). Note that the AC Control Module
contains the electronic Engine Governor, Voltage Regulator, Protection and Master/Slave
circuits.
2.3.1 Hands-Off Circuit (HOC)
The HOC consists of a battery charging circuit connected to two 12 Volt batteries. Phases
A and B of the Main AC Bus are tapped, fused, and then rectified in a diode bridge to
obtain the battery charging current. The batteries supply power for the Engine Starting
circuit and the Pulse Pickup circuit in the AC Control Module (refer to Figures 2-11 and 212).
2.3.2 Generator Circuit Breaker
The Generator Circuit Breaker isolates the Main AC Bus from the generator. It has a
magnetic trip unit which trips the circuit breaker if current exceeds a preset value. The
circuit breaker has a UV (Under Voltage) coil which is interlocked with an AC Control
Module Protection circuit. This circuit trips the circuit breaker for various abnormal
conditions such as reverse power, under/over-frequency and over-voltage.
2.3.3 Sy nchronization Panel
When the Main AC Bus is energized and another generator supply is to be connected to
the Main AC Bus, it is essential to match their voltage and frequencies before closing the
Generator Circuit Breaker. This is accomplished by comparing the two frequencies by
means of the Synchronization Box (shown in Figure 2-11).
When the front panel SYNC switch is in the OFF position, the Sync panel VOLT meter
indicates the Main AC Bus voltage. The needle of the SYNCHROSCOPE and the SYNC
LIGHTS compare the frequencies of the Main AC Bus and the on-coming generator. The
needle of the SYNCHROSCOPE rotates and the SYNC LIGHTS illuminate brightly when
the two frequencies are out of phase. When the frequencies and phases are identical,
there is no potential across the scope and the lights. As a result, the SYNCHROSCOPE
needle remains stationary in the vertical position and both SYNC LIGHTS extinguish.
www.nov.com
Document number
Revision 01
Page 24
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 25
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 26
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 27
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 28
D257272-1200-MAN-002
Document number
Revision 01
Page 29
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 30
D257272-1200-MAN-002
Document number
Revision 01
Page 31
D257272-1200-MAN-002
GEN. BUS
DEMODULATOR
SPEED FEEDBACK
REAL FEEDBACK
THROTTLE LIMIT
GEN.
PULSE
PICKUP
ENGINE
Z8
Z9
Q4
THROTTLE
SPEED REFERENCE
ENGINE CONTROL
SWITCH
RAMP CKT.
MS LOGIC
SLAVE
SLAVE
MASTER/SLAVE
LOGIC
AC MODULE
M/S
SWITCH
MASTER
SLAVE
CURRENT CONTROL LOOP
MASTER SLAVE
TO OTHER
GEN. UNITS
Document number
Revision 01
Page 32
D257272-1200-MAN-002
Document number
Revision 01
Page 33
D257272-1200-MAN-002
Document number
Revision 01
Page 34
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 35
D257272-1200-MAN-002
Document number
Revision 01
Page 36
D257272-1200-MAN-002
The engine governor employs two feedback control loops. The Outer Speed Control Loop
matches the actual generator frequency to the applied speed command. The Inner Current
Control Loop matches the horsepower (KW) output of all engines on line.
Speed Control Loop
Op Amp Z8 issues a speed command which is proportional to the difference between the
Speed Command and the Composite Speed Feedback. Speed Command is the Speed
Reference signal as modified by the Engine Control switch ramp circuit and the
Master/Slave Logic signal. Composite Speed Feedback is the sum of the Speed Feedback
and Throttle Limit signals.
Speed Reference
This signal is set by the operator on the front panel SPEED ADJUST knob. The SPEED
ADJUST knob is linked to a potentiometer which outputs a Zero to +11 VDC signal (pin
551). This corresponds to 46 to 54 Hz generator frequency.
Engine Control Switch
When the ENGINE CONTROL switch is moved from IDLE to RUN, the ramp circuit
generates an ascending ramp. This steadily increases the gain of Op Amp Z8. The ramp
circuit generates a descending ramp when the switch is moved from RUN to IDLE.
Changeovers in engine speed are thus accomplished smoothly over a 10 Second time
span.
Master/Slave Logic
A signal from the Master/Slave Logic circuit disables the Speed Reference signal when the
Generator Unit is in the Slave mode.
Speed Feedback
This signal is a low-level DC analog of the engine speed. At TP 19 in the AC Control
Module, the Speed Feedback signal is -2.5 VDC at 50 Hz and +5.0 VDC at 35 to 40 Hz
(the IDLE frequency). The Speed Feedback signal is derived either through a Tachometer
Pulse Pickup circuit or a Voltage Demodulator circuit.
www.nov.com
Document number
Revision 01
Page 37
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 38
D257272-1200-MAN-002
Figure 2-15 shows the Master/Slave circuit. The Master/Slave Logic switches from 10
VDC (this voltage is approximate since it is partially dropped through a resistor) to -16 VDC
when the circuit breaker is closed to connect the generator to the Main AC Bus. The
Master/Slave Logic of each generator is connected to the Slave inputs of the following
higher-numbered generators. As a result, the Master generator is always the one with the
lowest number. Generator 1 is never a Slave unit since it doesn't receive any Slave inputs.
If Generator 1 is off, the lowest-numbered generator connected to the Main AC Bus
becomes the master.
Note that Master/Slave lines of all generators are tied together.
Table 2-7. Master/Slave Truth Table
M/S Logic
Slave
Result
10 VDC
10 VDC
The ge nerator is
disconnected from
the Main AC Bus.
-16 VDC
10 VDC
The generator is
the Master.
-16 VDC
-16 VDC
The generator is
the Slave.
IREAL Feedback
IREAL is a low-level DC analog of the real current produced by the generator (IREAL x E =
KW). Generator phase voltages out of transformer T10 and line currents out of CT1, CT2,
and CT3 are processed in the AC Control Module through a current demodulator to
develop ITOTAL, I REAL and IREACTIVE signals (refer to Figure 2-10).
2.3.5 Voltage Regulator
This controls the generator's exciter current through the exciter power supply to regulate
the generator voltage (refer to Figures 2-11, 2-13, 2-16, and 2-17).
The Voltage Regulator output can be monitored across Generator EX+ (TB11-7) and
Generator EX- (TB11-8). It should be +10 VDC during IDLE and +70 VDC during RUN for
a nominal 100 VDC exciter.
The Voltage Regulator employs two Feedback Control Loops (Inner and Outer). The Outer
provides overall regulation by matching the generator voltage to the Voltage Reference.
The Inner regulates the Exciter Field Supply. Op Amp Z1 issues the Exciter Current
Command. It is proportional to the error difference between the Voltage Reference and
Voltage Feedback signals.
www.nov.com
Document number
Revision 01
Page 39
-16 VDC
-16 VDC
-16 VDC
CB AUX.
PIN
CB AUX.
O.
D257272-1200-MAN-002
PIN
CB AUX.
O.
PIN
O.
MS LOGIC
544
544
544
MASTER SLAVE
543
543
543
SLAVE
542
542
542
SLAVE
541
541
541
SLAVE
540
540
540
AC MODULE
GEN. 1
AC MODULE
GEN. 2
AC MODULE
GEN. 3
VOLT.
Z1
REFER.
Z2
SCR
FIRING
CIRCUIT
GEN.
BUS
AC
MTR
REACTIVE
EXCITER
EXCITER
FIELD
SUPPLY
UNDER FREQUENCY
CUTBACK
AC MODULE
GENERATOR
Document number
Revision 01
Page 40
D257272-1200-MAN-002
Document number
Revision 01
Page 41
D257272-1200-MAN-002
Control Module, build-up relay K1 energizes to switch the transformer output to the halfcontrolled bridge. The Exciter current feedback to the Op Amp Z2 summing junction (IEX +
and IEX -) is +0.33 VDC per 1.0 Amp of Exciter current (or as adjusted by the connection of
current-sensing resistors).
2.3.7 Protection Circuit
This circuit (refer to Figures 2-13 and 2-18) compares the generator supply parameters
against their respective preset limits.
It consists of a Protection switch controlled by the reverse power, under/over-frequency and
the over-voltage detector.
The Protection switch, made up of transistor Q3 and relay K2, de-energizes the Under
Voltage (UV) coil to trip the Generator Circuit Breaker. In some systems, the Generator
Circuit Breaker has a Shunt Trip coil and a UV coil. In these systems, the Shunt Trip coil is
wired to a switch on the Generator Cubicle. Closing this switch will energize the Shunt Trip
coil, thus causing the Generator circuit breaker to trip.
GEN. BUS
AC
CIRCUIT
BREAKER
NO PULSE
I REAL
FREQUENCY
FEEDBACK
REVERSE
POWER
DETECTOR
Z6, Q1, K1
UNDER/OVER
FREQUENCY
DETECTOR
Z7, Z14
PROTECTION
SWITCH
CB
Q3, K2
TRIP
AC BUS
UV
REVERSE
POWER LIGHT
UNDER FREQ.
CUTBACK
VOLTAGE
FEEDBACK
OVER VOLTAGE
DETECTOR
Q6
AC MODULE
www.nov.com
Document number
Revision 01
Page 42
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 43
D257272-1200-MAN-002
The Protection switch operates 100 mS after loss of magnetic pulses from the engine. This
will prevent nuisance tripping of the circuit breaker.
2.4
www.nov.com
Document number
Revision 01
Page 44
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 45
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 46
D257272-1200-MAN-002
The IREAL and ITOTAL signals are low-level DC analog signals representing the real and total
currents developed by the generator. Generator line currents are stepped down through
current transformers CT1, CT2 and CT3. The resulting low level AC signals are rectified
and processed in a current demodulator in the AC Control Module with the generator phase
voltages and rectified to derive IREAL and ITOTAL. The IREAL and ITOTAL signals of all
generators connected to the Main AC Bus are auctioneered to select the signals with the
highest positive values. The Power Limit signal (Op Amp Z1-6) goes positive as the load
increases. It is +0.25 to +0.5 VDC measured at Pin 12 of the Power Limit Board at power
limit. When the load exceeds the power limit, the Power Limit signal positively biases the
negative Firing Reference signals to all SCR bridges on line. Op Amp Z2 ramps input
signal to Z1 from 75% of Power Limit to allow the prime mover to handle a large change
demand for power. Transistor Q1 turns on at power limit to turn on the Driller's Console
POWER LIMIT light. In some systems, Op Amp Z4 output is used to drive the Driller's
Console POWER LIMIT meter.
2.5
2.6 TROUBLESHOOTING
Table 2-8 gives troubleshooting information for engine malfunctions. Table 2-9 gives
troubleshooting information for Generator malfunctions. Table 2-10 gives troubleshooting
information for the AC Control Module.
www.nov.com
Document number
Revision 01
Page 47
D257272-1200-MAN-002
ACTION
B. No power to the a ctuator. Throttle drops shut if B. The actions for the possible causes are:
the fuel rack is n ot held open by ha nd. Th e
possible causes are:
1. Leads to the throttle actuator are either open,
short-circuited, or grounded.
F. Generator Circuit Breaker does not a utomatically F. The actions for the possible causes are:
trip for reverse power, under/overfrequency, or no
pulse faults. There are two possible causes:
1. Defective AC Control Module.
www.nov.com
Document number
Revision 01
Page 48
D257272-1200-MAN-002
ACTION
www.nov.com
Document number
Revision 01
Page 49
D257272-1200-MAN-002
ACTION
DC POWER SUPPLY
A. The KVAR and KW meter nee dles A. Measure the voltage at t he follo wing AC Control Module
oscillate against their Zero Stop pin.
Pins:
Pin
501
502
503
546
Voltage
Zero Volts (This point is ground)
+16( 0.15) VDC
-16( 0.15) VDC
+11( 0.15) VDC
Voltage
+16( 0.15) VDC
-16( 0.15) VDC
-160( 20) VDC
+160( 20) VDC
Document number
Revision 01
Page 50
SYMPTOM/PROBABLE CAUSE
D257272-1200-MAN-002
ACTION
is Zero to +11 VDC.
If the voltage at Pin 54
7 is mi ssing, trouble shoot and
repair/replace as required.
THROTTLE OUTPUT
A. Engine will only
held by hand.
run when throttle is A. Measure the current from either Pin 533 or 545 when the
engine is at RUN speed with NO LOAD, the re ading should
be 30 to 60 mA. If the engine is at
RUN sp eed with FULL
LOAD, the reading should be 180 to 200 mA.
Check for an ope n ci rcuit betwee n the throttle le ads and
repair/replace as requi red. If the actuator resistance is 30 to
36 try replacing the AC Control Module.
AC CURRENT FEEDBACK
A. There is a lo ad imbalance between the
generators conne cted to the Main AC
Bus.
MASTER/SLAVE
A. A large KW load imbala nce bet ween A. Start an eng ine/generator and allow it to operate un til it is at
the en gines. This is pro bably caused
normal running temperatu re. Adjust the generator fr equency
by impro
per a
ctuator current
to 50 Hz. Disconnect the generater circuit breaker a nd then
adjustment.
measure the actuator curr ent a t e ither Pin 533 or 5 45 of the
AC Control b y connecting a multime ter (set on the 1 00 mA
There are several other, though
scale) in series with the wir e going to the pin. Actuator current
less comm on, reas ons for a
must be 30 to 60 mA. If it is not within that range, adjust until it
large KW load imbala nce: a
is. Perform this with all o f the engine/generators. Ensure that
defective KW Meter, a defective
all of them have an ac tuator current tha t falls within a 10 mA
AC Co ntrol Module,
a bad
range betwe en the smallest and lar gest. All actuator's
Actuator, or
an engine
currents must fall with the 30 to 60mA range given above.
problem.
www.nov.com
Document number
Revision 01
Page 51
3 HI-LINE
D257272-1200-MAN-002
OPERATION
Hi-Line operation allows you to replace or supplement the electrical power obtained from
your engine/generators with electrical power obtained from a commercial power company.
If this source of power is available at your site, the cost savings of utilizing Hi-Line
operation can be considerable.
The Hi-Line operation is primarily performed by a step-down transformer and two circuit
breakers (refer to Figure 2-21). There are other circuit components that allow control or
monitoring of Hi-Line operation. These other components are shown in Figure 2-22.
13,800 V (or Higher)
3000 KVA
600 VAC
MCB1
1600AF
MCB2
1600AF/AT
BUS
LOCATED IN
HI-LINE CUBICLE
REVERSE POWER TRIP RESET Lighted Push Button (LPB) switch (Item 40).
Two
www.nov.com
Document number
Revision 01
Page 52
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 53
D257272-1200-MAN-002
www.nov.com
Document number
Revision 01
Page 54
D257272-1200-MAN-002
4.1 Model
1000
In the Model 1000, the Generator Unit assemblies (refer to Figure 2-23) are mounted inside
the Generator Cubicle on the door and side panels.
www.nov.com
Document number
Revision 01
Page 55
4.2 Model
D257272-1200-MAN-002
1400
In the Model 1400, the Generator Unit assemblies (refer to Figure 2-24) are mounted inside
the Generator Cubicle on the door and side panels.
www.nov.com
Document number
Revision 01
Page 56
4.3 Model
D257272-1200-MAN-002
1861
In the Model 1861, the Generator Unit assemblies (refer to Figure 2-25) are mounted inside
the Generator Cubicle on the door and side panels.
www.nov.com
Document number
Revision 01
Page 57
www.nov.com
D257272-1200-MAN-002
Section 1.3
SCR Unit
www.nov.com
Technical Manual
50 Hz SCR Unit
REFERENCE
RIG/PLANT
SDRL CODE
TOTAL PGS
68
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
CLIENT DOCUMENT NUMBER
www.nov.com
DISCIPLINE
20605-48
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Dr
Houston, Texas 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-003
01
Section 1.4
Drillers Console
www.nov.com
Technical Manual
Drillers Console
RIG/PLANT
SDRL CODE
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
TOTAL PGS
41
DISCIPLINE
REFERENCE
20605-50
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Dr
Houston, Texas 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-004
01
Section 1.5
www.nov.com
Technical Manual
Transformer Feeder Unit
RIG/PLANT
SDRL CODE
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
TOTAL PGS
DISCIPLINE
REFERENCE
20605-52
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Dr
Houston, Texas 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-005
01
Section 1.6
www.nov.com
Technical Manual
50 Hz Motor Control Center
RIG/PLANT
SDRL CODE
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
TOTAL PGS
12
DISCIPLINE
REFERENCE
20605-53
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Dr
Houston, Texas 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-006
01
Section 1.7
Drawworks Braking
www.nov.com
Technical Manual
Drawworks Braking
REFERENCE
RIG/PLANT
SDRL CODE
TOTAL PGS
28
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK10301D
CLIENT DOCUMENT NUMBER
www.nov.com
DISCIPLINE
20605-56
REFERENCE DESCRIPTION
DOCUMENT NUMBER
REV
D257272-1200-MAN-007
01
Section 1.8
Unique Devices
www.nov.com
Technical Manual
Unique Devices
RIG/PLANT
SDRL CODE
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
TOTAL PGS
110
DISCIPLINE
REFERENCE
10567-02
REFERENCE DESCRIPTION
National-Oilwell Varco
11000 Corporate Centre Dr.
Houston, Texas 77041
USA
Phone +1 281 854 0400
Fax +1 281 854 0607
DOCUMENT NUMBER
REV
D257272-1200-MAN-008
01
Section 1.9
www.nov.com
RIG/PLANT
REFERENCE
REFERENCE DESCRIPTION
7272 C00,01,02,04
ADDITIONAL CODE
GMK710301D
This document contains proprietary and confidential information National Oilwell Varco
which belongs to National Oilwell Varco, it is loaned for limited Rig Solutions - Western
purposes only and remains the property of National Oilwell
Hemisphere
Varco. Reproduction, in whole or in part, or use of this design or
11000 Corporate Centre Dr
distribution of this information to others is not permitted without
Houston Texas 77041
the express written consent of National Oilwell. This document is
to be returned to National Oilwell Varco upon request and in any Phone 281 854 0400
event upon completion of the use for which it was loaned.
Fax
281 854 0607
Copyright National Oilwell Varco
DOCUMENT NUMBER
REVISION
D257272-1200-SPL-001
01
SDRL CODE
TOTAL PGS
4
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
www.nov.com
DISCIPLINE
Page: 2
Document Number:
Revision:
D257272-1200-SPL-001
01
REVISION HISTORY
01
Rev.
18.12.2008
Date (dd.mm.yyyy)
www.nov.com
SMA
NEG
KM
Prep.
Check
Appr.
Page: 3
EQUIPMENT DESCRIPTION
ALARM-120VAC,HORN,GREY FEDERAL
BDGE- 30A,1000V,1PH
BLWR-E/1 ,600V,1PH,.75HP,60HZ
CAP- 1 MFD,2000VDC
CB-1200 ,3P, 600VAC, 42KIC,1 200AF,NON AUTO
CB-1600AF,3P, 600VAC, 65KIC W/ACC,SHF16B216CB-CLOSING COIL,120VAC,F/POWER BREAK II,REMOTE CLOSE
CB-CONT,0A0B2C,FUW SPECTRA RMS F/SGLA CB'S
CB-UVR, 24VDC,F/GE POWER BREAK II
CB-UVR, 24VDC,FUW ALL SPECTRA RMS CB'S
CONN-OUTLET BOX,1.5X4X4,W/.5KO
CONN-RECP,3W,2P,15A
CONT-BLK,0A1B0C,OT,RED
CONT-BLK,1A0B0C,OT,GRN
CONTR-1250A, P,1000VDC,125VDC COIL, A B C CONT,A/C
CONTR-1800A,1P, V C, 74VDC COIL,ROSS HILL,MDL 1800/C
DIAL-15TURN REPL D211 BECKMAN
FUSE- .6A, 500V C, 10KIC, CLASS M
FUSE- 2. A, 500V C, 10KIC, CLASS M
FUSE- 3.5A, 500V C, 10KIC, CLASS,
FUSE- 6. A, 500V C, 10KIC, CLASS M
FUSE- 15. A, 600VAC,200KIC CLASS CC
FUSE- 900. A, 1300V C, KIC, CLASS,IND
FUSE-HOLDER,1P, 30A, 600VAC, CLASS M
FUSE-HOLDER,2P, 30A, 600VAC, CLASS M
FUSE-HOLDER,3P, 30A, 600VAC, CLASS M
FUSE-HOLDER,3P,30A,600VAC,FUW 1.5" FUSE,UL
KNOB-S/S,ROTARY TORQUE LMT
METER-AAC,0-1500,HOYT,0-1MADC, 200 OHM,NOI LOGO
METER-ADC,0-1000,EDGE,0-1MA RA TING,TYPE 185
METER-ADC,0-1500,HOYT,0-1MADC, 200 OHM,NOI LOGO
METER-HOUR,99999.HRS,120V,60HZ NON RESET,2.5"SQ
METER-KW,0-1200,HOYT,0-1MADC,
METER-PWR LMT,0-100%,PANEL,EDG EWISE,HORIZONTAL,0METER-VDC,0-1000,HOYT,0-1MADC, 200 OHM,N.O.V. LOGO
MODULE-AC,(JOB CAL'D)
MODULE-DC,SERIES,W/1K OHM RES INSTALLED FOR VFB AT
PB-110VAC ,30MM,YEL,MOMENT
PB-CAP,RED,DUST CVR
PB-CONT,1A0B0C, 6A,FUW MPX
PB-KIT, A B C,3HD OFF-IDLE-RUN
PB-RING,PROT F/MSHRM HD P/P
PCA-3PH (L-N) CUR FDBK W/1 OHM 10W BURDEN (X2) M1
PCA-VOLTAGE FEEDBACK
PC-DRLS CONS,ADD:JUMPER-PIN 1 TO D23 CATHODE
PC-GEN EXC,REV 120 OR 240V RATED
PC-S&A,PWR SPLY,60V
PL- 24VAC/DC,22MM,GRN LED,COMP
PL-110VAC ,22MM,CLR LED,COMP DC,22MM,RED INTEGRATED
PL-110VAC ,22MM,RED LED,COMP
PL-110VAC ,22MM,YEL LED,COMP
PL-110VAC ,30MM,RED LED,KIT (ML1-100R)+LAMP
PL-110VAC ,30MM,WHT LED,KIT (ML1-100W)+LAMP
REGULATOR-W/FILTER,0-15PSI W/G AUGE,20 MICRON
www.nov.com
VSP
Platfrom
Work
Ocean
Endeavor
Over
P.O. No.
Currency
GMK710301D
126-016632
0408-0001-00
0000-6817-69
0100-0302-01
0505-0014-00
0302-1636-03
0000-6975-23
0000-6972-34
0000-6897-31
0000-6982-13
0000-6927-67
1102-0063-00
0002-0523-45
0000-6854-48
0000-6854-47
0401-0015-00
0100-0389-02
0609-0002-00
0301-0009-00
0301-0010-00
0301-0011-00
0301-0012-00
0000-6981-43
0000-6935-14
0000-6984-02
0000-6988-00
0000-6988-01
0000-6980-71
0613-1233-01
0801-0009-22
0000-6810-01
0801-0070-22
0000-6905-90
P250002-0007-62
0801-0071-00
0801-0060-22
0521-2500-00
0522-2400-27
P250000-9692-93
0000-6921-48
P250000-9692-97
0100-1518-01
0000-6961-13
0510-0400-00
0509-3000-00
0509-2500-01
0509-7901-00
0510-0500-00
0406-0061-00
P250000-9692-38
0406-0065-00
0406-0067-00
P250000-9692-31
P250000-9692-35
0000-6892-12
Ref./Ser. No.
1
2
1
1
1
1
1
1
1
1
1
1
2
2
2
3
1
20
20
20
20
20
10
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Delivery time
for parts (in
weeks)
USD
Recommended
Item /
Ref. No.
Quantity to be
ordered
COMMISSIONING
SPARES
Recommended
Item No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
Rig
Quantity to be
ordered
Engineering &
Marine Services
TAG No.
MATERIALS DATA
DOC. NO:D257272-1200-SPL-001
Customer
INQUIRY NO:
Engineering contractor:
National Oilwell Varco
Engineering
contractor:
National Oilwell
Oilwell Varco, 1530 W. Sam Houston Pkwy.N,
Suppliers
name
and address: National
Suppliers name and address: Houston
NationalTX
Oilwell,
770431530 W. Sam Houston Pkwy.N, Houston TX 77043
Phone:
713-935-8000,
Fax.:
713-935-8305
Phone Numbers :
Phone:
713-935-8000,
Fax.:
713-935-8305
AfterSales
SalesSpare
SpareParts:
Parts:GERRY.WHITE
Clifton Hartoon (Extension
Suppliers contact person:
After
(Extension ## 7411)
8898)
EMAIL:
CLIFTON.HARTOON@NATOIL.COM
GERRY.WHITE@NOV.COM
www.nov.com
0504-0012-00
0504-0005-00
0506-0001-00
0100-0135-00
0000-6808-51
0000-6941-50
0501-0616-10
I110-001008
0000-6880-37
0000-6953-61
0000-6803-64
0000-6837-15
0000-6854-44
0000-6854-45
0403-0008-01
1003-0091-01
1003-0095-00
1003-0007-00
1003-0008-00
1003-0066-00
0100-0357-00
1
1
1
1
2
1
6
1
1
2
1
1
1
1
2
1
1
1
1
1
1
Page: 4
Section 1.10
SCR/GeQTest Procedure
www.nov.com
RIG/PLANT
0RELOH0RGXODU:RUNRYHU8QLWVW
ADDITIONAL CODE
SDRL CODE
TOTAL PGS
32
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
CLIENT DOCUMENT NUMBER
www.nov.com
DISCIPLINE
REFERENCE
J257272
REFERENCE DESCRIPTION
DOCUMENT NUMBER
REV
D257272-1200-PRO-001
02
Section 1.11
Certificate of Compliance
www.nov.com
Certificate of Compliance
VSP WORKOVER RIG
SCR / GENERATOR CONTROL
RIG/PLANT
REFERENCE
7272 C00,02
SDRL CODE
TOTAL PGS
REMARKS
MAIN TAG NUMBER
CLIENT PO NUMBER
GMK710301D
www.nov.com
DISCIPLINE
REFERENCE DESCRIPTION
DOCUMENT NUMBER
REV
D257272-1200-CER-001
01