Professional Documents
Culture Documents
and Telephones
03-300686
Issue 3
Release 5.0
January 2008
Contents
Chapter 1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . .
Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
10
11
Related resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
13
13
13
14
16
17
. . . . . . . . . . . . . . . . . . . . . . . . .
19
20
21
24
25
29
29
29
33
33
36
38
38
39
41
41
Information outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
Station cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
Closets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Satellite locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
43
43
Contents
Site locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
44
45
45
50
52
54
57
58
58
. . . . . . . . . . . . . .
62
. . . . . . . . . . . . . .
64
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
65
65
. . . . . . . . . . . . . .
67
69
69
Connecting telephones . . . . . . . . . . . . . . . . . . .
Connectable telephones and consoles . . . . . . . .
Connecting a typical telephone . . . . . . . . . . . .
Connecting adjunct power . . . . . . . . . . . . . . .
Connecting an analog station or 2-wire digital station
Analog tie trunk example . . . . . . . . . . . . . . . .
Digital tie trunk example . . . . . . . . . . . . . . . .
DS1 tie trunk example . . . . . . . . . . . . . . . . .
Collocated DS1 interface trunks . . . . . . . . . . . .
DS1 interface trunks using T1 channel service unit. .
.
.
.
.
.
.
.
.
.
.
70
70
73
74
75
76
77
78
78
79
81
84
85
. . . . . . . . . . . . . . . . . . .
86
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
86
86
87
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Contents
87
87
88
88
90
91
Off-premises connections . . . . . . . . . . . . . . .
Off-premises protection requirements . . . . . .
Telephone restrictions for exposed environments
Digital Out-of-Building Telephone Protection . . .
Installing the ITW Linx Enhanced Protector . .
Installing the 4C3S-75 Enhanced Protector . .
Installing the data link protector . . . . . . . .
.
.
.
.
.
.
.
91
93
94
94
95
95
95
96
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. . . . . . . . . . .
. . . . . . . . . . .
97
99
. . . . . . . . . . .
104
. . . . . . . . . . .
105
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
106
. . . . . . . . . . . . . . . . . . . . . . .
107
109
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
109
110
111
114
114
115
115
116
117
118
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
119
119
120
120
121
Contents
122
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
123
124
125
125
126
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
128
128
129
130
131
. . . . . . . . . . . . . .
131
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . .
132
132
133
135
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. . . .
. . . .
. . . .
136
136
137
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
138
139
140
141
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
142
143
143
144
144
144
144
145
145
145
145
145
146
147
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Contents
LED indicators . . . . . . . . . . . . .
Telephone console LEDs . . . . .
Attendant console LEDs . . .
Terminal alarm notification . .
DS1 Converter circuit pack LEDs
SPAN LEDs . . . . . . . . . .
Index
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
147
148
148
148
148
150
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
151
Contents
Chapter 1: Introduction
This documentation, Installing and Connecting the MDF and Telephones provides procedures
for installing Main Distribution Frames (MDF) and telephones. The procedures explain how you
connect media gateways to the MDF and how to connect the MDF to the public switched
telephone network (PSTN). This document also explains how to install and wire telephones.
The following information is included in this document:
Audience
This documentation is for the following audiences:
Installing the patch panel on page 29. This chapter is only for customers using a patch
panel rather than a main distribution frame (typically smaller installations).
MDF connections to stations and the public switched telephone network on page 41
Introduction
Connect the necessary telephone, trunking, and peripheral equipment using the information in
Installing and wiring telephones and trunks on page 69 and Installing and wiring telephone
power supplies on page 109.
Complete the installation using information in the following section:
Note:
Note:
If you do not have Acrobat Reader, you can get a free copy at
http://www.adobe.com.
Related resources
Sending us comments
Avaya welcomes your comments about this book. To reach us by:
When commenting, be sure that you mention the name and number of this book, Installing and
Connecting the MDF and Telephones (03-300686).
Related resources
You may need the information in the following documents to perform a complete installation.
These documents are included on the CD-ROM Documentation for Avaya Communication
Manager, Media Gateways and Servers, (03-300151). You can download the contents of this
CD-ROM from the Avaya Support Web site, http://support.avaya.com.
Installing the Avaya G650 Media Gateway, 03-300685. Provides procedures for installing
and cabling a G650 Media Gateway, connecting to the customers network, and testing the
complete configuration.
Adding New Hardware for Avaya Servers and Gateways (03-300684). Provides
information on installing adjunct and peripheral equipment that an S8400, S8500, or
S8700-series Server supports.
11
Introduction
Maintenance Commands for Avaya Communication Manager 5.0, Media Gateways and
Servers, (03-300431). Provides information on how to use command interfaces, command
syntax, and output from maintenance-related commands.
Maintenance Alarms for Avaya Communication Manager 5.0, Media Gateways and
Servers, (03-300430). Provides information on how to use alarms, error codes, and tests
to diagnose and repair problems.
Maintenance Procedures for Avaya Communication Manager 5.0, Media Gateways and
Servers (03-300432). Provides information on how to troubleshoot and replace various
components.
The following job aids are also available on the CD-ROM Documentation for Avaya
Communication Manager, Media Gateways and Servers:
- Approved Grounds. Provides a description of all approved grounds.
- Connector and Cable Diagrams (Pinout Charts). Provides pinout information for various
components.
- Option Switch Settings. Provides settings for various components.
For all documents associated with the S8400, S8500, S8700-series Server, see the CD titled
Documentation for Avaya Communication Manager, Media Gateways and Servers (03-300151).
If the installation will use a patch panel rather than a main distribution frame, use the procedures
in Chapter 3: Installing the patch panel on page 29.
110-type hardware
The trunk/auxiliary field and the distribution field are mounted on the same wall. Each 110P-type
terminal block is 8.5 inches (21.6 centimeters) wide. Vertical patch cord troughs are 5.31 inches
(13.4 centimeters) wide and horizontal patch cord troughs are 23 inches (58.4 centimeters)
wide.
Each 110A-type terminal block is 10.8 inches (27.4 centimeters) wide; however, no horizontal
patch cord troughs are used and the blocks are shorter than 110P-type terminal blocks. This
allows the 110A-type terminal blocks to be stacked. Therefore, the 110A-type hardware requires
less space than the 110P-type hardware on a per-station basis.
13
Note:
Installation layout
Make sure you review the following information:
To minimize the station wiring distances, centrally locate the sites/satellites, or adapters
among the information outlets.
One 258A/BR2580A adapter is required for each 25-pair station cable containing 4-pair station
circuits. One 356A adapter is required for each 25-pair station cable containing 3-pair station
circuits. Hardware requirements are the same as for the equipment room.
Note:
Note:
This formula may not compensate for the unused 25th pair in all cases. If not, it
must be allowed for.
15
The green field terminates the network interface leads from the central office (CO) and
provides the terminals to cross-connect the leads to the purple or yellow fields as required.
A single row of the 110-type terminal block can terminate 24 1-pair, 8 3-pair, or 12 2-pair
trunks.
The purple field terminates the trunk circuits from the media gateway with WP-90929, List
1 or 3 concentrator cables. Also, 25-pair cables can be used to terminate trunk circuits
from the media gateway with each trunk circuit pack connecting to one 25-pair row of the
110-type terminal block. Each terminal block row can terminate 24 1-pair, 8 3-pair, or 12
2-pair trunks.
The yellow field provides cross-connect terminals for all miscellaneous leads from the
media gateway, such as alarm monitors, emergency transfer relay power, and attendant
console power. This field is used for emergency transfer wiring, paging equipment, music
sources, and so forth.
The purple field (port field) terminates 25-pair cables from the media gateway. Each line
circuit pack connects to one 25-pair row of the 110-type terminal block. One 25-pair cable
is required for each line circuit pack.
Note:
The TN2183 16-port Analog Line circuit pack requires an adapter cable to
connect from one connector on the media gateway to two 25-pair connectors on
a terminal block. The yellow field (auxiliary field) terminates all 25-pair cables
from the auxiliary cabinet (if used). The yellow field is located in the lower
right-hand corner of the distribution field.
Note:
The white field (station field) terminates the station wiring. The white field indicates 3-pair
station circuits (eight circuits per 25-pair cable) routed through a satellite closet.
The blue field (station field) also terminates station wiring. The blue field indicates 3- and/
or 4-pair station circuits (eight or six circuits, respectively, per 25-pair cable). The fourth
pair, of the 4-pair station circuit provides adjunct power from the cross-connect field on an
as-needed basis to telephones and consoles within 250 feet (76 meters) of the MDF.
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Figure 2: Example MDF connections (G650 Media Gateway) on page 18 shows a detailed
example of the G600 Media Gateway cables connecting media gateways and satellite closets to
the MDF. This figure shows the cross-connections for one example station circuit.
17
4
9
13
14
11
12
15
7
13
6
13
18
8
17
16
10
14
13
12
11
10
09
08
-48 VDC
07
06
05
04
03
02
01
-48 VDC
RETURN
Figure notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
1
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
10
11
12
13
14
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
10
11
12
13
14
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
10
11
12
13
14
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
10
11
12
13
14
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
10
11
12
13
14
Powe
r
FA
N
FA
N
OR
PO
WE
R
AN
D
FA
IL
PO
WE
R
OK
AC
INP
UT
DC
INP
AC
TIV
UT
E
RIN
G
Figure notes:
1.
2.
3.
4.
19
Each label identifies two rows on the terminal block. The upper half identifies the row above it
and the lower half identifies the row below it. The labels are inserted into the clear plastic
designation strips furnished with the terminal blocks. The strip is snapped in place between the
terminal block rows. Label code number 1220A (comcode 103970000) contains all of the
required labels.
Figure 4: Label graphic symbols and nomenclature
Figure notes:
1. Floor or Building Identification (write as
required
2. Media Gateway
3. Carrier (leave blank for G600 Media
Gateway)
4. Slot
5.
6.
7.
8.
9.
Information Outlet
Site/Satellite Closet
Tie Circuit
Floor
Building
21
11. If installing another distribution field terminal block, partially install the first screw for the
terminal block, on the line, 7/8-inch (2.2 centimeter) to the right of the previous screw.
Partially install the second mounting screw 7-11/16 inch (19.5 centimeter) to right of the
screw just installed. Repeat Steps 4, 5, and 6.
12. If installing a vertical patch cord trough in the distribution field, repeat Step 6.
13. Repeat Steps 11 and 12 until all the terminal blocks and vertical patch cord troughs in the
distribution field are installed.
Figure 5: 110A-type terminal blocks (300-pair)
Figure notes:
1.
2.
3.
4.
5.
Figure notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
23
Figure notes:
1. 1110C1 Apparatus Mounting
2. 1110A2 Apparatus Mounting
3. 76 inches (193 centimeters)
Description
Comcode
1110A2
Apparatus Mounting
Frame
104032495
1110C1
104175120
1110A1
104176268
2110A1
104176276
2110B1
104176284
Note:
Note:
Nine 1/4-inch (0.63 centimeter) holes are provided in a cable slack manager base
if earthquake mounting is required. If a base is mounted on an uneven floor,
shims may be required for leveling and to assure proper fit of the covers.
Holes are provided in the sides of the base for bolting cable slack manager
together. Obtain bolts and shims locally.
4. An example of how the media gateway cables route through the cable slack manager is
shown in Figure 8: Cable routing through Cable Slack Managerexample for MCC1 Media
Gateway on page 26.
25
Cable clamps are required in installations with cable slack managers. At the rear of the media
gateways, install two cable clamps using the screws provided. These clamps hold the 25-pair
input/output or MDF cables in place. Figure 8: Cable routing through Cable Slack
Managerexample for MCC1 Media Gateway on page 26 and Figure 9: Cable routing through
Cable Slack Managerexample for SCC1 Media Gateway on page 27 show cable clamp
placement and cable routing.
Figure 8: Cable routing through Cable Slack Managerexample for MCC1 Media Gateway
Figure notes:
1. Top of Media Gateway
2. Cable Slack Manager
3. Cable Clamp
Figure 9: Cable routing through Cable Slack Managerexample for SCC1 Media Gateway
1
2
4
5
Figure notes:
1.
2.
3.
4.
5.
27
Note:
Note:
You do not have to mount the patch panels in the same rack as the media
gateways. You can mount the panels in telephone closets as appropriate.
For more information, see Figure 10: Typical RMC patch panel installation on page 30 while
you perform this procedure.
To install patch panels:
1. Use the supplied mounting screws to mount the patch panels on the rack below media
gateway A or above the topmost media gateway.
2. Attach B25A cables to the patch panels and the circuit pack amphenol connectors.
Note:
Note:
Note:
Connect 24-port DCP or analog circuit packs to the 24-port patch panels.
Note:
Connect 8-port analog trunk, combo, or DID trunk circuit packs to either of the
first two banks on the 8-port patch panel. If an TN2185B ISDN-BRI S/T-TE
Interface (4-wire, 8 ports) circuit pack is present, connect that circuit pack to the
third bank on the 8-port patch panel.
29
3
3
4
5
Figure notes:
1. Circuit pack amphenol
connectors and B25A cables
2. IP server interface adapter
and green CAT5 cable
DS1
24 Port Digital
24 Port Analog
16 Port Digital
16 Port Analog
12 Port BRI
8 Port Hybrid
8 Port Digital
8 Port DID
8 Port CO
8 Port Analog
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
31
Trunk cables among network interface, sneak fuse panel, and media gateway on page 38
33
A
labels LJK 060396
Figure notes:
1. Purple Label (Port Cable)
2. Blue/Yellow Label (Building
and Floor)
The top blue/yellow building and floor labels are for cables connecting from the equipment room
to a site/satellite location on another floor or in another building. The yellow label is for auxiliary
circuits connecting to the trunk/auxiliary field. The bottom blue/yellow label is for 25-pair cables
connecting to site/satellite closets. See Table 2: Equipment room labels.
Table 2: Equipment room labels
Label name
Range
Port Cable
1A1-1A20, 1B1-1B20,
1C1-1C20, 1D1-1D20,
1E1-1E20
Building
Field Identified
Floor
Field Identified
Auxiliary Cable
Field Identified
Site or Satellite
Figure 12: Equipment room cabling labels on page 34 details the label name and range of each
label. Table 3: Cable/connector/building label ordering information provides label ordering
information.
Table 3: Cable/connector/building label ordering information
Description
Quantity
Comcode
201A Labels
34 Sheets
103969994
Figure 13: Self-stick label on 25-pair cable connector shows the proper way to install a label on
a 25-pair cable connector. Install the label near the rear of the connector so it is not obscured by
the media gateway connector retainers. It can also be installed on the skin of the cable near the
connector.
Figure 13: Self-stick label on 25-pair cable connector
35
Figure notes:
1. Main Distribution Frame
2. AC Power Cord (AC-powered
media gateways only)
3. Cable Slack Manager Number 1
4. Trunk/Auxiliary Field
5. Station Distribution Field
6.
7.
8.
9.
10.
Figure notes:
1. Main Distribution Frame
2. AC Power Cord (AC-powered
media gateways only)
3. Cable Slack Manager Number 1
4. Trunk/Auxiliary Field
5. Station Distribution Field
6.
7.
8.
9.
10.
Use these guidelines when routing cables from the media gateway to the MDF. Following these
guidelines will maximize use of the cable slack managers and make future cabling additions
and changes easier.
Connect each port cable at the media gateway, and then route it along the front trough of
the cable slack manager to the connecting/terminal block, where the cable is terminated.
Leave enough slack at the media gateway end of the cable to allow for proper dressing of
the cables.
Route the cable from the media gateway to the wall. Place the cable beside one of the
rows of columns in the cable slack manager.
Note:
Retainers mounted on the columns keep the cable from protruding above the top
of the base of the cable slack manager.
Note:
Determine the length of the cable required to reach from the cable slack manager to the
assigned connecting/terminal block.
Use D rings on the wall to support the cable. (The cable must be supported.)
37
Coil the cable around the columns in the cable slack manager to store cable slack. The
first run should always go across the full length of the 5 columns in the cable slack
manager.
Avoid placing copper cables where they may bend or strain fiber optic cables.
39
Closets on page 43
Information outlets
Information outlets are 8-pin modular jacks. Most of the outlets are wired with push-on
connections. Information outlets are also available that connect to a double modular plug-ended
4-pair station cable routed from the MDF, a site/satellite location, or an adapter.
41
Station cables
For clarity a station cable is either a 25-pair cable, multiple 25-pair cable, or 4-pair D-inside wire
(DIW) run from the equipment room, site/satellite location, or adapter to the information outlets.
The following station cables are available. See Figure 17: Example of extending 4-pair station
cables on page 43.
25-pair station cable Use between the equipment room and site/ satellite locations or
adapters. Use an A25D cable (male to male) between the equipment room and satellite closet.
Use a B25A cable between the equipment room and site closet or adapter.
Multiple 25-pair station cable Use between the equipment room and site/satellite locations or
adapters. This cable consists of individually sheathed 25-pair cables with a factory-installed
25-pair connector on each end. Use a male-to-female cable to connect between the equipment
room and site location or adapter. Use a male-to-male cable to connect between the equipment
room and satellite location. Staggered finger cables are recommended for all multiple 25-pair
station cables and are available in both double-ended and single-ended types.
Single modular plug-ended 4-pair station cable Use this cable between adapters and
information outlets that require push-on connections. It can also be used when 4-pair station
cables are field-terminated on the 110-type terminal blocks in the equipment room or satellite
closet and modularly connected to information outlets. The station cables are available in the
following lengths:
Note:
Double modular plug-ended 4-pair station cable Use this cable to provide nonstandard length
runs between adapters and information outlets with push-on connections. It can also be used
between adapters and modularly connected information outlets. It is available in the same
lengths as the single modular plug-ended cable.
Bulk Cable Same as the 25-pair cable or multiple 25-pair cable; however, the bulk cable is
not equipped with connectors. Use this cable between the equipment room and satellite closets
when both are equipped with punch-down type terminal/connecting blocks.
Closets
4-pair station cable Use this cable when 4-pair station cables are to be field-terminated on
the 110-type terminal blocks in the equipment room or satellite closet and the information outlets
require push-on connections.
Figure 17: Example of extending 4-pair station cables
2
5
4
Figure notes:
1. Station Cable
2. Information Outlet
3. 451A In-Line Adapter
4. 258A Adapter
5. 4-Pair Station Cable
Closets
Closets are intermediate points between the Main Distribution Field and the endpoint. They are
used to distribute wiring to multiple destinations via cross-connect equipment.
There are two different types of closet configurations. Satellite closets are usually distribution
points for multiple site closets. However, information outlets may be wired directly to a satellite
closet. Site closets are the last cross-connection point before the end user information outlet.
Satellite and site closets may be used to apply bulk station power to information outlets.
Satellite locations
Satellite locations are closets that provide an administration point (using cross-connect
equipment) for station cables and where adjunct power may be applied. The station cable
circuits from the equipment room MDF are 3-pair. At the satellite location, 4-pair circuits run to
the information outlets. The hardware used is 110-type terminal blocks.
43
110PE1-300CT/FT 25-pair connector on the white field and field-terminated on the blue
field
110PE1-900CT/FT 25-pair connector on the white field and field-terminated on the blue
field
Site locations
Site locations are closets that provide a point in the station wiring for the administration of
remote powering. Adapters are used at site locations to terminate the 25-pair station cables and
provide connection points (modular jacks) for power adapters and 4-pair station cables.
The 258A and BR2580A adapters plug into a 25-pair female cable connector. These adapters
divide the 25-pair cable into six 4-pair (modular jack) circuits. See Figure 23: 258A and
BR2580A Adapters on page 50.
The 356A adapter plugs into a 25-pair female cable connector. See Figure 24: 356A
Adapter on page 51. The 356A adapter divides the 25-pair cable into eight 3-pair circuits.
Although the circuits are 3-pair, the adapters modular jacks will accept the 8-wide modular plug
used on the 4-pair station cable.
! CAUTION:
CAUTION:
Adapters wired similarly to the 356A should not be used. Their jacks do not
accept 4-pair plugs.
If most of the telephones/voice terminals that require remote powering are within 250 feet (76.2
meters) of the equipment room, 4-pair station circuits are run from the equipment room to the
information outlets. If this is not the case, or if the customer requires 2-point administration,
3-pair station circuits are run from the equipment room to satellite locations. Then, the 4-pair
station circuits are run from the satellite locations to the information outlets.
This section has information about
Lists of telephones and consoles currently sold are provided in Table 7: Connectable telephone
and consoles on page 70.
Note:
Note:
Bridged taps are not allowed on any part of the station wiring.
45
7
6
10
11
12
13
12
r7 6 4 7 9 7 a C J L 0 3 1 3 9 6
Figure notes:
1. Part of Main Distribution Frame
(MDF)
2. 3-Pair Connecting Blocks
3. 4-Pair Connecting Blocks
4. Purple Field
5. Blue Field
6. Patch Cord or Cross-Connect
Jumpers
5
2
4
Figure notes:
4. DIW Station Cable (D-Inside
Wire)
5. Information Outlet
9
3
11
10
5
6
r758532a CJL 031196
Figure notes:
1.
2.
3.
4.
5.
Part of MDF
3-Pair Connecting Blocks
4-Pair Connecting Blocks
Purple Field
Patch Cord or Cross-Connect
Jumpers
6. Blue Field
47
5
6
8
3
7
15
10
12
13
16
14
11
r758430b LAO 032103
Figure notes:
1.
2.
3.
4.
5.
Part of MDF
3-Pair Connecting Blocks
Purple Field
White Field
Patch Cord or Cross-Connect
Jumpers
6. To Media Gateway (3-Pair
Modularity)
7. A25D Cable (3-Pair Circuits)
8. B25A Cable
8
10
6
11
12
3
Figure notes:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
B25A Cable
3-Pair Circuits
356A Adapter
Information Outlet
3-Pair Circuit in 4-Pair Wire
DIW Station Cable (D-Inside Wire)
49
Figure notes:
1. BR2580A Adapter
2. 258A Adapter
Figure notes:
1. 356A Adapter
Comcode
258A Adapter
102605136
BR2580A Adapter
403384720
356A Adapter
104158829
400B Adapter
103848859
400B2 Adapter
104152558
ZD8AJ Adapter
103881421
103942272
103786240
51
Port circuit location on the media gateway for each endpoint (media gateway/slot/circuit)
Auxiliary power supply, if required (main distribution frame (MDF), site/satellite closet, or
information outlet)
53
Note:
Analog trunks use the 507B sneak protector or equivalent. Over-voltage protection is
normally provided by the local telephone company.
DS1/E1/T1 circuits require isolation from exposed facilities. This isolation may be provided
by a CSU (T1), LIU (E1), or other equipment that provides equivalent protection
Analog telephones use 146 Series Line Protectors combined over-voltage and sneak
current protection, or equivalent: See PEC 8310-0xx; SAP Code 10512x.
DCP and ISDN-BRI terminals, and E&M tie trunks, use a low voltage version of the 146
Series Line Protectors.
The Model 507B sneak current fuse panel, or equivalent, is recommended for sneak current
protection for analog trunks. The panel contains two 25-pair connectors, one fuse removal tool,
and 50, 220029 sneak fuses (and two spares). Each column of sneak fuse panels requires
approximately 8 inches (20 centimeters) of horizontal wall space.
See Figure 26: Model 507B sneak fuse panel on page 55. See Table 5: Sneak fuse panel
ordering information on page 55 for ordering information.
Sneak
Current
Protector
507B
Figure notes:
1. 507B sneak current protector
2. 25-pair male connector (in)
Comcode
403613003
SCP-110 Protector
406948976
107435091
407216316
846300994
846300994
Connector cables (B25A male to female) connect the network interface to the sneak fuse panel.
Also, 157B connecting blocks equipped with SCP-110 protectors can be used for sneak current
protection.
55
The 507B includes 52 sneak fuses and two cables and can be ordered using PEC code 63210.
Use the SCP-110 protectors with 110-type hardware and on the 507B sneak fuse panel. The
SCP-110 Protectors can be ordered separately and installed on the 157B connecting block. Fifty
protectors are required per block.
Install the 507B near the network interface or patch panels with locally obtained #12 x 3/4-inch
screws (or equivalent).
Table 6: Sneak fuse connector pinout on page 56 is a pinout of the cable wiring and associated
fuse numbers.
Table 6: Sneak fuse connector pinout
Connector
pin numbers
Pair/fuse
number
26/1
27/2
28/3
29/4
30/5
31/6
32/7
33/8
34/9
35/10
10
36/11
11
37/12
12
38/13
13
39/14
14
40/15
15
41/16
16
42/17
17
43/18
18
44/19
19
1 of 2
Pair/fuse
number
45/20
20
46/21
21
47/22
22
48/23
23
49/34
24
50/25
25
2 of 2
57
a 10 AWG (#25) (6 mm2) wire tie wrapped to the exposed telecom cables
A minimum of 12" spacing should be maintained between the CBC and other power, ground, or
non-exposed communications cables.
2
10 AWG
10 AWG
RED
-48 V RTN
MCC
BLACK
50A
-48 V
6
Battery
circuit
breaker
50A
-48
VDC
BLACK
-48 V
LVD
50A
DC power
from rectifiers
-48 V RTN
MCC
12
Rectifiers
10
AC
phase
AC
phase
10 AWG
RED
10 AWG
RED
50A
10 AWG
BLACK
10 AWG
RTN
RED
10 AWG
BLACK
Green/Yellow
Green/Yellow
Green/Yellow
6 AWG
-48 V RTN
MCC
-48 V
11
10 AWG
10 AWG
10 AWG
Figure notes:
1. Approved Ground
2. 1 AWG Ground Wire
3. CBC Ground Terminal Bar at the
MDF (if used)
4. System Single-point Ground
Discharge Bar
5. DC Power Cabinet J58890R or
new DC system
Note:
Note:
6.
7.
8.
9.
10.
11.
12.
Note:
For a high-rise building, connect the CBC to an approved building ground on
each floor.
Note:
Below is general information for installing the CBC in all installations having
exposed facilities.
59
Figure notes:
1. 25-Pair Tip & Ring Cables to Media
Gateways
2. Coupled Bonding Conductor (CBC)
Terminal Block
3. Tie Wraps
4. Cable Shield or Six Spare Pairs
5. Ground on Carbon Block Protector or
Equivalent
6. Trunk Cable to Network Interface
7. 10 AWG (#25) (2.5 mm2) Wire
61
Figure notes:
1.
2.
3.
4.
5.
6.
7.
Equipment Room
Satellite Location
Work Location
White Row on 110 Terminal Block
Purple Row on 110 Terminal Block
Blue Row on 110 Terminal Block
Central Location for Terminals 1
through 6
63
Figure notes:
1. Equipment Room
2. To Central Location for Terminals 1
through 6
3. Blue Row on 110 Terminal Block
4. Purple Row on 110 Terminal Block
5. To Port Connector on Media Gateway
(Media Gateway 1, Position B, Slot 03)
6. 258A Adapter
7. D-Inside Wire Cut Down to
Connecting Block
8. Information Outlet
9. Telephone
65
Figure notes:
1. Trunk/Auxiliary Field
2. To Expansion Control Carrier AUX
Connector (MCC1 Media Gateway
only)
3. Concentrator Cable (WP90929, List 1)
4. Concentrator Cable (WP90929, List 3)
5. A25D (Male-to-Male) Cable
6.
7.
8.
9.
10.
11.
Alternate Block/Rows
RJ21X/RJ2GX Network Interface
Sneak Fuse Panel
B25A Cable
Central Office Trunks
Media Gateway
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24
1 4 7 10 13 16 19 22
1 4 7 10 13 16 19 22
1 4 7 10 13 16 19 22
Figure notes:
1. Green Field
2. 1-Pair Jumpers
3. Pairs
4. Purple Field
67
Figure 33: 3-pair modularity for trunk pairs for 3-pair Tie trunks
3
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Figure notes:
1. Green Field
2. 1-Pair Jumpers
3. Pairs
4. Purple Field
Note:
! CAUTION:
Having a phone that is on an IP trunk too close to a fax machine can cause
problems. If the phone is too close, the handset can pick up the tones from the
fax machine and change itself into the fax mode.
CAUTION:
To prevent this, turn down the volume on the fax machine, or move the phone set
further away from the fax machine, or on the IP Codec Set screen (change
ip-codec-set), set the Fax field to off if not sending or receiving faxes on the
IP trunk.
Auxiliary connector outputs (MCC1 and SCC1 Media Gateways only) on page 81
69
See the Job Aid titled Connector and Cable Diagrams (Pinout Charts) (555-245-773) for
information on pinouts.
Connecting telephones
This section includes the various analog, digital, and IP telephones can be connected to the
media gateway including:
Type
Internet Protocol
(IP)
2500/2554
Analog
2402
Digital
1 of 3
Connecting telephones
Type
2410
Digital
2420
IP/Digital
Analog
Analog
Digital
3410
Wireless
Wireless VoIP
3701, 3711
Internet Protocol
(IP) DECT
46xx series:
4601, 4602, 4602SW, 4606, 4610SW, 4612, 4620,
4620SW, 4621SW, 4622SW, 4624, 4625SW, 4630,
4630SW, 4690
Internet Protocol
(IP)
62xx series:
6211, 6219
Analog
64xx series:
6402/D, 6408D+, 6416D/D+M, 6424D+/D+M
Digital
Wireless
Internet Protocol
(IP)
Digital
Digital
Digital
2 of 3
71
Type
Digital
Softphones:
Netmeeting H.323
IP Softphone
CentreVu IP Agent
Softconsole
Internet Protocol
(IP)
3 of 3
Connecting telephones
! CAUTION:
CAUTION:
Do not use the 329A power unit for the attendant console. Use an 1151B1,
1151B2, 1145A, or MSP-1 power unit.
5. For terminals needing adjunct power, wire -48 VDC and ground to appropriate pins on the
terminal. See Figure 34: 302D to 4-wire DCP wiring.
73
TXT 1
39 TXT5
TXR 2
14 TXR5
PXT 3
40 PXT5
PXR 6
15 PXR5
7
8
302cwire RBP 040596
Figure notes:
1. 302D Attendant Console
2. 4-wire Digital Line Circuit Pack
(Position 1C02)
Note:
Note:
Adjunct power can be provided locally at the telephone or console by either the
1151B1 or 1151B2 power supply. Adjunct power can be provided from the
equipment room or equipment closet with the 1145B power unit. See Installing
and wiring telephone power supplies on page 109 for power supply information
and installation procedures.
Connecting telephones
Figure notes:
1. Flush-Mounted Information Outlet
2. Surface-Mounted Information
Outlet
3. To Individual Power Unit
4. 400B2 Adapter
5. To Telephone
6. Destination Service Access Point
(DSAP) Power Cord
75
28 T.3
T 2
R 3
03 R.3
2500wire RBP 071996
Figure notes:
1. 2500-Type Analog Station
BRI-T
ADJUNCT
+Vadj
DSS
(QUEST)
DTX
T0
+TX
+RX
-RX
-TX
-V
GND
-V
GNDVoice
RRVoice
+V
S0
TTVoice
OKdig
-V
+V
-V
GND
DRX
DSS
(ISDN)
BRI-A
TX
RX
BRI-U
TX
RX
DCP
TIP
RING
ANALOG
TIP
RING
+RX
-RX
HANDSET
GND
-TX
-V
+TX
Connecting telephones
4. Figure 37: Analog Tie Trunk wiring on page 77 shows a media gateway tie trunk connected
to another media gateway tie trunk. Names of the tie trunk leads must be determined from
the manufacturer or supplier of the external trunk circuit.
5. Administer on the Trunk Group screen on Avaya Site Administration (ASA). See the
Administrator Guide for Avaya Communication Manager (03-300509) for more details.
Figure 37: Analog Tie Trunk wiring
T.1 26
29 T.2
R.1 1
4 R.2
T1.1 27
30 T1.2
R1.1 2
5 R1.2
E.1 28
M.1 3
31 E.2
6 M.2
tie_wire RBP 071796
Figure notes:
1. External Trunk or Adapter
77
Figure notes:
1. External Trunk
2. Digital Trunk Circuit Pack
3. LO
Note:
Note:
The maximum distance between cabinets is 1,310 feet (399 meters).
Connecting telephones
Note:
Note:
A 3150 CSU is shown, a 120A Integrated CSU (ICSU) may be used.
Contact your Avaya representative for maximum cabling distances for the 3127 series CSU or
the 120A ICSU.
Figure 39: Typical connections to channel service unit
POWER
MODEM
NETWORK
DTE
Figure notes:
1. Connector to DS1 Interface Circuit Pack
2. C6C Cable (For Distances Over 50 ft (15 m),
Use C6E Cable(s))
3. T1 Channel Service Unit (CSU) 3150 Shown
4. T (Tip)
5.
6.
7.
8.
9.
R (Ring)
T1 (Tip 1)
R1 (Ring 1)
1.544 Mbps Digital Service Interface
To T1 Carrier
79
Lead
designation
Pin
number
White/Green
47
Green
LI
22
White/Brown
LO
48
Brown
23
White/Slate
LBACK2
49
Slate
LBACK1
24
Three -48 VDC power sources for remotely powering three attendant consoles or
telephone adjuncts
A relay contact that actuates a customer-supplied light, bell, or similar device. The relay
can activate when a major, minor, or warning condition occurs. The device connected to
the alarm leads must not exceed a rating of 30Vac RMS or 60Vdc max, at 0.75A max. The
customer provided alarm circuit must also meet the requirements for an SELV (Safety
extra-low voltage) circuit; the alarm circuit power source must be a power supply or
transformer meeting the UL 60950 SELV, Level 3, or Level 5 requirements.
Table 11: Auxiliary lead appearances at AUX connector
Color*
Pinouts
Output
W-BL
BL-W
26
1
Major
W-O
O-W
27
2
Minor
W-G
G-W
28
3
GRD
W-BR
BR-W
29
4
GRD
W-S
S-W
30
5
GRD
R-BL
BL-R
31
6
GRD
Power
1 of 3
81
Pinouts
Output
R-O
O-R
32
7
GRD
R-G
G-R
33
8
Not Connected
R-BR
BR-R
34
9
Not Connected
R-S
S-R
35
10
Not Connected
BK-BL
BL-BK
36
11
-48
GND
BK-O
O-BK
37
12
-48
GND
BK-G
G-BK
38
13
-48
GND
BK-BR
BR-BK
39
14
-48
GND
BK-S
S-BK
40
15
-48
GND
Y-BL
BL-Y
41
16
-48
GND
Y-O
O-Y
42
17
-48
GND
Y-G
G-Y
43
18
Not Connected
Y-BR
BR-Y
44
19
GND
-48
Y-S
S-Y
45
20
GND
-48
V-BL
BL-V
46
21
GND
-48
V-O
O-V
47
22
Not Connected
V-G
G-V
48
23
Ext Alarm A3
Ext Alarm Return
Power
Emergency
Transfer Relay
Power
AUX Power
2 of 3
Pinouts
Output
V-BR
BR-V
49
24
Not Connected
V-S
S-V
50
25
INADS Tip
INADS Ring
Power
3 of 3
*. Color designation is the main wire color and the color of the stripe on the
wire. The following wire colors apply:
W White
BL Blue
O Orange
G Green
BR Brown
S Slate (Grey)
R Red
BK Black
Y Yellow
V Violet
. External alarm with signal incoming to server.
3External alarm with signal outgoing from server.
Table 12: Station pinout chart provides the station printout chart.
Table 12: Station pinout chart
Jack
Name
BRI-T
ADJUNCT
+Vadj
DSS
(QUEST)
DTX
T0
+TX
+RX
-RX
-TX
-V
GND
-V
GNDVoice
RRVoice
+V
S0
TTVoice
OKdig
-V
+V
-V
GND
DRX
DSS
(ISDN)
BRI-A
TX
RX
BRI-U
TX
RX
DCP
TIP
RING
ANALOG
TIP
RING
+RX
-RX
HANDSET
GND
-TX
-V
+TX
83
Figure notes:
1. Port Circuit Pack
2. Media Gateway Connector Pins
(3-Pair Modularity)
3. Main Distribution Frame (MDF) Pins
(3-Pair Modularity)
11
5
9
8
10
2
14
14
cydfadjn KLC 020599
Figure notes:
1. Typical Display Telephone
2. Individual Power Supply (Such as
1151B1 or 1151B2)
3. Information Outlet (Modular Jack)
4. 4-Pair D-Inside Wire (DIW) Cable
5. Satellite Site or Adapter Location
6. 25-Pair D-Inside Wire (DIW) Cable
7. Station Side of Main Distribution
Frame (MDF)
85
24 AWG wire
(0.5106 mm2)
26 AWG wire
(0.4049 mm2)
Feet
Feet
Meters
Meters
800
244
500
152
5,000
1,524
3,400
1,037
Phantom powered
1,400
427
900
274
Locally powered
5,000
1,524
3,400
1,037
Locally powered
Without Selector Console
Auxiliary power
! CAUTION:
CAUTION:
Do not use the 329A power unit for the attendant console.
The nonessential functions of an attendant console and its optional 26A1 or 24A1 selector
console derive their power from an auxiliary power source. Of the maximum of 27 attendant
consoles, 3 of the consoles can derive auxiliary power from the media gateway and through the
auxiliary cable located in the trunk/auxiliary field. Provide auxiliary power for a primary attendant
console through this cable so the console remains fully operational during short power outages.
258A-type adapters
Hard-wire bridging
Analog type hard-wire bridging is not allowed for any DCP endpoints. Hard-wire bridging
provides no way of combining the digital output of two bridged DCP sets. Also, a bridged
endpoint causes degradation of the DCP signal.
! CAUTION:
CAUTION:
87
IPSI-2
TN2312BP
Carrier
I/O
cable
Carrier
Amphenol/RJ21
25 pair connector
dli
1 KLC 111104
48VDC
750mA
Pin #
1
2
GRD
XFER48 BL-W
(-48VDC 120mA max)
GRD W-BL
XTALMA G-W
4
5
XTALMA
XTALMB W-G
XTALMB
GRD W-BR
808A
Emergency
Transfer
Panel
GRD W-O
Alarm Bell,
Light, or
Indicator
UPS Alarms
Major
GRD
Minor
GRD
Isolated
Contacts
60VDC, 5mA
89
AUX Connector
Pair Name*
White-Blue
Ground (Pin 2)
XR
Blue-White
White-Orange
Ground (Pin 8)
Orange-White
White-Green
Green-White
White-Brown
Ground (Pin 7)
Brown-White
1m
AL
1M
*. For additional information on the auxiliary field on the Main Distribution Field, see
Figure 49: Connections for telephone used for emergency transfer on page 103 and
Figure 50: Connections for telephone used for emergency transfer and as normal
extension on page 104.
! CAUTION:
CAUTION:
3. Connect an A25D cable between the sneak fuse panel and the terminal block connector
associated with the green row in the previous step.
4. Install a green label on the terminal block to identify the remote location.
5. Administer per the Administrator Guide for Avaya Communication Manager (03-300509).
Off-premises connections
Figure 44: Connections for 1 to 8 out-of-building analog telephones on page 92 shows the
connections for 1 to 8 off-premises analog telephones.
Figure 45: Connections to 24 out-of-building telephones on page 93 shows the connections for
up to 24 off-premises analog telephones. Concentrations of analog line pairs are used at both
buildings to minimize the off-premises wiring required. At the MDF, jumpers must be connected
between one row/connecting block in the white field and up to three rows/connecting blocks in
the purple field. At the station location, a WP-90929, List 1 Concentrator Cable is used. There
are eight station appearances on each of the three fingers of the concentrator cable.
The maximum distance from the media gateway to the out-of-building telephone is 6,000 feet
(1,829 meters) using 24 AWG (#5) (0.5 square millimeters) wire.
The maximum range of out-of-building analog telephones (500-, 2500-, or 7100-types)
connected to an analog line circuit pack should be such that the maximum loop resistance does
not exceed 1,300 ohms.
91
4
6
7
6
8
10
14
13
11
12
crdfobt CJL 101396
Figure notes:
1. Locally Engineered Cables and
Equipment
2. Out-of-Building Wiring
3. 25-Pair Connector
4. Multi-Pair Protector Units (Primary
Protectors with Heat Coils or Equivalent
with Sneak Current Protection)
5. 356A Adapter
6. B25A Cable (Male to Female)
7. Out-Of-Building Analog Telephones
Off-premises connections
2
4
6
4
10
11
15
16
14
12
13
crdf24o CJL 101396
Figure notes:
1. Locally Engineered Cables and
Equipment
2. 25-Pair Connector
3. Multi-Pair Protector Units (Primary
Protectors with Heat Coils or
Equivalent with Sneak Current
Protection)
4. B25A Cable (Male to Female)
5. Concentrator Cable (WP90929 List 1)
6. 356A Adapter
7. Out-of-Building Wiring
8. Out-Of-Building Analog
Telephones
9. Part of Main Distribution Frame
(MDF)
10. Station Side
11. Media Gateway Side
12. White Field
13. Purple Field
14. Cross-Connect Jumpers
15. Tip and Ring Wires
93
The 4-type protector is the preferred device. For installations not using primary protection,
4-type protectors should always be used. When the 3-type protector is already installed, a
separate sneak current protector is required.
The multi-pair protector units and the off-premises cabling must be locally engineered.
Connected multi-pair protector units (female 25-pair connector) are recommended.
Table 15: Analog line circuit protectors shows the recommended protectors.
Table 15: Analog line circuit protectors
Primary*
Primary
(with heat coil)
Sneak current
protectors*
3B1A (carbon)
4B1C (carbon)
220029 Fuse
3B1E-W
(wide gap gas tube)
4B1E-W
(wide gap gas tube)
SCP-1
3C1S
(solid state)
4C1S
(solid state)
*. The 3-type protectors should be used only if they are already part
of the existing protection system. A sneak current protector is
always required when a 3-type primary protector is used.
For catalogs and ordering information, go to the Avaya Cable Management Systems for Service
Providers Web site (http://connectivity.avaya.com/exchangemax/) and click Products &
Solutions.
Note:
Note:
The TN2181 16-port, 2-wire digital line circuit pack may not be approved for
some out-of-building uses. Contact your Avaya representative for more
information.
Off-premises connections
The 4C3S-75 may be used only with TN754B Digital Line circuit packs. Table 16: Digital Voice
Circuit Protectors lists the approved protectors.
Table 16: Digital Voice Circuit Protectors
Circuit Pack
TN2224CP all
vintages
When possible, all new and reused wiring installations should use blocks that accept the
standard 5-pin plug-in 4C3S-75 protector. However, there are reused wiring installations where
this may not be cost effective. For these installations, the ITW Linx protector may be installed.
An example of this is where screw-type carbon block protectorsor other nonplug-compatible
typesare in place and it is too costly to reterminate the outside plant cable on a 5-pin
mounting block for only a few out-of-building terminals.
95
See Figure 41: Example adjunct power connections on page 85 and Figure 46: Connections
at trunk/auxiliary field on page 96.
Figure 46: Connections at trunk/auxiliary field
25
50
IN
Figure notes:
1. To Network Interface Facility
2. To Control Carrier Auxiliary
Connector
Should power be restored to the relays while a call connected through the 808A is in progress,
the 808A maintains the connection until the user goes on-hook. Each 808A can handle up to
five CO trunks.
Installing telephones used only for emergency transfer (trunk/auxiliary field) on page 104
Installing telephones used for emergency transfer and as normal extension (trunk/auxiliary
field) on page 105
97
EMERGENCY
TRANSFER
PANEL
POWER
TRUNK/TEST SWITCHES
1
2
3
4
5
6
7
8
9
10
12
CIRCUIT
1
1
2
2
3
4
TRUNK OPTION
LOOP
GROUND
START
START
ACTIVATED
TRUNK IDENTIFICATION
TRUNK
LINE
EXT
LOC
808A
Figure notes:
1. 808A Emergency Transfer Panel
2. Circuit Start Selection Switches
Figure notes:
1. 808A Emergency Transfer Panel
2. Ear for Screw Mount
3. Cut-Out for Snap Mount
Note:
The 808A must be installed in a location that can be accessed only by authorized
personnel. The location must meet standard environmental considerations such
as temperature, humidity, and so forth.
99
4. Connect a 25-pair cable between the male RJ21 25-pair connector on the Emergency
Transfer Panel and the yellow field of the MDF. Table 18: Pin assignments for 25-pair
connector on page 101 shows the pinouts.
5. Make cross-connections for each emergency trunk/emergency station pair.
The 808A is connected to the MDF by means of a B25A cable. Figure 49: Connections for
telephone used for emergency transfer on page 103 shows the connections at the trunk/
auxiliary field for a telephone used only for emergency transfer.
Figure 50: Connections for telephone used for emergency transfer and as normal
extension on page 104 shows the connections at the trunk/auxiliary field for a telephone
used for emergency transfer as well as a normal extension.
The auxiliary field for a G650 connects via the DB9 alarm cable to the TN2312BP adapter in
the A carrier only. See Figure 42: IPSI-2 cabling on page 88 and Figure 43: Sample
Issue 1 IPSI-2 alarm cable connectivity on page 89.
6. On the trunk identification label at the bottom of the panel, record the trunk line, extension,
and location for each circuit.
7. To each telephone designated as an emergency terminal, attach a label identifying it as
such. The labels are provided with the unit.
8. Check for normal operation as follows:
Ensure the power supply is providing -48 VDC at 80 mA maximum. The power LED
should be ON.
If all of the above conditions are not met, remove the panel from service and replace it with
a new panel.
9. Check for transfer operation as follows:
If all of the above conditions are not met, remove the panel from service and replace it with
a new panel.
Circuit
number
10
11
Not Used
12
Test Switch
W-BL
TTC1
BL-W
RTC1
27
W-O
TTK1
O-W
RTK1
28
W-G
TLC1
G-W
RLC1
29
W-BR
TST1
Tip-Emergency Terminal 1
BR-W
RST1
Ring-Emergency Terminal 1
30
W-S
TTC2
S-W
RTC2
31
R-BL
TTK2
BL-R
RTK2
101
R-O
TLC2
O-R
RLC2
33
R-G
TST2
Tip-Emergency Terminal 2
G-R
RST2
Ring-Emergency Terminal 2
34
R-BR
TTC3
BR-R
RTC3
35
R-S
TTK3
10
S-R
RTK3
36
BK-BL
TLC3
11
BL-BK
RLC3
37
BK-O
TST3
Tip-Emergency Terminal 3
12
O-BK
RST3
Ring-Emergency Terminal 3
38
BK-G
TTC4
13
G-BK
RTC4
39
BK-BR
TTK4
14
BR-BK
RTK4
40
BK-S
TLC4
15
S-BK
RLC4
41
Y-BL
TST4
Tip-Emergency Terminal 4
16
BL-Y
RST4
Ring-Emergency Terminal 4
42
Y-O
TTC5
17
O-Y
RTC5
43
Y-G
TTK5
18
G-Y
RTK5
44
Y-BR
TLC5
19
BR-Y
RLC5
45
Y-S
TST5
Tip-Emergency Terminal 5
20
S-Y
RST5
Ring-Emergency Terminal 5
46
V-BL
COM1
21
BL-V
NO1
V-O
NC2
22
O-V
NC1
48
V-G
COM2
23
G-V
NO2
49
V-BR
24
BR-V
50
V-S
GRD
25
S-V
-48PX
EMXR
2822
TC
TK
LC
ST
TC
TK
LC
XR 1m AL 1M
ALARM MONITORS
3M
3m
3w
ST
TC
TK
LC
ST
TC
TK
LC
ST
TC
TK
LC
ST
C
O
M
1
N
O
1
N
C
2
N
C
1
C
O
M
2
N
O
2
C
O
M
3
N
C
3
G
R
D
-48
V
Figure notes:
1. To Network Interface Circuitry
2. To TN747B (or Equivalent) Central Office
Trunk Circuit Pack
3. To Blue or White Station Distribution Field
103
Figure 50: Connections for telephone used for emergency transfer and as normal
extension
10
35
ST
2820
ST
EMXR
TC
TK
LC
ST
TC
TK
LC
ST
TC
TK
LC
ST
TC
TK
LC
ST
TC
TK
LC
ST
C
O
M
1
N
O
1
N
C
2
N
C
1
C
O
M
2
N
O
2
C
O
M
3
N
C
3
G
R
D
-48
V
XR 1m AL 1M
ALARM MONITORS
Figure notes:
1. To Network Interface Facility
2. To Blue or White Station Distribution
Field
3. To TN2183 or Equivalent Analog
Line Circuit Pack
4. Connect ST leads on the yellow emergency transfer row/connecting block for each
emergency transfer telephone to the assigned terminal in the blue or white station
distribution field. The ST terminal leads should be terminated on the following pairs: 1, 4, 7,
10, 13, 16, 19, or 22 (the first pair of any 3-pair group).
5. Install the telephone:
Install patch cords/jumper wires between the media gateway side and the station side of
the station distribution field on the MDF.
Install patch cords/jumper wires between the media gateway side and the station.
105
Note:
Note:
A maximum of three devices can connect to one analog line circuit pack port.
Figure notes:
1. Port Circuit Pack
2. Media Gateway Connector Pins
(3-Pair Modularity)
3. Main Distribution Frame (MDF)
Pins (3-Pair Modularity)
Wire the queue warning indicator to the information outlet as shown in Figure 51: 3-pair
and 4-pair modularity on page 106 and Figure 41: Example adjunct power connections on
page 85.
107
Note:
Note:
Note:
Before you begin, read this Important warning for 1145B2 power supply on
page 110.
109
WARNING:
Important Safety Instructions follow.
When operating this equipment, basic safety precautions must be followed to reduce the risk of
fire, electric shock and personal injury, including the following:
For continued back-up protection and battery reliability, replace batteries every four years.
For mounting security, follow all installation instructions when mounting product.
Openings on top and bottom of power unit are provided for ventilation. Do not block or
cover these openings. Do not exceed recommended environmental temperatures.
Operate these products only from the type of power source indicated on the product
labels.
The power unit is equipped with a 3-wire grounding plug; a plug having a third (grounding)
pin. This plug will only fit into a grounding power outlet. This is a safety feature. If you are
unable to insert the plug into the outlet, contact an electrician to replace the outlet. Do not
defeat the safety purpose of the grounding plug.
To reduce risk of fire and electrical shock, do not overload power outlets.
Never push objects of any kind through the power supply or distribution unit slots as they
may touch dangerous voltage points or short out parts that could result in a risk of fire or
electrical shock.
To reduce risk of electric shock, do not disassemble these products. Return them for repair
when needed. Opening or removing covers may expose you to dangerous voltages or
other risks. Incorrect reassembly can cause electric shock when the products are
subsequently used.
Power down the power unit (see label on power unit on how to do this) and refer servicing
under the following conditions:
Do not attempt to recharge batteries on your own. The batteries may leak corrosive
electrolyte or explode. The 1145B2 power unit recharges the batteries safely.
Remove the batteries if the power unit will not be used for a long period of time (several
months or more) since during this time the battery may leak.
Discard discharged batteries as soon as possible. Discharged batteries are more likely to
leak.
Do not store batteries in high temperature areas. Batteries stored in a cold environment
should be protected from condensation during storage and warming. Batteries should be
stabilized at room temperature prior to use after cold storage. Do not install batteries if the
manufacturing date on the label indicates that the batteries are more than six months old.
Note:
The 1145B22/1146B2 is a -48 V power supply with 275 watts total output. Each output circuit is
current limited by a Polymer Positive Temperature Coefficient Resistance Device (PTC) that
limits the maximum output to 12 watts. Each 1146B2 output has an LED to indicate the status of
the PTC. If the LED is on, the PTC has a short on that power pair.
Not all outputs can simultaneously provide 12 watts. The average power per output cannot
exceed 8.6 watts (275/32 = 8.6). The 1145B22 is designed to power one ISDN terminal or DCP
adjunct per output. The maximum number of terminals or adjuncts is 32 at less than or equal to
6.25 watts each. The 1145B22 is required for installations outside the United States.
Auxiliary power (local or bulk) is always required for the following:
111
1149 Battery
On Battery Reserve
Charging Battery
Output Power On
-48V
-48V
RTN
RTN
17
18
19
20
21
22
23
24
25
10
26
11
27
12
28
13
29
14
30
15
31
32
16
Unit No.
Connected To:
1-8
1-32
Figure notes:
1.
2.
3.
4.
5. Power Cable
6. Nonswitched Outlet (120 VAC, 20
amp or 230 VAC, 15 amp)
7. Battery Backup Switch Setting
2
4
1149 Battery
On Battery Reserve
Charging Battery
Output Power On
8
7
6
1-8
1-32
Figure notes:
1. Wall Mounting Plate
2. Battery (1149B shown)
3. Second 1146B2 Power Distribution
Unit
4. T Cable (H600-347-G7)
113
Note:
Note:
A maximum of four power supplies can be powered from one dedicated 110 VAC,
20 amperes (or 230 VAC, 15 amperes) feeder. Use only nonswitched outlets
(outlets not connected to a wall switch).
2. Secure the wall mounting plates to a standard 3/4-inch (2 centimeters) thick plywood
mounting board. Each mounting plate comes with four #10 x 1/2-inch wood screws.
3. The 1145B2 Power Supply is snap-fit onto the bottom wall mounting plate without tools.
4. An installer-provided insulated ground wire, 16 AWG (#12) (1.2 square millimeters) or
greater, is required to connect the power supply frame ground lug to an approved ground.
The frame ground screw is located next to the AC outlet, to the left of the unit.
Rating
1148B
2.5 amp-hours
1149B
5 amp-hours
1147B
8 amp-hours
! CAUTION:
Total power cannot exceed 275 watts. The maximum ISDN terminal mixture is 24,
7500-series and 24, 8500-series terminals.
CAUTION:
The maximum DCP terminal mixture is 24, 7400-series and 24, 8400-series or
64, 8400-series terminals.
The expanded power distribution unit kit contains:
One T Cable
115
See Figure 53: Expanded power distribution unit on page 113 while installing the power
distribution unit. To install the expanded power distribution unit:
1. Set the spacer bracket onto the mounting plate and secure with the #8-32 x 1/2-inch
shoulder screws. The spacer bracket is not shown in the figure but is installed behind the
top power distribution unit.
2. Slide the keyhole slots in the power distribution unit over the shoulder screws.
3. Insert the #8-32 x 1-inch screw through the distribution unit, through the spacer bracket, and
into the plate. The mounting hole is located just above the wire clip. Tighten the screw
securely.
4. Set the battery back-up switch to the 1-32 (down) position.
5. Power-down the 1145B2 unit as described on the label on the side of the unit.
6. Remove the output power cable between the 1145B2 and the 1146B2 units. The cable will
not be reused.
7. Connect the P1 connector end of the T cable to the bottom power distribution unit.
Connect the P2 connector to the top distribution unit. Connect the P3 connector to the
1145B2.
8. Power-up the 1145B2 as described on the label on the side of the unit.
Meaning
Green
Yellow
Battery is charging
Red
Note:
Note:
A maximum of four power supplies can be powered from one dedicated 100120
V, 50/60 Hz, 20-amp feeder or 200240 V, 50/60 Hz, 10-amp feeder. Use only
nonswitched outlets.
2. Plug the cord into the outlet. This powers up the power supply.
3. Check AC operation of the 1145B2 Power Supply by monitoring the LEDs:
PASS: Green and yellow LEDs at the front of the unit should be lit together. See
Table 20: Power supply LEDs on page 116. After the battery reaches full charge (maximum
of 20 hours), the yellow LED should go out.
FAIL: If either green or yellow LED is not lit after powering up, check the connections. Test
the AC outlet. If power is available and the AC power cord and connections are good,
replace the power unit.
4. Disconnect the AC plug on the power supply; this activates the DC supply.
5. Check DC (battery back-up) operation of the 1145B2 Power Supply by monitoring the LEDs:
PASS: The red and green LEDs should be lit together. See Table 20: Power supply
LEDs on page 116.
FAIL: If either green or red LED is not lit after disconnecting AC power, check the
connections. If the connections are good, replace the power unit or batteries.
6. Reconnect AC power to the power supply.
117
11
5
14
6
12
14
13
10
Figure notes:
1.
2.
3.
4.
5.
6.
7.
8.
9. Modular Cord
10. Pins 7 and 8 (Display Terminal
Power)
11. AC Input
12. Installer-Provided Ground Wire
13. ISDN/ Display System Protocol
Terminal
14. Circuits 1-32
UL 1950
Approved
Approved
CE Regulatory
Compliance
Approved
EN 60950
Approved
TUV EN 60950
For safety instructions, see Important safety instructions on page 119. For installation
instructions, see Connecting the cables on page 121.
This product can be hazardous if immersed in water. To avoid the possibility of electrical
shock, do not use it near water.
The 1152A1 PDU contains components sensitive to electrostatic discharge. Do not touch
the circuit boards unless instructed to do so.
This product should be operated only from the type of AC (and optional DC) power source
indicated on the label. If you are not sure of the type of AC power being provided, contact
a qualified service person.
Do not allow anything to rest on the power cord. Do not locate this product where the cord
will be abused by persons walking on it.
119
Do not overload wall outlets and extension cords as this can result in the risk of line or
electric shock.
Disconnect the cords on this product and refer servicing to qualified service personnel
under the following conditions:
The 1152A1 PDU has no ON/OFF switch. To connect or disconnect power to the
1152A1 PDU, simply insert or remove the power cable from the AC power
receptacle on the rear of the 1152A1 PDU.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Data &
Power
1152A1 Power
Distribution Unit
AC
Data
Console
48Vdc
Use a standard CAT5, CAT6 or CAT6e straight-through Ethernet cable (not supplied), including
all eight wires (4 pairs) as shown in Figure 55: Connecting telephones and other end devices to
the 1152A1 PDU on page 121.
Figure 55: Connecting telephones and other end devices to the 1152A1 PDU
1
2
3
4
5
6
7
8
End Device
data
data
data
DC +
DC +
data
DC DC -
1
2
3
4
5
6
7
8
RJ-45
1
2
3
4
5
6
7
8
RJ-45
1
2
3
4
5
6
7
8
data
data
data
spare
spare
data
spare
spare
Data In
Ethernet
Switch/Hub
For Data-In ports connect the Ethernet cable leading from the Ethernet Switch/Hub to the Data
port. For Data & Power Out ports, connect the Ethernet cable leading to the telephone or other
end device to the corresponding Data & Power port.
Note:
Note:
Be certain to connect correspondingly numbered Data and Data & Power ports.
121
RJ-45
Male Connector
RJ-45
Female Socket
Data
IP
Phone
Connection to
Power over LAN Hub
Power
DC Power
Connector
Before connecting telephones or other end devices to the 1152A1 PDU, determine if:
Its power requirements are consistent with the 1152A1 PDU voltage and power ratings.
See Appendix B in the users guide that comes with the unit for voltage and power ratings.
Number of
Ports
SNMP
Summary
1152B48S
48
Yes
1152B24S
24
Yes
1152B06
No
1152B06S
No
123
The 1152B PDU complies with the Underwriters Laboratories Inc. (UL) standard UL 60950-1,
1st Edition.
Table 22: 1152B PDU UL 1950 Compliance
Complies
UL 1950
Approved
CAN/CSA-C22.2 No.
60950-1-03Std.
Approved
CE Regulatory
Compliance
Approved
EN 60950
Approved
TUV EN 60950
This product can be hazardous if immersed in water. To avoid the possibility of electrical
shock, do not use it near water.
The 1152B PDU contains components sensitive to electrostatic discharge. Do not touch
the circuit boards unless instructed to do so.
This product should be operated only from the type of AC (and optional DC) power source
indicated on the label. If you are not sure of the type of AC power being provided, contact
a qualified service person.
Do not allow anything to rest on the power cord. Do not locate this product where the cord
will be abused by persons walking on it.
Do not overload wall outlets and extension cords as this can result in the risk of line or
electric shock.
Disconnect the cords on this product and refer servicing to qualified service personnel
under the following conditions:
- The power supply cord or plug is damaged or frayed
- Liquid has been spilled into it
- Exposed to rain or water
Data &
Power
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PWR
communication
1152B1 Power
Distribution Unit
AC
Data
Console
48Vdc
Use a standard CAT5, CAT6 or CAT6e straight-through Ethernet cable (not supplied), including
all 8 wires (4 pairs) as shown in Connecting cables to telephones and other end devices on
page 126.
125
Figure 57: Connecting telephones and other end devices to the 1152B PDU
1
2
3
4
5
6
7
8
End Device
data
data
data
DC +
DC +
data
DC DC -
1
2
3
4
5
6
7
8
RJ-45
1
2
3
4
5
6
7
8
RJ-45
1
2
3
4
5
6
7
8
data
data
data
spare
spare
data
spare
spare
Data In
Ethernet
Switch/Hub
For Data-In ports connect the Ethernet cable leading from the Ethernet Switch/Hub to the Data
port. For Data & Power Out ports connect the Ethernet cable leading to the telephone or other
end device to the corresponding Data & Power port.
Note:
Note:
Be certain to connect correspondingly numbered Data and Data & Power ports.
RJ-45
Male Connector
RJ-45
Female Socket
Data
IP
Phone
Connection to
Power over LAN Hub
Power
DC Power
Connector
Before connecting telephones or other end devices to the 1152B PDU, determine if the device:
Power requirements are consistent with the 1152B PDU voltage and power ratings.
Refer to Appendix B in the users guide that comes with the unit for voltage and power
ratings.
127
C363T-PWR
C364T
C364T-PWR
The C360 converged stackable switches comply with the Underwriters Laboratories Inc. (UL)
standard UL 60950.
Complies
UL 60950
Approved
Approved
CE Regulatory
Compliance
For safety instructions, see C360 switch important safety instructions on page 128. For
installation instructions, see Connecting the C360 stackable switches on page 130.
This product can be hazardous if immersed in water. To avoid the possibility of electrical
shock, do not use it near water.
The Avaya C360 switches and modules contain components sensitive to electrostatic
discharge. Do not touch the circuit boards unless instructed to do so.
This product should be operated only from the type of AC (and optional DC) power source
indicated on the label. If you are not sure of the type of AC power being provided, contact
a qualified service person.
Do not allow anything to rest on the power cord. Do not locate this product where the cord
will be abused by persons walking on it.
Do not overload wall outlets and extension cords as this can result in the risk of line or
electric shock.
Disconnect the cords on this product and refer servicing to qualified service personnel
under the following conditions:
129
Note:
To provide more than 200 watts for the power over Ethernet ports
Note:
Please see the Avaya C360 Manager User Guide and the Quick Start for
Hardware Installation Avaya C360 Converged Stackable Switches (03-300148)
for more information.
!
WARNING:
WARNING:
The conductors to be used for connecting the BUPS to the C360 must be UL
Recognized and CSA Certified and be a minimum of 16 AWG or have a
cross-sectional area of 1.0 mm2.
2. Connect the power cable to the terminals on the C360 and then external DC power supply.
!
WARNING:
WARNING:
Make sure that you connect the cables between the C360 and the external power
supply correctly.
3. Replace the plastic cover by aligning the holes with the screw receptacles and replacing the
two Phillips screws.
Note:
Note:
Use standard RJ45 connections and a CAT5 cable for 100 megabits per second
operation.
2. Connect the other end of the cable to the Ethernet port of the PC, server, router,
workstation, IP telephone, switch, or hub.
3. Check that the appropriate link (LNK) LEDs light up.
UL 60950
Certified
CSA C22.2
Approved
EN
Approved
CE Regulatory Compliance
For safety instructions, see Important safety instructions for 1151B1 and 1151B2 Power
Supplies on page 132. For installation instructions, see Connecting the 1151B1 or 1151B2
Power Supplies on page 133.
131
This product can be hazardous if immersed in water. To avoid the possibility of electrical
shock, do not use it near water.
To reduce the risk of electric shock, do not disassemble this product except to replace the
battery.
This product should be operated only from the type of AC power source indicated on the
label. If you are not sure of the type of AC power being provided, contact a qualified
service person.
Do not allow anything to rest on the power cord. Do not locate this product where the cord
will be abused by persons walking on it.
Do not overload wall outlets and extension cords as this can result in the risk of line or
electric shock.
Disconnect the cords on this product and refer servicing to qualified service personnel
under the following conditions:
If the product does not operate normally by following the operating instructions.
! CAUTION:
CAUTION:
The power supply can be used only with telecommunications equipment, indoors,
and in a controlled environment.
The power supply has a single output of -48 VDC, 0.4 amperes and can operate from either a
120 VAC 60 hertz power source (105 to 129 VAC) or a 220/230/240 VAC 50 hertz power source
(198 to 264 VAC). Input voltage selection is automatic. The output capacity is 19.2 watts.
The power supply can be placed on a flat surface such as a desk. For wall-mounting, keyhole
slots are provided on the bottom of the chassis.
! CAUTION:
CAUTION:
Do not locate the unit within 6 inches (15 centimeters) of the floor.
133
test the IP server interfaces, expansion interfaces, and TDM buses in the port networks.
See LED indicators on page 147 for information regarding the LED status indicators for the
Avaya Ethernet switch(es), uninterruptible power supplies (UPSs), and different circuit packs.
Note:
Note:
Circuit pack positions are usually given by cabinet, and slot. They may also be
given by port. The term cabinet refers to five G650 Media Gateways
TDM-cabled together in a rack, making up one port network. A port network is
defined as a group of media gateways connected together with one TDM bus.
! CAUTION:
CAUTION:
135
Service State
TDM Bus A
in
TDM Bus B
in
Tone/Clock
in
PKT
in
Figure 60: Sample port network status screen for Cabinet 1Avaya S8500
status port-network 1
PORT NETWORK STATUS
Major Minor Warning Carrier
PN Control
PN Alarms Alarms Alarms Locs
Active
Standby
FIBERLINK
1
1
TDM Service
Bus State
A
B
195
Control
Channel
in
in
up
up
Dedicated
Tones
y
n
PKT
01A
01B
TONE/
CLOCK
n
y
01B
01A
Service
State
Major
Alarms
Minor
Alarms
in
Endpoints
Mode
Service
State
in
in
System
Clock
System
Tones
standby
active
standby
active
Bus
Open Bus
Faults Leads
0
Command:
137
Figure 61: Sample system configuration screen Page 4, Avaya S8700 Multi-Connect
list configuration all
Page
SYSTEM CONFIGURATION
Board
Number
Board Type
Code
01B01
01B02
01B03
IP SERVER INTFC
EXPANSION INTRFC
DS1 INTERFACE
01B05
DS1 INTERFACE
01B06
DS1 INTERFACE
Vintage
Assigned Ports
u=unassigned t=tti p=psa
03 04 05 06 07 08
03
11
19
27
03
11
19
27
03
11
19
27
04
12
20
28
04
12
20
28
04
12
20
28
05
13
21
29
05
13
21
29
05
13
21
29
06
14
22
30
06
14
22
30
06
14
22
30
07
15
23
31
07
15
23
31
07
15
23
u
08
16
24
u
08
16
24
u
08
16
24
u
Figure 62: Sample IPSI 01A test results screen Page 1, Avaya S8700 Multi-Connect
test ipserver-interface 1a
Page
TEST RESULTS
Port
Maintenance Name
01A
01A
01A0201
01A0201
01A0202
01A0202
01A0203
01A0203
01A0204
01A0204
01A0205
01A0205
01A0206
01A0206
01A0207
TONE-BD
TONE-BD
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
ETR-PT
46
52
42
43
42
43
42
43
42
43
42
43
42
43
42
Error Code
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
Note:
Note:
Labels on the port network and on the strip under the circuit pack contain this
information.
2. Verify the screen displays test results similar to Figure 63: Sample test results for
Expansion Interface Board 2A01 on page 140. This example is for board 2a01.
3. If any result is FAIL, check the connections for the fiber optic link.
4. Repeat Steps 1 and 2 for each Expansion Interface circuit pack.
139
Figure 63: Sample test results for Expansion Interface Board 2A01
TEST RESULTS
Port
Maintenance Name
02A01
02A01
02A01
02A01
02A01
02A01
EXP-INTF
EXP-INTF
EXP-INTF
EXP-INTF
EXP-INTF
EXP-INTF
Error Code
PASS
PASS
PASS
PASS
PASS
PASS
Maintenance Name
PN
PN
PN
PN
PN
PN
TDM-BUS
TDM-BUS
TDM-BUS
TDM-BUS
TDM-BUS
TDM-BUS
01A
01A
01A
01B
01B
01B
PASS
PASS
ABORT
PASS
ABORT
PASS
Error Code
1005
1005
Minor Warning
Alarms Alarms
1
19
Carrier
PNC Status
Locs
Active Standby
01A
up
2
01B
1
01C
01D
Service
PKT State
1
in
Major
Alarms
n
TONE/
CLOCK
01A
01B
Minor
Alarms
n
ATM
PNC
Conn Endpoints
Mode
A-PNC 01D01-AT02A
active
A-PNC 01C01-AT01A active
Service System
System
State
Clock
Tones
in
standby standby
in
active active
Bus
Faults
0
Open Bus
Leads
0
141
Figure 66: Sample of port network status after expansion link is set
status port-network
PORT NETWORK STATUS
Major Minor Warning Carrier
PN Control
PN Alarms Alarms Alarms Locs
Active
Standby
FIBERLINK
1
1
TDM Service
Bus State
A
B
220
Control
Channel
in
in
up
up
Dedicated
Tones
y
n
PKT
01A
01B
TONE/
CLOCK
n
y
Service
State
Major
Alarms
Minor
Alarms
in
Mode
Service
State
01B
01A
Endpoints
in
in
System
Clock
System
Tones
standby
active
standby
active
Bus
Open Bus
Faults Leads
0
Command:
Type save translations and press Enter to save the translations to the hard drive.
Note:
Note:
Releasing the buttons returns the console to normal mode.
2. Verify all lamps on display light and remain lighted.
Each row of lamps on the console lights and goes dark in sequence from top to bottom.
3. Press Start and listen for dial tone.
The green lamp associated with Idle Call Appearance lights up.
The Position Available lamp goes dark.
4. Dial a number associated with a working telephone.
Audible ringing tone is heard in ear piece.
5. Press Release.
Audible ringing tone is silenced. The green lamp associated with idle call appearance
button goes dark. The Position Available lamp lights.
143
Record an announcement
To record an announcement:
1. Select a test telephone with console permissions enabled.
2. Dial the access code followed by the integrated announcement extension number.
3. When you hear a dial tone, press 1. When you hear a beep or stutter tone, speak the
announcement into the telephone.
4. When done, press # if a digital phone or hang up if an analog phone to stop the recording.
You then hear a dial tone.
Playback announcement
To play back an announcement:
1. If using a digital phone, press 2 to hear the announcement. When the announcement is
over, you hear a dial tone. If satisfied, hang up.
2. If using an analog phone, dial the integrated announcement extension number to hear the
announcement.
When the announcement is over, you hear a dial tone. If satisfied, hang up.
Delete announcement
To delete an announcement:
1. Dial the access code followed by the integrated announcement extension number.
2. When you hear a dial tone, press 3 to delete the announcement and end the recording
session.
A confirmation tone is heard when the announcement is deleted.
Testing music-on-hold
Verify music is provided to a held party during any hold interval.
145
Test features
Test type
100
Test Type
102
Test Type
105
LED indicators
LED indicators
See the maintenance book for your system for detailed alarm and LED descriptions. If a
maintenance object begins to fail some periodic tests, the server will generate an alarm. The
server identifies three levels of alarms:
Major Alarms Failures that cause critical degradation of service and require immediate
attention.
Minor Alarms Failures that cause some degradation of service, but do not cause a
critical portion of the configuration to be inoperable. This condition requires action, but its
consequences are not immediate. Problems might be impaired service to a few trunks or
stations or interfering with one feature across the entire configuration.
Alarms are communicated to users and technicians by entries in the alarm and sys logs and the
lighting of LEDs located on the attendant console, on all circuit packs, and, optionally, on
customer-designated telephones.
More detailed information is available here for:
147
LED indicators
Figure notes:
1. Alarm LED (Red)
2. Test LED (Green)
3. Busy LED (Yellow)
4. STATUS LEDs
5. SPAN LEDs
The yellow LED indicates the state of the fiber interface, the fiber channel, the control channel,
and the communications link to the SPE in the following manner and order of priority. See
Table 23: DS1 Converter yellow LED flashing states.
.
LED off
Condition
0.1
second
0.1 second
0.5
second
0.5 second
1 second
1 second
2 seconds
0.2 second
149
LED off
solid on
Condition
DS1 Converter active. This is the normal state for an active DS1
Converter.
solid off
SPAN LEDs
The four SPAN LEDs indicate the status of the four T1/E1 facilities. A SPAN LED is in one of the
following states:
Blinking yellow for 2 seconds, off 0.1 seconds: Facility is operational and alarm free AND is
carrying the control channel (facility A or B only).
Index
Index
Numerical
110A-type terminal blocks (G650) . . . . . . . . . . 19
110P-type terminal blocks, frame-mounting . . . . . 24
110-type hardware . . . . . . . . . . . . . . . . . 17
110-type hardware, SCP-110 sneak current protection 54
110-type terminal blocks . . . . . . . . . . . . . . 19
110-type terminal blocks, wall-mounting . . . . . . . 21
1110A2 apparatus mounting frame . . . . . . . . . 24
1110C1 cable support . . . . . . . . . . . . . . . 24
1145B power supply . . . . . . . . . . . 109, 110, 114
1145B power supply, mounting . . . . . . . . . . . 111
1146B power distribution unit . . . . . . . . . .114, 117
1146B power supply, mounting . . . . . . . . . . . 111
1151B1 and 1151B2 power supply . . . . . . 132, 133
1151B1 power supply . . . . . . . . . . . . . . . 131
1151B2 power supply . . . . . . . . . . . . . . . 131
1152A1 power distribution unit . . . . . . . . . . . 119
connecting . . . . . . . . . . . . . . . . . . . 120
connecting cables . . . . . . . . . . . . . . . 121
258A adapter . . . . . . . . . . . . . . . . . . . 43
26B1 selector console . . . . . . . . . . . . . . 87, 88
2-wire and 4-wire endpoints, dual wiring . . . . . . . 87
2-wire digital station wiring . . . . . . . . . . . . . 75
302D attendant console . . . . . . . . . . . . . . 87
356A adapter . . . . . . . . . . . . . . . . . . . 43
3-pair and 4-pair modularity. . . . . . . . . . . . . 84
3-pair modularity . . . . . . . . . . . . . . . . . . 67
3-pair to 4-pair station circuits . . . . . . . . . . . . 44
3-pair trunks, cabling . . . . . . . . . . . . . . . . 38
451A extension adapter . . . . . . . . . . . . . . 42
4C3S-75 enhanced protector . . . . . . . . . . . . 94
4C3S-75 enhanced protector, installing . . . . . . . 95
4-pair station circuits . . . . . . . . . . . . . . . . 44
808A emergency transfer panel . . . . . . . . . . 96, 99
808A emergency transfer panel examples . . . . . . 97
A
adapter
258A, 356A, BR2580A, ZD8AJ . .
451A extender . . . . . . . . . .
adjunct power . . . . . . . . . . . .
connecting . . . . . . . . . . . .
connection locations . . . . . . .
administering patch cords and jumpers
alarms . . . . . . . . . . . . . . .
connections . . . . . . . . . . .
terminal alarm notification . . . . .
wiring . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 43
. 42
. 73
. 74
. 85
. 62
. 147
. 88
. 148
. 75
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
145
145
145
144
. 86
. 86
. 87
147, 148
. . . 73
. . 143
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
93
75
91
76
39
81
86
88
86
B
back-up battery . .
battery
back-up . . . .
mounting . . .
BR2580A adapter
. . . . . . . . . . . . . . . . . 115
. . . . . . . . . . . . . . . . . 114
. . . . . . . . . . . . . . . . . 115
. . . . . . . . . . . . . . . . . 43
C
C360 converged stackable switches . .
C360 switch
connecting . . . . . . . . . . . .
safety instructions . . . . . . . . .
using the C360 switch . . . . . . .
cabinet
cable clamps . . . . . . . . . . .
cabling to MDF . . . . . . . . . .
cable clamps . . . . . . . . . . . . .
cable clamps, for cable slack manager .
cable routing guidelines . . . . . . . .
cable routing, MDF . . . . . . . . . .
cable slack manager . . . . . . . . .
cable slack manager, installing . . . .
cables
25-pair I/O . . . . . . . . . . . .
attendant console cabling distances
installing . . . . . . . . . . . . .
. . . . . . 128
. . . . . . 130
. . . . . . 128
. . . . . . 129
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
13
38
25
13
36
36
13
25
. . . . . 13, 25
. . . . . . . 86
. . . . . . . 33
.
.
.
.
151
Index
installing between cabinet and MDF . . . . . . . 38
outputs for control carrier . . . . . . . . . . . . 81
cables, installing between auxiliary cabinet and MDF . 39
cabling
installing trunk cables . . . . . . . . . . . . . . 38
labels . . . . . . . . . . . . . . . . . . . . . 33
provisioning plan . . . . . . . . . . . . . . . . 52
cabling layout . . . . . . . . . . . . . . . . . . . 13
calling queue . . . . . . . . . . . . . . . . . . . 107
carbon block protectors
off-premises connections . . . . . . . . . . . . 93
checking
circuit pack configuration . . . . . . . . . . . . 137
system status. . . . . . . . . . . . . . . . . . 136
circuit packs
configuration, testing . . . . . . . . . . . . . . 137
DS1 converter LEDs . . . . . . . . . . . . . . 148
duplication interface LEDs . . . . . . . . . . . . 148
LEDs . . . . . . . . . . . . . . . . . . . . . 147
C-LAN connection, testing . . . . . . . . . . . . . 147
closets
site locations . . . . . . . . . . . . . . . . . . 41
CO trunk wiring . . . . . . . . . . . . . . . . . . 75
collocated DS1 tie trunks, wiring . . . . . . . . . . 78
concentrator cables, connecting trunk pairs . . . . . 65
connect
1151B1 and 1151B2 power supply . . . . . . . . 133
adjunct power . . . . . . . . . . . . . . . . . 74
external alarm indicators . . . . . . . . . . . . 88
connecting
1152A1 power distribution unit . . . . . . . . . . 120
C360 switch . . . . . . . . . . . . . . . . . . 130
connecting control carrier outputs cable . . . . . . . 65
connection diagrams, station cables . . . . . . . . . 44
console
attendant, testing . . . . . . . . . . . . . . . . 143
selector, testing . . . . . . . . . . . . . . . . . 144
control carrier cable labels . . . . . . . . . . . . . 64
control carrier outputs cable . . . . . . . . . . . 65, 81
coupled bonding conductor wires, installing . . . . . 58
critical reliability
testing systems . . . . . . . . . . . . . . . . . 141
cross-connect fields, MDF . . . . . . . . . . . . . 16
D
data link protector, installing . . . . . . . . . .
DC power . . . . . . . . . . . . . . . . . . .
DID trunk wiring . . . . . . . . . . . . . . . .
digital line circuit protectors . . . . . . . . . . .
digital tie trunk wiring . . . . . . . . . . . . . .
direct department calling
testing queue warning indicator . . . . . . .
downloading this book and updates from the Web
DS1 converter
.
.
.
.
.
.
.
.
.
.
95
58
75
94
77
. . 144
. . 10
E
emergency transfer panel, installing . . .
emergency transfer telephones . . . . .
emergency transfer units . . . . . . . .
emergency transfer, testing . . . . . . .
equipment room
cable routing . . . . . . . . . . . .
cabling labels . . . . . . . . . . . .
station circuit distribution from . . . .
expanded power distribution unit . . . .
expansion interface circuit packs, testing .
expansion interface exchange, testing . .
expansion links, service state . . . . . .
external alarm indicators, connecting . .
external alarm wiring . . . . . . . . . .
external ringing
installing . . . . . . . . . . . . . .
testing . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
. . . 99
104, 105
. . . 96
. . 145
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 36
. 33
. 44
. 115
139
141
136
. 88
. 75
. . . . . 106
. . . . . 144
F
floor plans . . . . . . . . . . . . . . . . . . . . . 13
G
G650 Media Gateway
110A-type terminal blocks . . . . . . . . . . . . 19
cross connecting to MDF. . . . . . . . . . . . . 29
H
hardware
MDF . . . . . . . . . . . . . . . . . . . . . . 17
hard-wire bridging . . . . . . . . . . . . . . . . . 87
I
I/O cables . . . . . . . . . . . . . . . . .
information outlets, wiring design . . . . . .
installing
26B1 Selector Console . . . . . . . . .
4C3S-75 enhanced protector . . . . . . .
808A emergency transfer panel . . . . .
attendant console . . . . . . . . . . . .
cable slack manager . . . . . . . . . . .
cables . . . . . . . . . . . . . . . . .
cables between auxiliary cabinet and MDF
cables between cabinet and MDF . . . .
coupled bonding conductor wires . . . . .
.
.
.
.
. . . . 25
. . . . 41
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
88
95
99
87
25
33
39
38
58
Index
coupled bonding conductors . . . . . .
data link protector . . . . . . . . . . .
external ringing . . . . . . . . . . . .
ITW Linx enhanced protector . . . . .
MDF . . . . . . . . . . . . . . . . .
MDFMain Distribution Frame. See MDF
patch cords and jumpers . . . . . . .
patch panels . . . . . . . . . . . . .
sneak fuse panels . . . . . . . . . .
telephone power supplies
procedures . . . . . . . . . . . .
telephones used for emergency transfer
trunk cables . . . . . . . . . . . . .
integrated announcement
testing . . . . . . . . . . . . . . . .
IP network connection, testing . . . . . .
ITW Linx enhanced protector . . . . . . .
ITW Linx enhanced protector, installing . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 58
. 95
. 106
. 95
. 19
. . . . . 62
. . . . . 29
. . . . 54, 57
. . . . . 109
. . 104, 105
. . . . . 38
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 144
. 147
. 94
. 95
J
jumper wires, connecting trunk pairs . . . . . . . . 67
jumpers, installing and administering . . . . . . . . 62
L
labels
equipment room cabling . . . . .
MDF . . . . . . . . . . . . . .
labels, control carrier cable . . . . .
lead designations
port circuit packs and telephones
LEDs
alarms . . . . . . . . . . . . .
attendant consoles . . . . . . .
DS1 converter circuit packs . . .
power distribution unit . . . . . .
T1/E1 status . . . . . . . . . .
light emitting diodes. See LEDs.
locating the MDF . . . . . . . . . .
. . . . . . . . 33
. . . . . . . . 20
. . . . . . . . 64
. . . . . . . 76, 83
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 147
. 148
. 148
. 118
. 150
. . . . . . . . 19
M
MDF
cabling . . . . . . . . . . . . .
cabling to auxiliary cabinet . . .
cabling to cabinet . . . . . . . .
connections . . . . . . . . . .
cross connecting media gateway
cross-connect fields . . . . . . .
emergency transfer connections .
emergency transfer unit . . . . .
hardware . . . . . . . . . . . .
installation . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
33
39
38
17
29
16
99
96
17
17
labels . . . . . . . . . . .
location . . . . . . . . . .
off-premises connections .
media gateway
cross connecting to MDF. .
media gateway installation
coupled bonding conductors
modularity
3-pair and 4-pair. . . . . .
mounting terminal blocks . . .
music-on-hold, testing . . . .
. . . . . . . . . . . 20
. . . . . . . . . . . 19
. . . . . . . . . 90, 91
. . . . . . . . . . . 29
. . . . . . . . . . . 58
. . . . . . . . . . . 84
. . . . . . . . . 21, 24
. . . . . . . . . . 145
N
night ringing, testing . . . . . . . . . . . . . . . 144
O
off premise protection . . . . .
off-premises
connections . . . . . . . .
digital line circuit protectors
protection . . . . . . . . .
station wiring . . . . . . .
stations . . . . . . . . . .
out-of-building connections . .
out-of-building stations . . . .
outputs cable for control carrier
. . . . . . . . . . . 54
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. . 91
. . 94
93, 94
. . 90
. . 91
. . 91
. . 91
. . 81
P
patch cords, installing and administering .
patch panels
installing . . . . . . . . . . . . . .
pin designations
port circuit packs and telephones . . .
playback announcement, testing . . . . .
Port Assignment Record form . . . . . .
port circuit pack pin designations . . . .
port network
expansion interface exchange, testing
TDM bus, testing . . . . . . . . . .
power distribution unit . . . . . . . . . .
power supplies for telephones
1151B1 -48V . . . . . . . . . . . .
1151B2 -48V . . . . . . . . . . . .
installing and wiring . . . . . . . . .
testing . . . . . . . . . . . . . . .
primary protectors
off-premises
connections . . . . . . . . . . .
off-premises connections . . . . . .
provisioning plan . . . . . . . . . . . .
. . . . . . 62
. . . . . . 29
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
76, 83
. 145
. . 62
76, 83
. . . . . 141
. . . . . 140
. . . . . . 118
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. . . . . . 93
. . . . . . 94
. . . . . . 52
131
131
109
. 116
153
Index
Q
queue warning indicator . . . . . . . . . . . . . . 107
testing . . . . . . . . . . . . . . . . . . . . . 144
R
recorded announcement, testing . . . . . . . . . . 145
ringing, testing . . . . . . . . . . . . . . . . . . . 144
routing cables to MDF . . . . . . . . . . . . . . . 36
S
safety instructions
1145B power supply . . . . . . .
1151B1 and 1151B2 power supply .
selector console . . . . . . . . . . .
selector console, testing . . . . . . .
service states, checking . . . . . . .
site locations, adapters . . . . . . . .
sneak current
fuse panels . . . . . . . . . . . .
fuses. . . . . . . . . . . . . . .
sneak current protection . . . . . . .
sneak current protection, installing . .
sneak current protectors
off-premises connections . . . . .
sneak fuse panels . . . . . . . . . .
sneak fuse panels, installing . . . . .
sneak fuse, connector pinout . . . . .
space requirements
110-type hardware . . . . . . . .
cable slack manager . . . . . . .
sneak fuse panels . . . . . . . .
SPAN LEDs . . . . . . . . . . . . .
station cables
sizing . . . . . . . . . . . . . .
wiring design . . . . . . . . . . .
station circuit distribution . . . . . . .
system status, checking . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 110
. 132
. 88
. 144
. 136
. 41
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 93, 94
. 13, 54
. . 57
. . 54
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 13
. 13
. 13
. 150
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 13
. 41
. 44
. 136
54
54
54
57
T
T1 CSU, and DS1 tie trunk . . .
T1/E1 status LEDs . . . . . . .
TDM bus
service state . . . . . . . .
testing . . . . . . . . . . .
telephone calls
making test calls . . . . . .
telephone installation examples .
telephone pin designations . . .
telephones
connecting . . . . . . . . .
. . . . . . . . . . 78
. . . . . . . . . . 150
. . . . . . . . . . 136
. . . . . . . . . . 140
. . . . . . . . . . 143
. . . . . . . . . . 97
. . . . . . . . . 76, 83
. . . . . . . . . . 73
emergency transfer . . . . . . . . .
terminal alarm notification
alarms . . . . . . . . . . . . . . .
terminal blocks
frame-mounting . . . . . . . . . . .
wall-mounting . . . . . . . . . . . .
terminals,connecting . . . . . . . . . .
terminating trunk transmission test types .
terminating trunk transmission testing . .
test types, terminating trunk transmission
testing
1145B2 power supply . . . . . . . .
complete configuration . . . . . . . .
emergency transfer . . . . . . . . .
expansion interface circuit packs . . .
expansion interface exchange . . . .
external ringing . . . . . . . . . . .
integrated announcements . . . . . .
IP network connection . . . . . . . .
music on hold . . . . . . . . . . . .
night ringing . . . . . . . . . . . . .
playback announcement . . . . . . .
queue warning indicator . . . . . . .
selector console . . . . . . . . . . .
TDM bus . . . . . . . . . . . . . .
terminating trunk transmission . . . .
TN2312AP/BP . . . . . . . . . . .
tie trunk
analog wiring . . . . . . . . . . . .
digital wiring. . . . . . . . . . . . .
TN2312AP/BP
testing . . . . . . . . . . . . . . .
TN799DP C-LAN circuit pack . . . . . .
tone clocks
service state . . . . . . . . . . . .
trunk cables, installing . . . . . . . . .
trunk pairs
connecting with concentrator cables .
connecting with jumper wires . . . . .
. . . . . 148
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 24
. 21
. 44
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 116
146
146
146
135
145
139
141
144
144
147
145
144
145
144
144
140
146
138
. . . . . . 76
. . . . . . 77
. . . . . 138
. . . . . 147
. . . . . 136
. . . . . . 38
. . . . . . 65
. . . . . . 67
U
uniform call distribution
testing queue warning indicator. . . . . . . . . 144
using this documentation . . . . . . . . . . . . . . . 9
V
voice terminals, exposed environments . . . . . . . 94
W
wall-mounting plates . . . . . . . . . . . . . . . . 114
wiring
. . . 104, 105
Index
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
117
75
75
75
76
115
75
75
77
78
90
69
73
. . . . . . . . . . 109
Z
ZD8AJ adapter . . . . . . . . . . . . . . . . . . 43
155
Index