You are on page 1of 2

200 kA clamps

For classes of LPS I and II

The new 200 kA clamps from DEHN meet high requirements.


According to the IEC 62561-x standard series, connection components must meet certain mechanical and electrical requirements. In
tests according to IEC 62561-1, they are subjected to ageing and an
electrical test with three lightning current impulses of 10/350 s
wave form each*. Depending on the lightning current carrying
capability, a distinction is made between

Class N: 50 kA (normal duty) and

Class H: 100 kA (high duty).

DEHN offers connection components with a lightning


current carrying capability of 200 kA (10/350 s) based
on the IEC 62561-1 standard*.

Connection components tested according to this standard can be


used for class III/VI lightning protection systems and if the lightning
current is distributed in a meshed lightning protection system.
In case of class I/II lightning protection systems, the lightning current
is poorly distributed or not distributed at all if air-termination rods are
connected to existing mesh systems. If an air-termination rod is connected to a mesh/roof parapet by means of a single conductor, 100%
connection components. The case is similar for HVIConductors or
HVIpower Conductors without current distribution used for class
I/II lightning protection systems. When conducting the lightning
current from the high-voltage-resistant, insulated down conductor to
the existing lightning protection system, the clamps/connectors are
exposed to 100% of the lightning current. This would be 150 kA in
case of a class II lightning protection system and 200 kA in case of a
class I lightning protection system.

** DIN EN 62305-3 Bbl2 (VDE 0185-305-3 Bbl 2):2012-10 Protection against lightning
Part 3: Physical damage to structures and life hazard
Supplement 2: Additional information for special structures

The 200 kA imprint is characteristic of the new components.

Ex zone 2/22**. The manufacturers test reports and installation


instructions for the individual components are available at
www.dehn-international.com.

www.dehn-international.com

200 kA clamps
For classes of LPS I and II

The components are tested with a lightning current


of 200 kA (10/350 s) based on the IEC 62561-1 standard.
UNI disconnecting clamp

Disconnecting clamp

Allows two round wires to be connected.

Allows HVIpower Conductors/round conductors to be connected with the earth entry.

Technical data

Part No. 459 200

Clamp material
Clamping range Fl / Fl
Packing unit

Part No. 459 219

Material

Stainless steel

10 / 10 mm

Clamping range Rd / Rd

8-10 / 16 mm

10 / 30 mm

Packing unit

Stainless steel

Clamping range Rd / Rd

Technical data

1 piece

1 piece

Clamping piece

KS connector
Allows connection to building elements.

connected with an isolated air-termination


system and can also be used for connection to
other structural parts (M10 screws).

Technical data
Technical data

Part No. 380 209

Material

Stainless steel

Clamping range Fl

30 x 4 mm

Packing unit

Part No. 301 209

Material

Stainless steel

Clamping range Rd

10 mm

Packing unit

1 piece

1 piece

MV clamp

Disconnecting clamp

Allows two round wires to be connected.

Allows HVIpower Conductors to be connected with the earth entry and the air-termination rod with round wires.

Technical data

Part No. 390 209

Material

Stainless steel

Clamping range Rd / Rd
Packing unit

8-10 mm
1 piece

Technical data

Stainless steel

Clamping range Rd/Rd

8-10 / 16 mm

Packing unit

Manufacturers test report available


DEHN, DEHN logo and DEHN schtzt are protected by German Trademark and / or are registered trademarks in other
DS244/E/1114

Copyright 2014 DEHN + SHNE

Part No. 392 209

Material

1 piece

DEHN + SHNE
GmbH + Co.KG.
Tel.: +49 9181 906-0
info@dehn.de

www.dehn-international.com

You might also like