Cutler-Hammer

October 1998

CAT.73.01.T.E

Type BR Loadcenters
Index

C-1

Page

Page

Loadcenter Selection Chart . . . . . . . . .C-2


Product Styles . . . . . . . . . . . . . . . . . . . .C-3
Catalog Numbering System. . . . . . . . .C-4
Applications and Warranties . . . . . . . .C-5
1-Phase Main Circuit Breakers . C-6 C-7
1-Phase Main Lugs . . . . . . . . . . . C-8 C-9
3-Phase Main Circuit Breakers . . . . .C-10
3-Phase Main Lugs . . . . . . . . . . . . . . .C-11
Convertible Base Units and
Main Devices . . . . . . . . . C-12 C-13
New York City Indoor . . . . . . . . . . . .C-14

1- and 3-Phase Circuit Breaker


Unit Enclosures . . . . . . . . . . . . . . .C-15
Loadcenter Accessories . . . . . . . . . . .C-16
Surge Protectors . . . . . . . . . . . . . . . . .C-17
Plug-On Circuit Breakers . . . . C-18 C-23
Circuit Breaker Accessories . . . . . . . .C-24
Loadcenter and Unit Enclosure
Box Dimensions . . . . . . . . . . . . . .C-25
Knockout Congurations
and Dimensions. . . . . . . . . C-26 C-27
Wiring Diagrams. . . . . . . . . . . C-28 C-36
Typical Specications. . . . . . . C-37 C-38

C-2

Cutler-Hammer

Type BR Loadcenters
Selection Chart

October 1998

Loadcenter Selection Chart


Service

Single-phase, three-wire, 120/240V AC

Short Circuit Current Rating

Main Breaker/Main Lug


Loadcenters

Convertible Loadcenters

Three-phase, four-wire, 208Y/120V AC


Three-phase, three-wire, 240V AC delta

10,000 AIC: All single- and three-phase


loadcenters 70 through 225 amperes,
8 to 42 circuits.
22,000 AIC: All convertible loadcenters
using 125 amperes rated Type BRH main
breakers or selected factory installed 125
ampere rated Type BRH main breaker.

Single-Phase

Three-Phase

Main Breaker: 100, 125, 150, 200, 225,


400, 600 amperes.
Main Lugs: 70, 125, 150, 200, 225, 400,
600 amperes.

25,000 AIC: All convertible and factory


installed single-phase loadcenters
rated 150 and 200 amperes using
Type BWH main breakers.

Main Breaker: 100, 125, 150, 200, 225,


400, 600 amperes.
Main Lugs: 100, 125, 150, 200, 225, 400,
600 amperes.

Main Breaker: Single-phase up to 200 amperes and three-phase up to 100 amperes


Main Lugs: Single-phase up to 200 amperes and three-phase up to 125 amperes

Branch Breakers

Types BR, BRH, and BRH: 10 to 125


amperes. One-, two-, and three-pole.
Selected amperages available in
switching duty, HACR, shunt trip,
and high magnetic setting.
Type GFCB: 15 to 50 amperes.
One- and two-pole ground fault breakers.
Types BJ, and BJH: 125 to 225 amperes
Two- and three-pole.
Type BD Twin: 10 to 50 amperes
Two of one-pole. Take one 1-inch
(25.4 mm) space.

Enclosures

Meets or exceeds UL requirements for


indoor or outdoor applications

Loadcenter and Breaker Accessories

Bussing

NEMA Type 1 indoor.


NEMA Type 3R outdoor.

Branch Circuit Breaker


Auxiliary components.
Hold Down Kits.
Handle ties.
Lockoffs.
Lockdogs.
Complete Line of Ground Bar Kits
5, 10, 14, and 21 circuit, some with
additional #2/0 lugs. Each terminal will
accommodate: (3) #14-#10 Cu/Al or
(1) #14-#4 Cu/Al
Main and Sub-feed Lugs
125, 150, 225 amperes two- and
three-pole.
Shunt Trips

Type BQ and BQC Multibreaker: 15 to 30


amperes. Two of two-pole or one twopole and two one-pole. Takes two 1-inch
(25.4 mm) spaces.
Type BRW: 15 to 30 amperes.
Two-pole water heater breakers.
Type BRSN: 15 to 30 amperes.
Two-pole switching neutral breakers.
Type BR 15 to 100 amperes.
Two-pole, 240V AC delta breakers.

Surge Protection
Single-phase plug-on surge protector.
Single-phase bottle type surge protector.
Three-phase bottle type surge protector.
Single-phase whole home surge
protector.
Universal Rainproof Conduit Hubs
Group One: 3/4, 1, 1-1/4, 1-1/2, 2 inches
(19.6, 25.4, 31.8, 38.1,
50.8 mm)
Group Two: 2, 2-1/2, 3 inches
(50.8, 63.5, 76.2 mm)
Adapter plate.

Tin-plated aluminum as standard.


Some copper bus panels available.

CAT.73.01.T.E

Cutler-Hammer
October 1998

Type BR Loadcenters
Product Styles
Convertible

Three-Phase

Single-Phase

Main Circuit Breaker

C-3

Main Circuit Breaker

Circuit Breaker
Unit Enclosures
Outdoor

CAT.73.01.T.E

Main Circuit Breaker


Commercial

Main Circuit Breaker


Commercial

Main Lugs

Main Lugs

C-4

Cutler-Hammer

Type BR Loadcenters
Loadcenter Features - Catalog Numbering System

Extra 1-1/2-inch (38.1 mm)


knockout for bundling of wires

Tangential main
knockout

October 1998

Standard 14-3/8 inches (365.1 mm) wide


enclosures t snugly between wall studs

Same size Allen wrench can be used


for phase and neutral lugs

Drywall marking on enclosure

Commercial grade main breaker


designed for straight-in wiring that
allows for top or bottom feed
Twin neutral design for easier wiring
and balancing of the load, located in
wireway, away from circuit breakers

Factory pre-attached
neutral bonding strap

Predrilled mounting holes for


ease of installing ground bar kits

Maximum wiring gutter space for


ease of wiring in compliance with
NEC requirements

Maximum variety of concentric


knockouts, at rear and sides
One piece roll formed metal backpan
with circuit breaker alignment notches
assures accurately aligned breaker and
bus stabs

Combination trim has sliding latch and


adjustable deadfront for neat, clean
appearance

Six mounting holes (three top,


three bottom) for ease of installation

BR2040B200

Catalog Numbering System


Single- and Three-Phase Through 225 Amperes

BR

30

Phase
Blank = 1-Phase
3
= 3-Phase

42
Maximum
Number
of Poles

Number of 1-inch
(25.4 mm) Spaces

Cutler-Hammer
Type BR Loadcenter

B
L
N
H

=
=
=
=

200

Blank = No Feed
Thru Lugs
F
= Feed Thru
Lugs
G
= Ground
Bar
P
= Current
Design

Bus
Blank = Aluminum Bus
C
= Copper Bus

Main Breaker
Main Lug
Convertible Main
Main Breaker High AIC

__

Amperes
70 = 70 Amperes
100 = 100 Amperes
125 = 125 Amperes
150 = 150 Amperes
200 = 200 Amperes
225 = 225 Amperes

Enclosure
R
= NEMA Type 3R Rainproof
S
= NEMA Type 1 Indoor with
Surface Trim
F
= NEMA Type 1 Indoor with
Flush Trim
Blank = NEMA Type 1 Indoor with
Combination Trim

Single- and Three-Phase 400 Amperes Through 600 Amperes

3
Phase
Blank = 1-Phase
3
= 3-Phase

30
Number of 1-inch
(25.4 mm) Spaces

42
Maximum
Number
of Poles

D
Amperes
D = 400 Amperes
E = 600 Amperes

N
N = Current Design

Enclosure
F = NEMA Type 1 Indoor with Combination Trim
S = NEMA Type 1 Indoor with Surface Trim
R1 = NEMA Type 3R Rainproof

Main
Blank = Main Lug
B
= Main Breaker

Example No. 1: BR1224L125G

Example No. 2: BR24L70RP

Example No. 3: 3B4242EFN

1-Phase Cutler-Hammer Type BR Loadcenter Rated at 125 Amperes with Main


Lugs, 12 Spaces Allowing 24 Poles, Indoor
Combination Enclosure, Aluminum Bus,
and Ground Bar.

1-Phase Cutler-Hammer Type BR Loadcenter Rated at 70 Amperes with Main


Lugs, 2 Spaces Allowing 4 Poles, Rainproof Enclosure with Aluminum Bus.

3-Phase Cutler-Hammer Type BR Loadcenter Rated at 600 Amperes with Main


Breaker, 42 Spaces Allowing 42 Poles,
Indoor Combination Enclosure.

No character space used.

CAT.73.01.T.E

Cutler-Hammer
October 1998

Type BR Loadcenters
Applications and Warranties

C-5

Application Notes and Extended Warranty Highlights


Application Information
Loadcenter Construction

Grounds

Cutler-Hammer Type BR loadcenters


have standard tin-plated aluminum bus
with a limited availability of copper bus.
The sum of the handle ratings connected
to any stab is limited to 150 amperes
maximum on the 100 and 125 ampere
loadcenters, and 200 amperes on loadcenters with 150 ampere or higher main
bus. NEMA Type 1 boxes or enclosures
are manufactured from G60 16-gauge
galvanized steel. Raintight boxes are
manufactured from G60 16-gauge galvanized steel, then nished using an electrostatic powder coat, baked urethane
paint process.

Separate ground bars are supplied on


those loadcenters having a G in the
catalog number. For service entrance
panels not having a separate ground bar,
the extra neutral terminals may be used
for equipment ground conductors. When
using the loadcenter as a sub-feed, the
bonding strap should not be attached,
and a separate ground bar must be
installed.

UL Listings
All Cutler-Hammer Type BR loadcenters
are listed under UL le E52977 except
the 2-8 circuit loadcenters, up through
and including 125 amperes, which are
listed under UL le E8741.
Neutrals
Cutler-Hammer Type BR loadcenters
feature two types of neutrals:
Split Neutrals Single-phase loadcenters 12 circuits and above feature a
twin neutral (mounted on both sides of
the interior assembly) with a cross bus
connecting them unless otherwise
noted. The neutral is bondable in the
eld by means of a bonding strap that is
supplied with each loadcenter. The cross
bus is not removable for separate
ground and neutral bars. For sub-feed
applications, a separate ground bar must
be used. In a service entrance application, where the neutral is bonded,
unused neutral connections may be
used for equipment ground conductors.
Single Neutral Single phase 2-8 circuit,
three-phase and commercial loadcenters
are supplied with a single insulated/
bondable neutral. The three-phase loadcenter neutral is movable to the other
side if desired. The neutral is bondable
in the eld by means of a bonding strap
that is supplied with each loadcenter. For
sub-feed applications, a separate ground
bar must be used. In a service entrance
application, where the neutral is bonded,
unused neutral connections may be
used for equipment ground protectors.

See Cutler-Hammer Publication Number


SA-365 for complete details.

CAT.73.01.T.E

Neutral and Ground Terminals


The standard terminals on grounds and
neutrals are rated to accept (3) #14-#10
Cu/Al or (1) #14-4. For larger cables,
add-on neutral lugs may be ordered
from the accessories on page C-16.
Bottom Fed Loadcenters
Where power cable is brought into the
loadcenter from below the panel, main
lug panels, and single-phase, 225
ampere and below loadcenters can be
rotated 180 degrees to allow straight-in
wiring of power cables to the main terminals. Because the main circuit breaker
handle operates horizontally, the orientation of the main circuit breaker handle
is consistent with the requirements of
NEC Article 240-81.

The date code is in the following format:


F # # # = . The F is the numeric code
for the Lincoln, IL plant, and the three
numbers are the year and week of manufacture e.g. 623. The = sign at the end
signies the decade of the 1990s. Therefore, the date code F623= would indicate
that the product was manufactured in
the 23rd week of 1996. The 1980s are
represented by a + sign at the end of
the code.
Surge Protectors
The BRSURGE Surge Protector has indicating lights that indicate when the units
should be replaced. The CHSA01 and
CHSA03 Surge Protectors internally
short, causing the circuit breaker feeding
the surge protector to trip. All but the
BRSURGE Surge Protector should be
wired to the load side of 15 or 20 ampere
feeder circuit breakers mounted adjacent
to the main incoming device.
The CHSPCH Clipper Home Surge
Protector is an externally mounted TVSS
unit that provides industrial level surge
protection in a residential design.
Circuit Breaker Case Interrupting
Capacity
10,000 AIC Black
22,000 AIC Gray

Gutter Splicing
Loadcenters are not UL listed as wiring
troughs. Therefore, gutter splicing of
riser cables to tap off to the main device
is not permitted.
Fire Rating
Due to the numerous openings in both
loadcenter boxes and trims, they should
not be mounted in rewalls. There is no
approved method for sealing the enclosures for this application.
Date Code
The date of manufacture of each loadcenter is printed on the outside of the
carton as well as inside the loadcenter.
On the carton, the date code is printed
on the end carton label. In the loadcenter, the date code is located on the
small white label located on the right
side wall (with the main device on top).

Extended Residential Warranty


Highlights

Five-year branch breaker warranty.


Five-year loadcenter warranty.
Both the loadcenter and branch circuit
breaker warranties are extended to 10
years if a functioning surge protector
is installed in the loadcenter.

C-6

Cutler-Hammer

Type BR Loadcenters
1-Phase with Main Circuit Breakers

October 1998

1-Phase Main Circuit Breaker Loadcenters


10,000/22,000 Amperes Interrupting Capacity
1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main
Breaker
Type

Main
Ampere
Rating

Maximum
Number
1-inch (25.4 mm)
Spaces

BR
10 kAIC

BW
10 kAIC

Main
Breaker
Type

Enclosure Loadcenter Catalog Number with


Type
Combination OR NEMA Type 3R
Cover

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Breaker

$205.00
247.00
319.00
226.00
319.00
257.00
258.00
363.00
258.00
368.00

B1
A1
B2R
B2
B2R
C1
C1
C1R
C2
C3R

17
65
59
19
17
60
24
24
22
10

#4 - 1/0

BR1624B125
BR2024B125
BR2024B125R

417.00
474.00
545.00

C1
C1
C3R

24
10
10

#4 - 2/0

Outdoor
Indoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor

BR816B150RF
BR1630B150
BR2030B150
BR2030B150R
BR2040B150
BR2040B150R
BR2430B150
BR3030B150
BR3030B150R
BR3040B150

505.00
394.00
467.00
605.00
505.00
605.00
494.00
525.00
670.00
545.00

C3R
C4
C4
D1R
D1
D1R
G1
G1
G1R
G1R

18
25
26
26
29
29
27
28
28
30

#2 - 300 kcmil

8
16
32
40
40
40
40
40
40
40

Outdoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Outdoor

BR48B200RF
BR816B200RF
BR1632B200
BR2040B200
BR2040B200R
BR2440B200
BR3040B200
BR3040B200R
BR4040B200
BR4040B200R

456.00
491.00
422.00
472.00
605.00
496.00
565.00
670.00
660.00
935.00

8R
C3R
C4
D1
D1R
G1
G1
G1R
L1
L1R

46
18
29
29
29
61
30
30
28
28

#2 - 300 kcmil

42
42

Indoor
Outdoor

BR4242B225
BR4242B225R

720.00
985.00

L2
L2R

31
31

#1 - 250 kcmil

8
10
10
12
12
16
16
16
20
20
30

16
20
20
20
24
20
24
24
20
24
30

Indoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Outdoor
Indoor

BR816B100
BR1020B100SP
BR1020B100RF
BR1220B100
BR1224B100R
BR1620B100
BR1624B100
BR1624B100R
BR2020B100
BR2024B100R
See Copper Bus Offering, Page C-13

125

16
20
20

24
24
24

Indoor
Indoor
Outdoor

150

8
16
20
20
20
20
24
30
30
30

16
30
30
30
40
40
30
30
30
40

200

4
8
16
20
20
24
30
30
40
40

225

42
42

Maximum
Number
1-inch (25.4 mm)
Spaces

Box
Size

Poles

100

Main
Ampere
Rating

List
Price

Enclosure Commercial Loadcenter


Type
Catalog Number

Poles

With Flush or
NEMA Type 3R
Cover

DK

300

42

42

Indoor

400

42
42

42
42

Indoor
Outdoor

LA

600

42

42

Indoor

All main circuit breaker loadcenters are


listed for use as service entrance equipment
and are shipped with a neutral bonding strap
preattached. The maximum rating of the
panel is the main circuit breaker rating when
used as service entrance equipment.
Ground bar kits priced separately.
See page C-16.
Refer to page C-25 for dimensions.
Includes through-feed lugs for both phase
and neutral conductors.
Rainproof panels are furnished with hub
closure plates. For rainproof hubs, refer to
page C-16.

List
Price

Box
Size

With
Surface
Cover

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Breaker

BR304242F

BR304242F

$3,375.00

24

36

(2) #3/0 - 250 kcmil

B4242DFN
B4242DR1N

B4242DFN

3,545.00
4,115.00

24
47

36
36

(2) #3/0 - 250 kcmil

B4242EFN

B4242EFN

5,580.00

24

36

(2) #3/0 - 500 kcmil

Type DK main circuit breaker is rated 65,000


AIC at 240V AC and allows a 22,000 AIC
series rating on the panel when Types BR,
BD and BJ branch circuit breakers are used.
Type LA main circuit breaker is rated 42,000
AIC at 240V AC. Type LA circuit breaker is
not series rated with Types BR, BD and BJ
branch circuit breakers.
Supplied with adapter plate to use DS Group
1 hubs on page C-16. If 2-1/2-inch (63.5 mm)
hub is needed, remove adapter and use
ARP00007CH25 hub.
Neutral is bonded suitable for service
entrance only can not be converted for
sub-feed application.

The maximum rating of the panel is the main


circuit breaker rating when used as service
entrance equipment.
Door lock and key included with loadcenter.
Combination style covers may be used in
surface or ush applications.
Loadcenter has surface cover no ush offering available.
Wire range size for BR1020B100SP is #6 - #1
Al/Cu.

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
1-Phase with High Interrupting Main Circuit Breakers

October 1998

1-Phase Main Circuit Breaker Loadcenters


22,000/25,000 Amperes Interrupting Capacity
1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main
Breaker
Type

Main
Ampere
Rating

Maximum
Number
1-inch (25.4 mm)
Spaces

Enclosure Loadcenter Catalog


Type
Number with
Combination Cover

Box
Size

Poles

BRH
22 kAIC

100

20

24

Indoor

BWH
25 kAIC

150

20

30

Indoor

BR2030H150

200

20
30
40

40
40
40

Indoor
Indoor
Indoor

BR2040H200
BR3040H200
BR4040H200

All main circuit breaker loadcenters are


listed for use as service entrance equipment
and are shipped with neutral bonding strap
preattached. The maximum rating of the
panel is the main circuit breaker rating when
used as service entrance equipment.
Ground bar kits priced separately.
See page C-16.
Refer to page C-25 for dimensions.
22,000 AIC series combination rating is
obtained when Types BD, BR, BQ, BQC and
GFCB 10,000 AIC branch breakers are used
in series with Type BRH main breaker.
25,000 AIC series combination rating is
obtained when Types BD, BR, BQ, BQC and
GFCB 10,000 AIC branch circuit breakers are
used in series with Type BWH main breaker.

CAT.73.01.T.E

List
Price

BR2024H100

$296.00

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Breaker

C2

10

#2/0 - 300 kcmil

580.00

C4

26

#2/0 - 300 kcmil

545.00
645.00
755.00

D1
G1
L1

29
30
28

#2/0 - 300 kcmil

Discount Symbol 22CD

C-7

C-8

Cutler-Hammer

Type BR Loadcenters
1-Phase with Main Lugs

October 1998

4, 6, and 8 Circuits 125 Amperes

2 Circuits 70 Amperes

Surface

Flush

Surface no Door

2 Circuits 125 Amperes

Flush with Door

Surface

Outdoor

Outdoor

Flush

Outdoor

1-Phase Main Lug Loadcenters


1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main Ampere Maximum Number
Rating
1-inch (25.4 mm)
Spaces

Type of
Enclosure

Type of
Trim

Loadcenter Catalog
Number

List
Price

Box
Size

Wiring
Diagram
Figure
Number

$ 41.00
43.60
80.00
41.00
43.60

5
5
5R
5
5

1
1
1
1
1

#8 - #2

51.00
88.00
51.00

6
6R
6

1
1
1

#14 - 1/0

Poles

Wire Size Range


for Cu/Al
60C or 75C
for Main Lugs

70

2
2
2
2
2

4
4
4
4
4

Indoor
Indoor
Outdoor
Indoor
Indoor

Surface no Door
Surface no Door

Flush no Door
Flush no Door

BR24L70SP
BR24L70SGP
BR24L70RP
BR24L70F
BR24L70FGP

125

2
2
2

4
4
4

Indoor
Outdoor
Indoor

Surface no Door

Flush no Door

BR24L125SP
BR24L125RP
BR24L125FP

4
4
4
4
4
4

8
8
8
8
8
8

Indoor
Indoor
Outdoor
Indoor
Indoor
Indoor

Surface no Door
Surface no Door

Flush no Door
Flush with Door
Flush with Door

BR48L125SP
BR48L125SGP
BR48L125RP
BR48L125FP
BR48L125FDP
BR48L125FGP

66.00
76.00
109.00
66.00
85.00
76.00

7
7
7R
7
7
7

2
2
2
2
2
2

#14 - 1/0

6
6
6
6
6
6
6
6
6

12
12
12
12
12
12
12
12
12

Indoor
Indoor
Indoor
Indoor
Outdoor
Indoor
Indoor
Indoor
Indoor

Surface no Door
Surface no Door
Surface with Door
Surface with Door

Flush no Door
Flush no Door
Flush with Door
Flush with Door

BR612L125SP
BR612L125SGP
BR612L125SDP
BR612L125SDGP
BR612L125RP
BR612L125FP
BR612L125FGP
BR612L125FDP
BR612L125FDGP

78.00
86.00
88.00
96.00
118.00
78.00
86.00
88.00
96.00

7
7
7
7
7R
7
7
7
7

3
3
3
3
3
3
3
3
3

#14 - #1

8
8
8
8
8
8
8
8
8
8
8

16
16
16
16
16
16
16
16
16
16
16

Indoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Indoor
Indoor
Indoor
Indoor
Indoor

Surface no Door
Surface no Door
Surface with Door
Surface with Door
Surface with Door

Flush no Door
Flush no Door
Flush with door
Flush with Door
Flush with Door

BR816L125SP
BR816L125SGP
BR816L125SDP
BR816LC125SDP
BR816L125SDGP
BR816L125RP
BR816L125FP
BR816L125FGP
BR816L125FDP
BR816LC125FDP
BR816L125FDGP

98.50
110.00
110.00
140.00
120.00
174.00
98.50
110.00
127.00
140.00
120.00

7
7
7
7
7
7R
7
7
7
7
7

4
4
4
4
4
4
4
4
4
4
4

#14 - #1

Ground bar kits priced separately.


See page C-16
For 2/4 circuit loadcenters use GBK5 or
GBK520 Ground Bar.
For 4/8, 6/12 and 8/16 circuit loadcenters
use GBK10 Ground Bar.
Ground bars mount to the left side wall of
the enclosure for the 4/8, 6/12 and 8/16
circuit loadcenters
Refer to page C-25 for dimensions.
Copper bus is included.
Ground bar GBK10 is installed.

Rainproof panels are furnished with hub closure


plates. For rainproof hubs refer to page C-16.

Ground bar GBK5 is installed.


Ground bar GBK14 is installed.
CSA and UL approved.

Suitable for use as service equipment when not


more than two service disconnecting mains are provided or when not used as a lighting and appliance
panelboard (see Article 384-14 of the NEC).
Suitable for use as service equipment when not
more than two service disconnecting mains are provided or when not more than six service disconnect-

ing mains are provided and when not used as a


lighting and appliance panelboard (see Article
384-14 of the NEC).
Suitable for use as service equipment when a main
breaker is used or when not more than six service
disconnecting mains are provided and when not
used as a lighting and appliance panelboard
(see Article 384-14 of the NEC).

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
1-Phase with Main Lugs

October 1998

C-9

1-Phase Main Lug Loadcenters, Continued


1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main
Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

Enclosure
Type

Loadcenter Catalog Number with


Combination or NEMA Type 3R Cover

List
Price

Wiring
Diagram
Figure
Number

Box
Size

Poles

125

12
12
12
12
12
16
16
16
20
20
20
24
24

12
24
24
24
24
24
24
24
24
24
24
24
24

Indoor
Indoor
Indoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Indoor

150

16
20

30
30

Indoor
Indoor

200

8
12
12
20
20
24
30
30
40
40

16
24
24
40
40
40
40
40
40
40

225

42
42

42
42

Main
Maximum Number
Ampere 1-inch (25.4 mm)
Rating
Spaces
Poles

$ 117.00
125.00
133.00
166.00
192.00
163.00
177.00
230.00
207.00
219.00
270.00
207.00
219.00

BR1212L125
BR1224L125
BR1224L125G
BR1224L125DG
BR1224L125R
BR1624L125
BR1624L125G
BR1624L125R
BR2024L125
BR2024L125G
BR2024L125R
BR2424L125
BR42424L125G

Wire Size
Range Cu/Al
60C or 75C
for Main Lugs

B1
B1
B1
B1
B1R
B2
B2
B2R
C1
C1
C1R
C2
C2

9
6
6
6
6
7
7
7
8
8
8
5
5

#6 - 2/0

BR1630L150
BR2030L150

195.00
221.00

C1
C2

62
11

#1 - 300 kcmil

Outdoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Outdoor

BR816L200RF
BR1224L200
BR1224L200R
BR2040L200
BR2040L200R
BR2440L200
BR3040L200
BR3040L200R
BR4040L200
BR4040L200R

239.00
197.00
261.00
257.00
355.00
282.00
304.00
498.00
415.00
665.00

B2R
B2
B2R
C2
C3R
C4
D1
D1R
G1
G1R

63
12
12
12
12
64
15
15
5
5

#1 - 300 kcmil

Indoor
Outdoor

BR4242L225
BR4242L225R

455.00
715.00

L1
L1R

20
20

#1 - 300 kcmil

Enclosure Commercial Loadcenter


Type
Catalog Number

400

12
12
24
42
42

24
24
42
42
42

Indoor
Outdoor
Indoor
Indoor
Outdoor

600

42

42

Indoor

List
Price

Box
Size

Wiring Diagram
Figure Number

Wire Size Range


Cu/Al
60C or 75C
for Main Lugs

With Flush or NEMA


Type 3R Cover

With Surface Cover

1224DRIN

4242DFN
4242DRIN

1224DSN

2442DSN
4242DSN

$ 770.00
930.00
935.00
1,060.00
1,335.00

19
42
20
22
46

44
44
21
14
14

(1) #4/0 - 750 kcmil


or
(2) #3/0 - 400 kcmil

4242ESN

1,365.00

22

14

(2) #2 - 500 kcmil

1-Phase Main Lug Loadcenters, Non-Metallic


1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main
Maximum Number
Ampere 1-inch (25.4 mm)
Rating
Spaces
Poles

Enclosure Type
Type
of Trim

Loadcenter
Catalog
Number

40

Indoor

Flush No Door

60

2
2
2
2
2

4
4
4
4
4

Indoor
Indoor
Indoor
Indoor
Outdoor

Flush no Door
Surface no Door
Flush no Door
Surface no Door

Ground bar kits priced separately unless


otherwise noted. See page C-16.
Rainproof panels are furnished with hub
closure plates. For rainproof hubs refer to
page C-16.
Has notch for BREQS125 hold-down kit.
Has notch for BRHDK125 hold-down kit.
Door lock and key included with loadcenter.
Single, movable neutral is provided.
Combination cover style.
Suitable for use as service equipment when

CAT.73.01.T.E

TT120FLGNM
TT120SLGNM
2460FNM
2460SNM
2460FGNM
2460SGNM
2460RNM

List
Price

$ 40.00
40.00
44.25
44.50
46.75
47.00
85.50

not more than six main disconnecting


means are provided and when not used as a
lighting and appliance panelboard
(see article 384-14 of the NEC.)
Ground bar GBK8 installed.
Ground bar GBK10 installed.
Ground bar GBK1220 installed.
Ground bars GBK5 and GBK520 installed.
Includes through-feed lugs for both phase
and neutral conductors.
Refer to page C-25 for dimensions.

Box
Size

Wiring Diagram
Figure Number

Wire Size Range


Cu/Al
60C or 75C
for Main Lugs

2
2

65
65

2
2
2
2
2R

1
1
1
1
1

#14 - 2

This device has no main lugs. A Type BR or


BD breaker is required to be backfed to supply power to branch breakers. This device is
single phase 120 V AC only. With the use of
three Type BR breakers there are two branch
circuits available. With the use of three Type
BD breakers there are ve branch circuits
available. See Wiring Diagram 61 on
page C-35.
Includes GB4NM ground bar.

Discount Symbol 22CD

C-10

Cutler-Hammer

Type BR Loadcenters
3-Phase with Main Circuit Breakers

October 1998

3-Phase Main Circuit Breaker Loadcenters


10,000/22,000/100,000 Amperes Interrupting Capacity
3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral
Main
Breaker
Type

Main
Ampere
Rating

Maximum
Number
1-inch (25.4 mm)
Spaces

Enclosure
Type

Poles

Loadcenter Catalog Number

List Price

Box
Size

$ 580.00
660.00

C1
CR

With Combination or With Surface


NEMA Type 3R Cover Cover

CC
10 kAIC

125

30

42

Indoor

3BR3042B125

3BR3042B125S

1,080.00

L1

41

#1 - 2/0

150

30
30

42
42

Indoor
Outdoor

3BR3042B150
3BR3042B150R

3BR3042B150S

1,125.00
1,245.00

L1
L1R

41
41

#1 - 3/0

200

30
30
42
42

42
42
42
42

Indoor
Outdoor
Indoor
Outdoor

3BR3042B200
3BR3042B200R
3BR4242B200
3BR4242B200R

3BR3042B200S

3BR4242B200S

1,130.00
1,250.00
1,195.00
1,470.00

L1
L1R
L2
L2R

41
41
43
43

#1 - 250 kcmil

225

42
42

42
42

Indoor
Outdoor

3BR4242B225
3BR4242B225R

3BR4242B225S

1,255.00
1,585.00

L2
L2R

43
43

#1 - 300 kcmil

List Price

Box
Size

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Breaker

Spaces

Enclosure
Type

Poles

400

42
42

42
42

Indoor
Outdoor

LD

600

42

42

Indoor

Main
Ampere
Rating

Maximum
Number
1-inch (25.4 mm)
Spaces

Commercial Loadcenter Catalog


Number
With Combination or With Surface
NEMA Type 3R Cover Cover

DK
22 kAIC

Main
Breaker
Type

BR1224B100S

#4 - 1/0

12
12

Maximum
Number
1-inch (25.4 mm)

3BR1224B100
3BR1224B100R

65
65

100

Main
Ampere
Rating

Indoor
Outdoor

Wire Size Range


Cu/Al
60C or 75C
for Main Breaker

BR
10 kAIC

Main
Breaker
Type

24
24

Wiring
Diagram
Figure
Number

Enclosure
Type

Poles

3B4242DFN
3B4242DR1N

3B4242DSN

$4,170.00
4,755.00

24
47

42
42

(2) #3/0-250 kcmil

3B4242EFN

3B4242ESN

6,785.00

24

42

(2) #3/0-500 kcmil

List Price

Box
Size

Loadcenter Catalog Number

With Combination
Cover

With Surface
Cover

Wire Size
Wiring
Diagram Range for Main
Cu/Al
Figure
Number

BRH
22 kAIC

100

12

24

Indoor

3BR1224H100

3BR1224H100S

$ 670.00

C1

65

#4 - 1/0

CHH
100 kAIC

150

30

42

Indoor

3BR3042H150

3BR3042H150S

1,365.00

L1

41

#1 - 250 kcmil

CHH
100 kAIC

200

30
42

42
42

Indoor
Indoor

3BR3042H200
3BR4242H200

3BR3042H200S
3BR4242H200S

1,375.00
1,465.00

L1
L2

41
43

#1 - 250 kcmil

All main circuit breaker loadcenters are listed


for use as service entrance equipment and
are shipped with a neutral bonding strap
pre-attached (commercial loadcenters do not
have a pre-attached bonding strip). The maximum main rating of the panel is the main
circuit breaker rating when used as service
entrance equipment.
Ground bar kits priced separately.
See page C-16.
Refer to page C-25 for dimensions.
Rainproof loadcenters are furnished with
hub closure plates. For rainproof hubs, refer
to page C-16.
Door lock and key included with loadcenter.

Type DK main circuit breaker is rated 65,000


AIC at 240V AC and allows a 22,000 AIC
series rating on the loadcenter when Types
BR, BD and BJ branch circuit breakers are
used.
The LD main circuit breaker is rated 65,000
AIC at 240V AC. Type LD circuit breaker is
not series rated with Types BR, BD and BJ
branch circuit breakers.
22,000 AIC series combination rating is
obtained when Types BD, BR, BQ, BQC and
GFCB branch breakers are used with BRH
main.
100,000 AIC series combination rating is
obtained when Types BD, BR, BQ, BQC and
GFCB branch breakers are used with CHH
main.

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
3-Phase with Main Lugs

October 1998

C-11

3-Phase Main Lug Loadcenters


3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral
Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

Enclosure
Type

Poles

Loadcenter Catalog Number


With Combination or
NEMA Type 3R Cover

With Surface
Cover

100

3
3

3
3

Indoor
Outdoor

S3100RN

S3100SLN

125

12
12

24
24

Indoor
Outdoor

3BR1224L125
3BR1224L125R

3BR1224L125S

150

18
18
24
24

36
36
42
42

Indoor
Outdoor
Indoor
Outdoor

3BR1836L150
3BR1836L150R
3BR2442L150
3BR2442L150R

3BR1836L150S

12
12
18
18
24
30
30
42
42

24
24
36
36
42
42
42
42
42

Indoor
Outdoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Outdoor

3BR1224L200
3BR1224L200R
3BR1836L200
3BR1836L200R
3BR2442L200
3BR3042L200
3BR3042L200R
3BR4242L200
3BR4242L200R

3BR1224L200S

42
42

42
42

Indoor
Outdoor

3BR4242L225
3BR4242L225R

200

225

Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

Enclosure
Type

Poles

400

18
18
24
42
42

36
36
42
42
42

Indoor
Outdoor
Indoor
Indoor
Outdoor

600

42

42

Indoor

Ground bar kits priced separately.


See page C-16.
Refer to page C-25 for dimensions.
Rainproof loadcenters are furnished with
hub closure plates. For rainproof hubs, refer
to page C-16.
Has notch for BREQS125 hold-down kit.

CAT.73.01.T.E

List
Price

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Lugs

9
9R

32
32

#14 - 1/0

197.00
271.00

C1
C1R

35
35

#6 - 2/0

277.00
350.00
333.00
446.00

C2
C3R
D1
D1R

35
35
34
34

#1 - 300 kcmil

C2
C3R
C4
C3R
G1
G1
G1R
L1
L1R

35
35
35
35
34
33
33
37
37

#1 - 300 kcmil

3BR2442L200S
3BR3042L200S

3BR4242L200S

271.00
346.00
329.00
407.00
377.00
392.00
469.00
540.00
830.00

3BR4242L225S

595.00
880.00

L1
L1R

37
37

#1 - 300 kcmil

3BR2442L150S

3BR1836L200S

Commercial Loadcenter Catalog Number


With Flush or
NEMA Type 3R Cover

With Surface
Cover

31836DFN
31836DR1N

34242DFN
34242DR1N

31836DSN

32442DSN
34242DSN

34242EFN

34242ESN

$ 91.50
136.00

Box
Size

List
Price

Box
Size

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Lugs

$1,025.00
1,340.00
1,115.00
1,310.00
1,625.00

19
43
19
22
46

40
40
38
39
39

(1) #4/0 - 750 kcmil


or
(2) #3/0 - 400 kcmil

1,645.00

22

39

(2) #2 - 500 kcmil

Door lock and key included with loadcenter.


Suitable for use as service equipment when
not more than six main disconnecting
means are provided and when not used as
a lighting and appliance panelboard (see
article 384-14 of the NEC.)

Discount Symbol 22CD

C-12

Cutler-Hammer

Type BR Loadcenters
Convertible, Base Units and Main Devices

October 1998

Convertible Loadcenters MCB or MLO Base Units and Main Devices


10,000/22,000/25,000 Amperes Interrupting Capacity
Complete Assembly Consists Of: Loadcenter and Either Main Breaker Kit or Main Lug Kit
Base Units
1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

Enclosure
Type

Poles

Loadcenter Catalog Number


With Combination or NEMA
Type 3R Cover

125

12
12
16
16
20
20

24
24
24
24
24
24

Indoor
Outdoor
Indoor
Outdoor
Indoor
Outdoor

BR1224N125
BR1224N125R
BR1624N125
BR1624N125R
BR2024N125
BR2024N125R

200

8
12
12
16
20
20
24
30
30
40
40

16
24
24
32
40
40
4
40
40
40
40

Outdoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Indoor
Outdoor

BR816N200RF
BR1224N200
BR1224N200R
BR1632N200
BR2040N200
BR2040N200R
BR2440N20U
BR3040N200
BR3040N200R
BR4040N200
BR4040N200R

List
Price

Box
Size

Wiring
Diagram
Figure
Number

$124.00
191.00
158.00
230.00
206.00
267.00

B2
B2R
C1
C1R
C2
C3R

49
49
45
45
50
50

239.00
158.00
242.00
195.00
231.00
316.00
262.00
329.00
398.00
429.00
463.00

C3R
C4
C3R
C4
D1
D1R
G1
G1
G1R
L1
L1R

52
13
13
13
13
13
61
53
53
47
47

Wire Size Range


Cu/Al
60C or 75C
for Main
See main breaker and
main lug kit tables
below.

3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral


Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

Enclosure
Type

Poles

Loadcenter Catalog Number


With Combination
or NEMA Type 3R
Cover

List
Price

With Surface
Cover

100

30

30

Indoor

3BR3030N100

3BR3030N100S

125

12

24

Indoor

3BR1224N125

3BR1224N125S

Main Devices
2- and 3-Pole Main Circuit Breakers;
120/240V AC or 208Y/120V AC or 240V AC
Ampere
Rating

10,000 AIC

22,000/25,000 AIC

Box
Size

Wiring
Diagram
Figure
Number

$326.00

D1

48

201.00

C1

51

Wire Size Range


Cu/Al
60C or 75C
for Main

See main breaker and


main lug kit tables
below.

2- and 3-Pole Main Lug Kits


120/240V AC or 208Y/120V AC or 240V AC
Wire Size Range
Cu/Al
60C or 75C
for Main Breaker

Ampere
Rating

Catalog
Number

List
Price

Wire Size Range


Cu/Al
60C or 75C
for Main Lugs

Catalog
Number

List
Price

List
Catalog
Number Price

100

BR2100

$118.00

BRH2100

$160.00

#4 - 1/0

125

BRSF125

$20.60

#6 - 2/0

110

BR2110

246.00

BRH2110

590.00

#4 - 1/0

150

BRL200

53.00

#1 - 300 kcmil

125

BR2125

246.00

BRH2125

590.00

#4 - 2/0

175

BRL200

53.00

#1 - 300 kcmil

125

BW2125

261.00

BWH2125

600.00

#2 - 300 kcmil

200

BRL200

53.00

#1 - 300 kcmil

150

BW2150

261.00

BWH2150

600.00

#2 - 300 kcmil

175

BW2175

261.00

BWH2175

600.00

#2 - 300 kcmil

150

3BRSF150

52.00

#6 - 3/0

200

BW2200

261.00

BWH2200

600.00

#2 - 300 kcmil

2-Pole

2-Pole

Main Circuit Breaker with Accessory

3-Pole
100

3-Pole

BR3100

213.00

BRH3100

307.00

Interrupting rating depends on main circuit


breaker selected.
The maximum rating of the loadcenter is the
main circuit breaker rating when used as
service entrance equipment.
100, 125 and 200 ampere Convertible base
unit catalog numbers include interior, box and
cover only. Main devices and accessories
must be ordered separately for eld installation. All Convertible base units are listed as
suitable for use as service entrance equipment when used per Article 384 of the NEC.
Ground bar kits priced separately, refer to
page C-16.

#1

Example: BW22005R01
(Put description with catalog number
on order. See page C-24.)

Refer to page C-25 for dimensions.


BREQS125 hold-down screw comes with
loadcenter for back-fed Types BR and BRH
main circuit breakers.
Rainproof loadcenters are furnished with
hub closure plates. For rainproof hubs, refer
to page C-16.
Includes through-feed lugs for both phase
and neutral conductors.
No hold-down provisions for back-fed Types
BR and BRH main circuit breakers.

Convertible to maximum of 100 ampere main


circuit breaker and 125 ampere main lug.
Series combination rating with Types BD, BR,
BQ, BQC and GFCB is 22,000 AIC with BRH
main and 25,000 AIC with BWH main.
Suitable for use as service equipment when
not more than six main disconnecting means
are provided and when not used as a lighting
and appliance panelboard (see article 384-14
of the NEC.)

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters

October 1998

Copper Bus Main Circuit Breaker, Main Lug, Convertible

Main Circuit Breaker/Main Lug/Convertible Loadcenters With Copper Bus


10,000/22,000/25,000 Amperes Interrupting Capacity
Main Circuit Breaker 1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral
Main Breaker
Type

Main
Ampere
Rating

BR
10 kAIC

100

BRH
22 kAIC

Maximum Number
1-inch (25.4 mm)

Enclosure
Type

Loadcenter Catalog
Number With
Combination Cover

List
Price

Box
Size

Wiring Diagram
Figure Number

Spaces

Poles

30

30

Indoor

BR3030BC100

$392.00

D1

16

30

30

Indoor

BR3030HC100

432.00

D1

16

Wire Size Range


Cu/Al 60C or 75C
for Main Breaker

#4 - 1/0

Main Lug 1-Phase 3-Wire 120/240V AC Single Neutral


Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

125

8
8

Enclosure
Type

Type
of Trim

Loadcenter
Catalog Number

List
Price

Surface w/door
Flush w/door

BR816LC1255DP
BR816LC1255PDP

$140.00
140.00

Box
Size

Wiring Diagram
Figure Number

Poles

16
16

Indoor
Indoor

7
7

7
7

Wire Size Range


Cu/Al 60C or 75C
for Main Lugs

#14 - 1

Main Circuit Breaker 3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral


Main Breaker
Type

BW
10 kAIC

Main
Ampere
Rating

200A

Maximum Number
1-inch (25.4 mm)
Spaces

30
42
42

Enclosure
Type

Poles

42
42
42

Indoor
Indoor
Outdoor

Loadcenter Catalog Number


With Combination or
NEMA Type 3R Cover

3BR3042BC200
3BR4242BC200
3BR4242BC200R

List
Price

Box
Size

$1,260.00
1,380.00
1,405.00

L1
L2
L2R

Wiring Diagram
Figure Number

41
43
43

Wire Size Range


Cu/Al 60C or 75C
for Main Breaker

#1/0 - 250 kcmil

Main Lug 3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral


Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

200

30
42
42

Enclosure
Type

Loadcenter Catalog Number


With Combination or
NEMA Type 3R Cover

Poles

42
42
42

Indoor
Indoor
Outdoor

3BR3042LC200
3BR4242LC200
3BR4242LC200R

List
Price

Box
Size

$434.00
620.00
705.00

G1
L1
L1R

Wiring Diagram
Figure Number

33
37
37

Wire Size Range


Cu/Al 60C or 75C
for Main Lugs

#1/0 - 300 kcmil

Convertible 1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral


Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)

Spaces

Enclosure
Type

Loadcenter Catalog Number


With Combination or
NEMA Type 3R Cover

Poles

125
10/22 kAIC

12
12
20
20

24
24
24
24

Indoor
Outdoor
Indoor
Outdoor

BR1224NC125
BR1224NC125R
BR2024NC125
BR2024NC125R

200
10/25 kAIC

20
20
30
30
40
40

40
40
40
40
40
40

Indoor
Outdoor
Indoor
Outdoor
Indoor
Outdoor

BR2040NC200
BR2040NC200R
BR3040NC200
BR3040NC200R
BR4040NC200
BR4040NC200R

List
Price

Box
Size

Wiring Diagram
Figure Number

$135.00
204.00
223.00
287.00

B2
B2R
C2
C3R

49
49
50
50

249.00
338.00
379.00
436.00
462.00
498.00

D1
D1R
G1
G1R
L1
L1R

13
13
53
53
47
47

Wire Size Range


Cu/Al 60C or 75C
for Main

See main breaker


and main lug kit tables
on page C-12.

Convertible 3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral


Main Ampere
Rating

Maximum Number
1-inch (25.4 mm)
Spaces

Enclosure Type

Loadcenter Catalog Number


With Combination or
NEMA Type 3R Cover

Poles

100
10/22 kAIC

30
30

30
30

Indoor
Outdoor

3BR3030NC100
3BR3030NC100R

125
10/22 kAIC

12
12

24
24

Indoor
Outdoor

3BR1224NC125
3BR1224NC125R

All main circuit breaker loadcenters are listed


for use as service entrance equipment and
are shipped with a neutral bonding strap preattached. The maximum main rating of the
loadcenter is the main breaker rating when
used as service entrance equipment.
Ground bar kits priced separately.
See page C-16.
Refer to page C-25 for dimensions.
Rainproof loadcenters are furnished with
hub closure plates. For rainproof hubs, refer
to page C-16.

CAT.73.01.T.E

List
Price

Box
Size

Wiring Diagram
Figure Number

$358.00
446.00

D1
D1R

48
48

225.00
309.00

C1
C1R

51
51

100, 125 and 200 ampere Convertible base


unit catalog numbers include interior, box and
cover only. Main devices must be ordered
separately from page 12. Accessories must
also be ordered separately for eld installation. All Convertible base units are listed as
suitable for use as service entrance equipment
when used per article 384 of the NEC.
Hold-down screw BREQS125 comes with
loadcenter for back-fed Types BR and BRH
main circuit breakers.
Convertible to maximum of 100 ampere
main breaker and 125 ampere main lug.

Wire Size Range


Cu/Al 60C or 75C
for Main

See main breaker


and main lug kit tables
on page C-12.

Interrupting rating depends on main circuit


breaker selected. See page C-12 for mains.
Suitable for use as service equipment when
not more than six main disconnecting
means are provided and when not used as a
lighting and appliance panelboard (see article 384-14 of the NEC.)
22,000 AIC series combination rating is
obtained when BD, BR, BQ, BQC and GFCB
10,000 AIC branch circuit breakers are used
with a BRH main.

Discount Symbol 22CD

C-13

C-14

Cutler-Hammer

Type BR Loadcenters
New York City Indoor

October 1998

New York City Loadcenters Indoor Enclosures


Main Circuit Breaker and Main Lug, 1-Phase and 3-Phase
MAIN CIRCUIT BREAKER FACTORY INSTALLED
Main
Breaker
Type

Main
Ampere
Rating

Maximum Number
1-inch (25.4
mm)
Spaces

Poles

Enclosure
Type

Loadcenter Catalog Number


Flush Cover

Surface Cover

List
Price

Box
Size

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Breaker

1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral


WFP
10 kAIC

200

42

42

Indoor

B4242BYSQ

$ 850.00

56

#1 - 300 kcmil

3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral


WFL
10 kAIC

200
225

42

42

Indoor

3B4242BYSQ

3B4242BYSQ
3B4242CYSQ

1,590.00
1,695.00

A
A

57
57

#1 - 300 kcmil
#1 - 300 kcmil

DK
42 kAIC

400

42

42

Indoor

3B4242DYSN

4,870.00

42

#1 - 300 kcmil

MAIN LUGS FACTORY INSTALLED


Main Lug
Ampere
Rating

Maximum Number
1-inch (25.4 mm) Poles
Spaces

Enclosure
Type

Loadcenter Catalog Number


Flush Cover

Surface Cover

List
Price

Box
Size

Wiring
Diagram
Figure
Number

Wire Size Range


Cu/Al
60C or 75C
for Main Lugs

1-Phase 3-Wire 120/240V AC Insulated/Bondable Neutral


225

42

42

Indoor

4242CYSN

$ 580.00

55

#1 - 300 kcmil

3-Phase 4-Wire 208Y/120V AC or 240V AC Insulated/Bondable Neutral


225

42

42

Indoor

34242CYFN

34242CYSN

955.00

58

#1 - 300 kcmil

400

42

42

Indoor

34242DYSN

1,455.00

39

250-750 kcmil

Refer to page C-25 for dimensions.

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
1- and 3-Phase Circuit Breaker Unit Enclosures

October 1998

C-15

1-Phase and 3-Phase


Circuit Breaker Unit Enclosures
10,000/25,000 Amperes Interrupting Capacity

Circuit Breaker
Unit Enclosures

Main
Ampere
Rating

Unit Enclosure Catalog Number


Enclosure
Type

Flush
Cover

BW2200

Unit Enclosure Catalog Number

Surface
Cover

List
Price

Enclosure
Type

Rainproof
NEMA Type 3R

List
Price

Type of
Circuit
Breaker

Wire Size Range


Cu/Al
60C or 75C

Type ECB Circuit Breaker Unit Enclosures Order Types BW and BWH Circuit Breakers Separately
Unit Enclosure Includes Lug Tree Kit
1-Phase 3-Wire 240V AC Maximum
225

Indoor

ECB225F

ECB225S

$ 135.00

Outdoor

ECB225R

$ 260.00

BW
10 kAIC
BWH
25 kAIC

280.00

CC
10 kAIC

Type ECC Circuit Breaker Unit Enclosures Order Type CC Circuit Breakers Separately
1-Phase 3-Wire/3-Phase 4-Wire 240V AC Maximum
225

Indoor

ECC225F

ECC225S

155.00

Types BW and BWH Circuit Breakers


120/240V AC 10,000, 25,000 AIC
For Use in Type ECB Unit Enclosures
Ampere
Rating

125
150
175
200
225

Wire Size Range


Cu/Al
60C or 75C for
Line Terminals

25,000 AIC

Catalog
Number

List
Price

Catalog
Number

List
Price

BW2125
BW2150
BW2175
BW2200
BW2225

$251.00
251.00
251.00
251.00
251.00

BWH2125 $575.00
BWH2150
575.00
BWH2175
575.00
BWH2200
575.00
BWH2225
575.00

#2-300 kcmil

BW/BWH Lug Tree Kit


For Replacement Purposes Only
For Use in Type CCM Unit Enclosures
Ampere
Rating

225

Description

Catalog
Number

For use on
MCBK225
125, 150, 175, 200 and
225 Ampere BW and
BWH Breakers

Order circuit breaker separately.


Dimensions see page C-25.
BW2150 factory installed circuit breaker.
BW2200 factory installed circuit breaker.
Rainproof enclosures are furnished with hub
closure plates. For rainproof hubs, refer to
page C-16.
One ground lug accepting (1) #14-#2 is
factory installed. Also, there are pre-drilled
holes to accept a GBK5 ground bar.

CAT.73.01.T.E

ECC225R

Type CC Circuit Breakers


240V AC 10,000 AIC
For Use in Type ECC Unit Enclosures

2-Pole Breakers
10,000 AIC

Outdoor

Ampere
Rating

Type CC
10,000 AIC

Type CC Hi Mag
10,000 AIC

Wire Size Range


Cu/Al
60C or 75C for
Line Terminals

Catalog
Number

List
Price

Catalog
Number

List
Price

100
125
150

CC2100
CC2125
CC2150

$284.00
284.00
284.00

CC2100HM
CC2125HM
CC2150HM

$352.00
352.00
352.00

#4-4/0

175
200
225

CC2175
CC2200
CC2225

284.00
284.00
284.00

CC2175HM
CC2200HM
CC2225HM

352.00
352.00
352.00

#2/0 - 300 kcmil

100
125
150

CC3100
CC3125
CC3150

414.00
760.00
760.00

CC3100HM
CC3125HM
CC3150HM

483.00
825.00
825.00

#4-4/0

175
200
225

CC3175
CC3200
CC3225

760.00
760.00
760.00

CC3175HM
CC3200HM
CC3225HM

825.00
825.00
825.00

#2/0 - 300 kcmil

2-Pole

3-Pole
List
Price

Wire Size Range


Cu/Al
60C or 75C for
Line Terminals

$41.00

#2-300 kcmil

Wire size is determined by the circuit breaker


installed in enclosure. Maximum wire size
and ampere rating is determined by table as
follows:
Wire/Application

Maximum
Wire Size

Maximum
Ampere Rating

Aluminum
Standard

250 kcmil

200

Aluminum
Service Entrance

250 kcmil

225

Copper
Standard and
Service Entrance

250 kcmil

225

Discount Symbol 22CD

Cutler-Hammer

Type BR Loadcenters
Accessories

C-16

October 1998

Loadcenter Accessories
Field Installation Kits and Parts
Number
of Poles

Ampere
Rating

Number of 1-inch (25.4 mm)


Spaces Needed

Wire Size Range


Cu/Al 60C or 75C

Catalog
Number

List Price
Each

Ordering
Quantity

$ 19.40
36.80
59.50

1
1
1

Main and Sub-Feed Lug Blocks


2

125
150
225

2
2
2

#6 - 2/0
#6 - 3/0
#2 - 300 kcmil

BRSF125
BRSF150
BRS225

150
225

3
3

#6 - 3/0
#2 - 300 kcmil

3BRSF150
3BRS225

48.90
93.50

1
1

#1-300 kcmil

BRL200

49.90

#2/0 Maximum
#3/0 Maximum
300 kcmil Maximum

NL20
NL30
NL300

11.30
13.90
25.50

1
1
1

BRFP
BWFP

2.50
5.60

25
1

Main Lugs
2-Pole, 200 Ampere Stud Mounted
(Includes Deadfront Filler Plate)
Neutral/Ground Lug
Add-On Neutral or Ground Lug
Filler Plates
1-Inch (25.4 mm) Circuit Breaker Space
CM Main Circuit Breaker Space (with Hardware)

Door Lock 12 through 42 Circuits, and 100 through 225 Amperes

TDL

Door Lock 4 through 8 Circuits, 125 Amperes

CH9FL

48.90

BRSF125

1
1

ANSI-61 Light Gray Touchup Paint for Current Loadcenters

SPC61

30.50

Isolated Neutral Assembly (Computer Circuits)

BINA

7.40

Circuit Directory Adhesive Backed

TCD

1.20

10

Cover Screws

LCCS

.70

25

Cover Replacement Latch (Gray) 14-5/16 (363.55 mm) Wide


Loadcenters Only

BRRL

6.60

Circuit Marking Strip (Next to Breaker)

BRMS

1.50

10

Circuit Identification Label (preprinted breaker labels)

CHBL

2.10

25

Series Rated Caution Label

SRL

1.30

25

3BRS225

BRL200

TDL

Field Installation Rainproof Conduit Hubs


Description

Conduit Size
Inches (mm)

Catalog
Number

List Price
Each

Ordering
Quantity

Group 1 For use with 70, 100 and 125 Ampere


MLO and MCB Loadcenters and Circuit Breaker
Enclosures

3/4 (19.1)
1 (25.4)
1-1/4 (31.8)
1-1/2 (38.1)
2 (50.8)

DS075H1
DS100H1
DS125H1
DS150H1
DS200H1

$22.30
22.30
22.30
22.30
36.40

1
1
1
1
1

Group 2 For use with 150, 200 and 225 Ampere


MLO and MCB Loadcenters and Circuit Breaker
Enclosures

2 (50.8)
2-1/2 (63.5)
3 (76.2)

DS200H2
DS250H2
DS300H2

36.40
64.50
76.00

1
1
1

Type R1H Conduit Hubs for 400 and 600 Ampere


Loadcenters and New York City Loadcenters

2 (50.8)
2-1/2 (63.5)
3 (76.2)

R1H200
R1H250
R1H300

34.70
56.50
75.50

1
1
1

Type H Conduit Hubs for Loadcenters PL0724R and


S3100RN

3/4 (19.1)
1 (25.4)
1-1/4 (31.8)
1-1/2 (38.1)

RH75
RH100
RH125
RH150

20.90
20.90
20.90
20.90

1
1
1
1

DS900AP
CS900CP1
CS900CP2

10.50
1.70
3.30

1
1
1

Adapter Kit Allows Installing a Group 1 Hub on


Devices Arranged for Group 2 Hubs
Group 1 Small Blank Hub Plate with Bump
Group 2 Large Blank Hub Plate with Bump

DS100H1

GBK14

BRGBK39512

Ground Bar Kits


Length
Inches (mm)

Must be purchased in multiples of ordering


quantities indicated.
Distance between mounting holes is
1-3/4 inches (44.5 mm).

2.54 (64.5)
3.59 (91.9)
4.29 (109.0)
5.34 (135.6)
4.61 (117.1)
5.69 (144.5)
6.74 (171.2)
8.14 (206.8)
9.19 (233.4)
5.78 (146.9)
1.84 (46.7)

Catalog
Number
GBK5
GBK520
GBK10
GBK1020
GBK13
GBK14
GBK1420
GBK21
GBK2120
BRGBK39512
GB4NM

List Price
Each

Ordering
Quantity

$ 9.60
12.10
10.90
13.70
12.00
12.80
15.90
17.40
18.40
13.00
8.60

1
1
1
1
1
1
1
1
1
1
1

For 1- and 3-phase 400 and 600 ampere


applications.
Distance between mounting holes is
2-11/32 inches (59.5 mm).

Ground Bar Legend


(3) #14 - #10 Cu/Al or (1) #14 - #4 Cu/Al
(1) #6 - 2/0 Cu/Al
(1) #14 - #6 Cu/Al or (2) #14 - #12 Cu/Al
(1) 1/8 - 14 or (3) #10 - 12 Cu/Al
(1) #14 - 1/0 Cu/Al or (3) #14 - #10 Cu/Al
(1) #6 - 14 or (2) #10 - 14 Cu/Al
Mounting Hole

Description
(See Legend)

For non-metallic enclosures. Snaps into


molded base.

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Surge Protection

October 1998

C-17

Surge Protectors

The CHSP is backed by a 5-year product


warranty and provides a $10,000 warranty
for properly connected equipment.

Unique Surge Plane design


-25C to +50C
Steel enclosure
5-year limited warranty

Protection Specications
AC Power Protection

Clipper Home Surge Protector Catalog


Numbering System

120/240V (3-wire + Ground)


39 kA surge current per phase
All modes protected
Nanosecond response time
24-inch (609.6 mm) leads included for
installation
Two status indicator lights

CHSPCH A R B
Protection
Position 1
A = AC
Protection
Only
S = AC,
Telephone
and Cable

Telephone Protection
CHSP (Clipper Home Surge Protector)

Clipper Home Surge Protector


CHSP This surge protector is an externally mounted TVSS unit that provides
industrial level surge protection in a
residential design. It is available in two
versions, available in both indoor and
outdoor enclosures. The rst provides AC
power line protection only. The second
provides complete surge protection for
your electrical, telephone, and coaxial
cable lines in one convenient unit. Both
CHSP models are UL1449 (2nd edition)
and 497A listed.

Two incoming lines


10 kA per pair surge protection
PTC polyswitch resetting fuses
230V DC gas tube protection

Enclosure
Position 2
R = Surface/
Flush
O = Outdoor
Enclosure

Packaging
Position 3
B = Box
P = Blister
Pack

Coaxial Cable Protection

Two Cable Type F connectors


(input and output)
Line-to-shield (ground) protection
90V DC gas tube protection

Catalog
Number

Construction/Safety Specications

UL1449 listed (2nd Edition) UL497A,


400V Rating, CSA Certied
Tested to ANSI/IEEE Category B3 and
C3 levels

BRSURGE
Surge
Protector

List
Price

CHSPCHARB
CHSPCHARP
CHSPCHAOB
CHSPCHAOP

$325.00
325.00
395.00
395.00

CHSPCHSRB
CHSPCHSRP
CHSPCHSOB
CHSPCHSOP

400.00
400.00
470.00
470.00

CHSA01
Surge
Protector

CHSA03
Surge
Protector

Surge Protector

Surge Protector

Surge Protector

BRSURGE For use on single-phase,


120/240V AC systems. This easily plugs
into a single-phase Type BR loadcenter
and occupies two 1-inch (25.4 mm) pole
spaces similar to a 2-pole Type BR
breaker. When plugged into the rst two
stabs at the top of the loadcenter just
below the main breaker or main lug, it
provides surge protection for the entire
loadcenter. If internal components are
damaged, the BRSURGE LED visual indicators will signal the need for replacement. This device is suitable for service
entry locations installed in accordance
with NEC Article 280. The BRSURGE is
ideal for protecting sensitive appliances
and electronics, such as refrigerators,
microwave ovens, and home computers.

CHSA01 For use on single-phase, 120/


240V AC systems. This surge protector
can be easily installed in the enclosure of
indoor or outdoor loadcenters by using
the 1/2-inch (12.7 mm) threaded nipple. It
is ideal for protecting outdoor lighting,
garages, sump and irrigation pumps, etc.

CHSA03 For use on three-phase, 600V


AC systems. This surge protector is
installed in the enclosure of indoor and
outdoor loadcenters by using the 1/2-inch
(12.7 mm) threaded nipple. It provides
protection for commercial electrical services especially those using electric
motors.

Refer to Cutler-Hammer CHSP warranty for


complete details.

CAT.73.01.T.E

Description

Catalog
Number

List
Price

Surge Protector Plug-On Type BR,


Single-Phase, 120/240V AC

BRSURGE

Surge Protector, 2-Pole


Single-Phase, 3-Wire, 120/240V AC
Surge Protector, 3-Pole
Three-Phase, 4-Wire, 600V AC

Discharge Voltage, V AC

Lead Length
10 kA Inches (mm)

1.5 kA

3 kA

5 kA

$100.00

345

370

500

545

8 (203.2)

CHSA01

47.80

490

640

980

1410

15 (381.0)

CHSA03

96.50

1700

2100 2510

3800

15 (381.0)

Discount Symbol 22CD

Cutler-Hammer

Type BR Loadcenters
Plug-On Circuit Breakers

C-18

October 1998

Plug-On Circuit Breakers, Types BR


10,000/22,000/42,000/65,000 Amperes
Interrupting Capacity 120V AC,
120/240V AC and 240V AC

BR120

BR215

BR320

Type BR Breakers, 1-Inch (25.4 mm) per Pole 120/240, 10,000, 22,000 and 42,000 AIC
Amperes

1-Pole 120/240V AC
Requires One 1-Inch Space

2-Pole 120/240V AC
Common Trip
Requires Two 1-Inch Spaces

10 per Shelf Carton

5 per Shelf Carton

10 kAIC
Catalog
Number
10
15
20
25
30

BR110
BR115
BR120
BR125
BR130

35
40
45
50

BR140

BR150

55

22 kAIC
List
Price

Catalog
Number

$18.10
18.10
18.10
18.10
18.10
18.10
18.10

10 kAIC
List
Price

BRH115
BRH120
BRH125
BRH130

$40.00
40.00
40.00
40.00

BRH140

BRH150

40.00
40.00

60
70
80
90
100
110

BR160
BR170

125
150

Wire Size
Range
Cu/Al
60C or
75C

18.10
39.25

BRH160
BRH170

40.00
50.00

22 kAIC

42 kAIC

Catalog
Number

List
Price

Catalog
Number

List
Price

Catalog
Number

BR215
BR220
BR225
BR230

BRH215
BRH220
BRH225
BRH230

$ 83.00
83.00
83.00
83.00

#14-4

$ 41.00
41.00
41.00
41.00

BR235
BR240
BR245
BR250

41.00
41.00
41.00
41.00

BRH240

BRH250

#14-4

BR255

39.40

BR260
BR270
BR280
BR290
BR2100
BR2110

41.00
82.00
118.00
118.00
118.00
246.00

BRH260
BRH270

BRH290
BRH2100
BRH2110

83.00
127.00

BR2125
BR2150

246.00
261.00

BRH2125

590.00

83.00
83.00

List
Price

160.00
160.00
590.00

#14-3

BRHH260
BRHH270
BRHH280
BRHH290
BRHH2100
BRHH2110

$127.00
194.00
272.00
272.00
272.00

#4-1/0

BRHH2125

785.00

#4-2/0

Type BR Breakers, 1-Inch (25.4 mm) per Pole 240V AC,


10,000, 22,000 and 42,000 AIC
Amperes

3-Pole 240V AC
Common Trip
Requires Three 1-Inch Spaces

Wire Size
Range
Cu/Al
60C or
75C

5 per Shelf Carton


10 kAIC
Catalog
Number

22 kAIC
List
Price

Catalog
Number

List
Price

10
15
20
25
30

BR315
BR320
BR325
BR330

$143.00
143.00
143.00
143.00

BRH315
BRH320

BRH330

35
40
45
50

BR335
BR340
BR345
BR350

143.00
143.00
143.00
143.00

BRH340

BRH350

55

BR355

137.00

60
70
80
90
100
110

BR360
BR370
BR380
BR390
BR3100

143.00
143.00
143.00
143.00
213.00

BRH360
BRH370

BRH390
BRH3100

125
150

All Type BR 1-, 2-, and 3-pole circuit breakers


carry listing for HACR application.
For circuit breakers with a shunt trip, add
ST sufx and obtain pricing from table on
page C-24.

#14-4
$219.00
219.00
219.00
#14-4
219.00
219.00
#14-3
219.00
275.00

#4-1/0

307.00
307.00
#4-2/0

One pole, 1-inch (25.4 mm) per pole circuit


breakers are available with high magnetic
setting for switching large tungsten lamp
loads. Add sufx H to catalog number.
Switching duty rated.

For use as a branch circuit breaker in 400


and 600 ampere panels only.
On the new black handle breaker add sufx
B to the catalog number and $4 to the list
price to obtain a tapped molded opening for
proper use with hold-down kits.

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer
October 1998

Type BR Loadcenters
Plug-On Circuit Breakers

C-19

Plug-On Arc Fault Circuit Breakers, Type BR


10,000 Amperes Interrupting Capacity
120V AC and 120/240V AC
Type BR Arc Fault Circuit Breakers
1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC
AFCI technology recognizes the unique characteristics of an
arcing fault to trip the breaker and interrupt the circuit.
Amperes

1-Pole
120V AC

2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Spaces

Requires One 1-Inch Space

Type BR 1- and 2-Pole


AFCI Circuit Breakers

1 per Shelf Carton

1 per Shelf Carton

10,000 AIC

10,000 AIC

Configuration

The NEC will mandate the use of AFCI


Protection for 15 and 20 ampere bedroom
outlet circuits in the year 2002. Information will be published in the 1999 National
Electrical Code.

Two-pole AFCI breakers are designed for use


in 3-Wire, 120/240V AC circuits, multiwire
circuits utilizing a shared neutral (often
referred to as a home run circuit),
and 240V AC circuits obtained from
120/240V AC source.
Availability to be announced.

CAT.73.01.T.E

Catalog
Number

List
Price

Configuration

Catalog
Number

Wire Size
Range Cu/Al
60C or 70C

List
Price

15

AFCI
AFCI w/GFCI

BR115AF
BR115GFAF

$146.00

AFCI
AFCI w/GFCI

BR215AF
BR215GFAF

20

AFCI
AFCI w/GFCI

BR120AF
BR120GFAF

$146.00

AFCI
AFCI w/GFCI

BR220AF
BR220GFAF

#14-4

Discount Symbol 22CD

Cutler-Hammer

Type BR Loadcenters
Plug-On Ground Fault Circuit Breakers

C-20

October 1998

Plug-On Ground Fault Circuit Breakers, Type GFCB and GFEP


10,000/22,000 Amperes Interrupting Capacity
120V AC and 120/240V AC
Type GFCB
1-Pole

Type GFCB Ground Fault Circuit Breakers (5 Milliampere),


1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC, 10,000 AIC
Amperes

1-Pole
120V AC
Requires One 1-Inch Space

2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Space

1 per Shelf Carton

1 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number
15
20
25
30
40
50

GFCB115
GFCB120
GFCB125
GFCB130
GFCB140

List Price
$136.00
136.00
136.00
136.00
136.00

Catalog Number
GFCB215
GFCB220
GFCB225
GFCB230
GFCB240
GFCB250

Wire
Size
Range
Cu/Al
60C or
75C

Type GFEP Ground Fault Equipment Protectors (30 Milliampere),


1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC, 10,000 AIC.
Amperes

1-Pole
120V AC
Requires One 1-Inch Space

List Price
$241.00
241.00
241.00
241.00
241.00
241.00

15
20
25
30
40
50

2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Space

1 per Shelf Carton

1 per Shelf Carton

10,000 AIC

10,000 AIC

Catalog Number
#14-4

Type GFCB
2-Pole

GFEP115
GFEP120
GFEP125
GFEP130
GFEP140
GFEP150

List Price
$223.00
223.00
223.00
223.00
223.00
223.00

Catalog Number
GFEP215
GFEP220
GFEP225
GFEP230
GFEP240
GFEP250

Wire
Size
Range
Cu/Al
60C or
75C

List Price
$395.00
395.00
395.00
395.00
395.00
395.00

#14-4

Type GFCBH Ground Fault Breakers (5 Milliampere),


1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC, 22,000 AIC
Amperes

1-Pole
120V AC
Requires One 1-Inch Space
1 per Shelf Carton

1 per Shelf Carton

22,000 AIC

22,000 AIC

Catalog Number
15
20
25
30

2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Space

HAGFH15
HAGFH20
HAGFH25
HAGFH30

List Price
$347.00
347.00
347.00
347.00

Catalog Number
GFCBH215
GFCBH220
GFCBH225
GFCBH230

Wire
Size
Range
Cu/Al
60C or
75C

List Price
$472.00
472.00
472.00
472.00

#14-4

Ground Fault Application Notes


Single-pole GFCBs are designed for use in
2-wire, 120V AC circuits. Figure 1 shows a typical
wiring conguration.
Two-pole GFCBs are designed for use in
3-wire, 120/240V AC circuits, 120V AC multiwire circuits employing common, neutral and
2-wire, 240V AC circuits obtained from a
120/240V AC source.

Figure 1
1-Pole

Figure 2
2-Pole

Figure 3
2-Pole

Figure 4
2-Pole

Figures 2 and 3 illustrate typical wiring congurations for a 120/240V AC multiwire circuits.
Figure 4 depicts a 240V AC, 2-wire circuit. Note
the panel neutral conductor connects to the
neutral bar, even though the neutral is not
included in the load circuit. This connection is
necessary to supply a 120V AC power source
to the ground fault sensing circuit.
The gures are shown with a 120/240V AC,
single-phase, 3-wire power source, but are also
applicable to a 120/208V AC, 3-phase, 4-wire
power supply. For all gures the electrical operation of the GFCB is not affected by the equipment ground.
Available with bell alarm or auxiliary
switch. See circuit breaker accessories
on page C-24.

For use with copper wire only.

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters

October 1998

CTL Plug-On Circuit Breakers, BD Duplex, BQ and BQC Quadplex

CTL Plug-On Circuit Breakers, Type BD Duplex, BQ and BQC Quadplex


10,000 Amperes Interrupting Capacity
120/240V AC

BD2020

BQ2302115

BQC230230

Duplex and Independent Trip Quadplex Breakers


Class CTL 10,000 AIC All circuit breakers have rejection tab feature.
Type BD Duplex (UL Type BRD)

Type BQ Quadplex Independent Trip (UL Type BRD)

1-Pole

2-Pole and 1-Pole

120V AC
120V AC

Requires One 1-Inch Space

Type BQ Quadplex Independent Trip (UL Type BRD)


120V AC
120/240V AC
120V AC

Requires Two 1-Inch Spaces

2-Pole

120/240V AC
120/240V AC

Requires Two 1-Inch Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

Ampere
Rating

10,000 AIC

10,000 AIC

10,000 AIC
120V AC
Catalog
Number

15-15
15-20
20-20
30-20

BD1515
BD1520
BD2020
BD3020

120V AC
List
Price

$35.20
35.20
35.20
35.20

120/240V AC

120V AC

Catalog
Number

Ampere Rating
Outer Left
1-Pole

Center
2-Poles
Independent
Trip

15
20
15
20
15
20
15
20

List
Price

Outer Right
1-Pole

20
20
30
30
40
40
50
50

15
20
15
20
15
20
15
20

BQ2202115
BQ2202120
BQ2302115
BQ2302120
BQ2402115
BQ2402120
BQ2502115
BQ2502120

120/240V AC

Catalog
Number

Ampere Rating
Outer
2-Poles
Independent
Trip

Center
2-Poles
Independent
Trip

15
20
20
20
20
25
30
30
30
40
40
50

15
20
30
40
50
25
30
40
50
40
50
50

$68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50

BQ215215
BQ220220
BQ220230
BQ220240
BQ220250
BQ225225
BQ230230
BQ230240
BQ230250
BQ240240
BQ240250
BQ250250

Wire Size
Range
Cu/Al
65C or
75C

List
Price

$68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50

Common Trip Quadplex Breakers


Class CTL 10,000 AIC All circuit breakers have rejection tab feature.
Type BQC Quadplex Common Trip Center Poles (UL Type BRD)

Type BQC Quadplex Common Trip Center and Outer Poles (UL Type BRD)

2-Pole and 1-Pole

2-Pole

120V AC
120/240V AC
120V AC

Requires Two 1-Inch Spaces

5 per Shelf Carton

10,000 AIC

Wire
Size
Range
Cu/Al
65C or
75C

10,000 AIC
120/240V AC

120V AC

Ampere Rating
Outer Left
1-Pole

120/240V AC

Requires Two 1-Inch Spaces

5 per Shelf Carton

120V AC

120/240V AC

Center 2-Poles
Common Trip

Catalog
Number

List
Price

Outer Right
1-Pole

120/240V AC

Catalog
Number

Ampere Rating
Outer 2-Poles
Common Trip

List
Price

Center 2-Poles
Common Trip

15
15
15
15
15

20
25
30
40
50

15
15
15
15
15

BQC2202115
BQC2252115
BQC2302115
BQC2402115
BQC2502115

$72.50
72.50
72.50
72.50
72.50

15
20
20
20
20

15
20
30
40
50

BQC215215
BQC220220
BQC220230
BQC220240
BQC220250

$79.00
79.00
79.00
79.00
79.00

#14-4

20
20
20
20
20
20

15
20
25
30
40
50

20
20
20
20
20
20

BQC2152120
BQC2202120
BQC2252120
BQC2302120
BQC2402120
BQC2502120

72.50
72.50
72.50
72.50
72.50
72.50

25
25
30
30
30

25
30
30
40
50

BQC225225
BQC225230
BQC230230
BQC230240
BQC230250

79.00
79.00
79.00
79.00
79.00

#14-4

30

50

20

BQC2502030

74.50

40
40
50

40
50
50

BQC240240
BQC240250
BQC250250

79.00
79.00
79.00

#14-4

All Type BD Duplex, BQ and BQC Quadplex


circuit breakers carry listing for HACR
applications.

CAT.73.01.T.E

All 15 and 20 ampere single poles are switchduty rated.

Discount Symbol 22CD

C-21

C-22

Cutler-Hammer

Type BR Loadcenters
Non-CTL Plug-On Circuit Breakers, BR Duplex, BR and BRD Quadplex

October 1998

Non-CTL Plug-On Replacement Circuit Breakers, Type BRD


10,000 Amperes Interrupting Capacity
120/240V AC
Non-CTL 10,000 AIC for
Replacement Purposes Only
For replacement in enclosures manufactured prior to 1968 with unnotched stabs.
Circuit breakers do not have rejection tab.
Type BR Duplex
1-Pole

BD1515

Type Brand BRD Quadplex Independent Trip


120V AC
120V AC

Requires One 1-Inch Space

2-Pole

Type BRD Quadplex Common Trip center and Outer Poles


2-Pole

120/240V AC
120/240V AC

Requires Two 1-Inch Spaces

120/240V AC

Requires Two 1-Inch Spaces

10 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

Ampere
Rating

10,000 AIC

10,000 AIC

10,000 AIC
120V AC
Catalog
Number

15-15
15-20
20-15
20-20
30-30

BR1515
BR1520
BR2015
BR2020
BR3030

120/240V AC
List
Price

$48.90
48.90
48.90
48.90
48.90

120/240V AC

Ampere Rating
Outer 2-Poles
Independent Trip
15
20
30
20
30
30

Important Note:
Type BD Duplex, BQ and BQC Quadplex
(CTL) circuit breakers conform to Section
384-15 of the latest National Electrical
Code. Install breaker only in panel positions that have notched bus stabs.

Wire Size
Range
Cu/Al
65C or
75C

120/240V AC

Catalog
Number

List
Price

Center 2-Poles
Independent Trip
15
20
30
30
40
50

Notched
Bus Stab

Unnotched
Bus Stab

120/240V AC

Outer 2-Poles
Common Trip
BR415
BR420
BR430
BRD220230
BRD230240
BRD230250

$87.00
87.00
87.00
87.00
87.00
87.00

Catalog
Number

Ampere Rating

15
30
30
30

List
Price

Center 2-Poles
Common Trip
15
30
40
50

BRDC215215
BRDC230230
BRDC230240
BRDC230250

$97.50
97.50
97.50
97.50

CTL Circuit
Limiting
Feature

Type BR or
Type BD Duplex, (CTL),
Type BQ and BQC Quadplex

#14-4

Type BD
Duplex
Rejection
Tab

Type BR

Notched
Stab

Non-CTL
Non-Circuit
Limiting

Type BR

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Special Applications Plug-On Circuit Breakers

October 1998

C-23

Plug-On Circuit Breakers, Types BJ and BJH


10,000/22,000 Amperes Interrupting Capacity
120/240V AC and 240V AC
For Use in 1-Phase and 3-Phase Loadcenters
150 Amperes and Above

Type BJ

Types BJ and BJH Breakers, 120/240 or 240V AC, 10,000, 22,000 AIC
Amperes

2-Pole
120/240V AC
Common Trip
Requires Four 1-Inch Spaces

3-Pole
240V AC
Common Trip
Requires Six 1-Inch Spaces

10 per Shelf Carton

5 per Shelf Carton

10,000 AIC

22,000 AIC

Catalog
Number
125
150
175
200
225

List
Price

BJ2125
BJ2150
BJ2175
BJ2200
BJ2225

Wire Size
Range
Cu/Al
60C or 75C

10,000 AIC

Catalog
Number

$264.00
264.00
264.00
264.00
264.00

List
Price

BJH2125
BJH2150
BJH2175
BJH2200
BJH2225

Catalog
Number

$620.00
620.00
620.00
620.00
620.00

22,000 AIC
List
Price

BJ3125
BJ3150
BJ3175
BJ3200
BJ3225

Catalog
Number

$745.00
745.00
745.00
745.00
745.00

List
Price

BJH3125
BJH3150
BJH3175
BJH3200
BJH3225

$1,045.00
1,045.00
1,045.00
1,045.00
1,045.00

#2-300 kcmil

Plug-On Special Application Circuit Breakers


10,000 Amperes Interrupting Capacity
120V AC, 120/240V AC and 240V AC

BRWH215
Water Heater Breaker

BRSN220
Switching Neutral Breaker

Special Application Circuit Breakers


Water Heater Breakers
2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Spaces

LINE
LOAD

With Isolated Line Terminals for


Separately Metered Water Heaters

Switching Neutral Breakers

240V Breakers

Non-Automatic Molded Case Switches

2-Pole
120V AC
Common Trip
NEUTRAL
Requires Two 1-Inch Spaces

2-Pole
240V AC
Common Trip
Requires Two 1-Inch Spaces

2-Pole
240V AC

Where Voltage to
Ground is 240V AC

For Use as Disconnect Contains No


Magnetic or Thermal Trip Properties

OUT
IN

With Switching Neutral


Pole for Gasoline Pump Applications

Requires Two 1-Inch Spaces

5 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

5 per Shelf Carton

10,000 AIC

10,000 AIC

10,000 AIC

5,000 AIC

Amperes
15
20
30

Catalog
Number
BRWH215
BRWH220
BRWH230

List
Price
$50.00
50.00
50.00

Amperes
15
20
25
30

If BJ or BJH breakers are used as a main


or a back feed device, a hold-down kit is
required. See page C-24.
Breaker uses two 1-Inch (25.4 mm) pole
spaces on left side and two 1-Inch (25.4 mm)
pole spaces on right side of loadcenter.

CAT.73.01.T.E

Catalog
Number
BRSN215
BRSN220
BRSN225
BRSN230

List
Price
$52.00
52.00
52.00
52.00

Amperes

Catalog
Number

List
Price

Amperes

Catalog
Number

List
Price

15
20
30
40
50

BR215H
BR220H
BR230H
BR240H
BR250H

$41.00
41.00
41.00
41.00
41.00

50

BR250NA

60
70
80
90
100

BR260H
BR270H
BR280H
BR290H
BR2100H

81.00
115.00
115.00
115.00
115.00

60

100

BR260NA

BR2100NA

Breaker uses three 1-Inch (25.4 mm) pole


spaces on left side and three 1-Inch (25.4 mm)
pole spaces on right side of loadcenter.
On the new black handle breaker add sufx
"B" to the catalog number and $4 to the list
price to obtain a tapped molded opening for
proper use with hold-down kits.

Wire Size
Range
Cu/Al
60C or
75C

#14-4

$39.40
39.40

#4-1/0

113.00

Discount Symbol 22CD

C-24

Cutler-Hammer

Type BR Loadcenters
Circuit Breaker Accessories

October 1998

Circuit Breaker Accessories


Field Installation Kits and Parts
Description
Handle Ties
Handle tie bar for physically joining the handles of two adjacent
1-pole Type BR Circuit Breakers. (Metal Cylinder Pin Type) . . . . . . .

Catalog
Number

List Price
Each

Ordering
Quantity

BHT

$ 3.30

10

THS1

Handle tie bar for joining two independent outside poles of


Types BQ and BQC Quadplex and outside poles of two Type BD
Duplex Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

THOW

3.10

10

Handle tie bar for joining two adjacent outside poles of Types BQ
and BQC Quadplex and outside poles of two Type BD Duplex
Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

THS1

2.10

10

Handle Lockoffs
Padlockable device for locking the handle of 1-, 2-, or 3-pole
Type BR Circuit Breakers and 1-pole of a Type BD Duplex or
one independent outside pole of a Type BQ or BQC Quadplex
Circuit Breakers. (Escutcheon Mounted) . . . . . . . . . . . . . . . . . . . . . .

BRLW

8.70

10

Padlockable device for locking the handle of a 1-pole Type BR


Circuit Breaker. (Handle Mounted) . . . . . . . . . . . . . . . . . . . . . . . . . .

BRLW1

14.00

10

Padlockable device for locking the handle of a 2- and 3-pole


Type BR Circuit Breaker. (Handle Mounted) . . . . . . . . . . . . . . . . . .

BRLW2

14.00

10

Padlockable device for locking the handle of a 1-pole Type BD


Duplex, BQ or BQC Quadplex Breaker. (Handle Mounted) . . . . . .

BRDL1

13.30

10

Padlockable device for locking the handle of the two center


poles of Type BQ and BQC Quadplex Circuit Breakers.
(Escutcheon Mounted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

BRQLW

11.90

10

Padlockable device for locking the handle of main circuit


breaker Types CC and CHH into the On or Off position.
(Screw Mounted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CCPL

20.30

Padlockable device for locking the handle of main breaker Types


BW and BWH into the On or Off position. (Escutcheon
Mounted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MCBPL

23.80

Handle Lockdogs
Device used to secure handle in On or Off position for 1-, 2-,
or 3-pole Type BR Circuit Breakers and 1-pole of Type BD Duplex
and one independent outside pole of Type BQ or BQC Quadplex
Circuit Breakers. (Escutcheon Mounted) . . . . . . . . . . . . . . . . . . . . . .

BHLW

8.00

10

Device used to secure handle in On or Off position for 1-pole


Type BR Circuit Breakers. (Handle Mounted) . . . . . . . . . . . . . . . . . .

BHLW1

8.00

10

Device used to secure handle in On or Off position for


2- and 3-pole Type BR Circuit Breakers. (Handle Mounted) . . . . .

BHLW2

8.00

10

Device used to secure handle in On or Off position for 1-pole


Type GFCB Ground Fault Circuit Breakers. (Handle Mounted) . . .

BHGW

7.70

10

Device used to secure handle in On or Off position for


one independent outside pole of Types BQ and BQC Quadplex or
1-pole Type BD Duplex Circuit Breakers. (Handle Mounted) . . . . .

HLW1

12.20

10

BRLW2

Hold-Down Kits
Hold-down retainer kit for 3-pole Type BR Circuit Breakers in
S3100SLN and S3100RN Loadcenters only. . . . . . . . . . . . . . . . . . . . .

BRHDB

1.40

Hold-down screw kit for 2- and 3-pole Type BR Circuit Breakers


in MLO Loadcenters through 125 amperes.. . . . . . . . . . . . . . . . . . . . .

BREQS125

3.40

Hold-down screw kit for 2- and 3-pole Type BR Circuit Breakers


in MLO Loadcenters 150 through 225 amperes. . . . . . . . . . . . . . . . . .

BRHDK125

7.90

Hold-down screw kit for 2-pole Types BJ and BJH Circuit


Breakers in MLO Loadcenters 125 through 225 amperes.. . . . . . . . .

BJHDS

10.90

Hold-down screw kit for 3-pole Types BJ and BJH Circuit


Breakers in MLO Loadcenters 125 through 225 amperes.. . . . . . . . .

BJHDS3P

13.20

Main Breaker Lug Kits


Types CC and CHH Main Breaker Lug Kit (2) 300 kcmil.. . . . . . . . . . .

CC1300

39.90

Types BW/BWH Main Breaker Lug Kit (2) 300 kcmil. . . . . . . . . . . . . .

MCBL300

41.00

Handle Ties: Typically used to join two similar independent single-pole breakers to form
a 2-pole noncommon trip breaker.
Handle Lockoffs: Devices that use a padlock
to lock the circuit breakers handle in the
On or Off position.
Handle Lockdogs: Devices that are used to
secure a circuit breakers handle in the On
or Off position. Handle Lockdogs are not
padlockable devices.
Hold-Down Kits: Devices used to secure the
circuit breaker to the loadcenter for back-feed
main application. See NEC Article 384-16(f).

BHLW2

BRQLW

BHLW

BREQS125

BRHDK125

THOW (Installed)

MCBPL (Installed)

Shunt Trips, Auxiliary and Alarm Contacts


Description

Catalog
Number

Shunt Trip for


Types BW/BWH
- 12 Volt . . . . . . . . . . . . . . . . . . . . . . . .
- 24 Volt . . . . . . . . . . . . . . . . . . . . . . . .
- 120 Volt . . . . . . . . . . . . . . . . . . . . . . .
Type BR
- 120 Volt . . . . . . . . . . . . . . . . . . . . . . .
Auxiliary Contact for
Types BW/BWH
- (1) N.O. and (1) N.C. . . . . . . . . . . . .
- (2) N.O. and (2) N.C. . . . . . . . . . . . .
Alarm Contact for
Types BW/BWH . . . . . . . . . . . . . . . . . . .
Alarm Contact for GFCB (1-Pole) . . . .
Type GFCB (1-Pole)
- (1) N.O. and (1) N.C. . . . . . . . . . . . .

Add Sufx:

Escutcheon Mounted: Device mounted semipermanently to the face of the circuit breaker
and secured by the loadcenter deadfront.
Handle Mounted: Device mounted directly
to the handle by the use of a set screw.
Screw Mounted: Device permanently
mounted to the face of the circuit breaker by
the use of a non-removable screw.
Must be purchased in multiples of ordering
quantities indicated.
Add sufx indicated to end of breaker
catalog number.
Add amount shown to circuit breaker list price.

List Price
Adder Each

$392.00
392.00
392.00

SR12
SR24
SR01
ST

121.60

AL1
AL2

170.00
334.00

CR1
W1

170.00
117.00

W2

117.00

Handle Position Changeability Chart.


Handle Lockoff
and Lockdog
Types

To Change Handle Position from


On to Off, or Off to On
You Must...
Remove
Padlock

Remove
Device

Remove
Loadcenter
Deadfront

Lockoff
Escutcheon Mounted

Remove

Lockoff Handle Mounted

Remove

Remove

Lockoff Screw Mounted

Remove

Lockdog
Escutcheon Mounted

N/A

Remove

Remove

Lockdog Handle Mounted

N/A

Remove

Discount Symbol 22CD


CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Box Sizes

October 1998

C-25

Residential/Commercial/New York City Loadcenters, Unit Enclosures Box Sizes


Dimensions in Inches (mm)
Residential Loadcenters
NEMA Type 1 Indoor
Box
Size

Residential Loadcenters
NEMA Type 3R Outdoor

Dimensions in Inches
Height

A1
B1
B2
C1
C2
C4
D1
G1
L1
L2
2
3
4
5
6
7
9

15
16-3/4
18-3/4
21
23
27
29-1/8
34-1/8
39
45
8-5/8
9-7/16
13
9-7/16
12
13
14-1/2

Width

Dimensions in mm
Depth

11-1/4
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
5
4-1/2
11
4-1/2
6-7/8
11
6-1/2

Height

3-3/4
3-7/8
3-7/8
3-7/8
3-7/8
3-7/8
3-7/8
3-7/8
3-7/8
3-7/8
3-1/2
3
3-9/16
3
4-1/2
3-9/16
3-1/2

381.0
425.3
476.1
533.2
584.0
685.5
739.5
866.4
990.2
1142.6
219.1
239.6
330.1
239.6
304.8
330.1
368.3

Width
285.8
363.4
363.4
363.4
363.4
363.4
363.4
363.4
363.4
363.4
127.0
114.3
279.3
114.3
174.6
279.3
165.1

Depth
95.3
98.4
98.4
98.4
98.4
98.4
98.4
98.4
98.4
98.4
88.9
76.2
90.5
76.2
114.3
90.5
88.9

Commercial Loadcenters
NEMA Type 1 Indoor
Box
Size
19
20
22
24

B1R
B2R
C3R
D1R
G1R
L1R
L2R
2R
3R
4R
5R
6R
7R
8R
9R

Dimensions in Inches
Height

Width

16-3/4
18-3/4
25
29-1/8
34-1/8
39
45
8-5/8
9-7/16
13
9-7/16
12
13
27
14-1/4

14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
14-5/16
5
4-1/2
11
4-1/2
6-7/8
11
10-1/2
6-1/2

Dimensions in mm

Depth

Height

5-3/16
5-3/16
5-3/16
5-3/16
5-3/16
5-3/16
5-3/16
3-1/2
3
3-9/16
3
4-1/2
3-9/16
4-3/4
4

Width

425.3
476.1
634.8
739.5
866.4
990.2
1142.6
219.0
239.6
330.1
239.6
304.8
330.1
685.5
362.0

363.4
363.4
363.4
363.4
363.4
363.4
363.4
127.0
114.3
279.3
114.3
174.6
279.3
266.6
165.1

Depth
131.8
131.8
131.8
131.8
131.8
131.8
131.8
88.9
76.2
90.5
76.2
114.3
90.5
120.6
101.6

Commercial Loadcenters
NEMA Type 3R Outdoor

Dimensions in Inches

Dimensions in mm

Height

Width

Depth

Height

16-5/32
16-5/32
16-7/32
16-7/32

6-1/4
6-1/4
6-5/16
6-5/16

1117.2
1117.2
1371.1
1688.4

Dimensions in Inches

Dimensions in mm

Height

Depth

Height

44
44
54
66-1/2

Box
Size

Width
410.2
410.2
411.8
411.8

Depth
158.7
158.7
160.3
160.3

Box
Size
42
43
46
47

Dimensions in Inches

Dimensions in mm

Height

Height

38
44
54
66-9/16

Width

Depth

16-5/16
16-5/16
16-5/16
16-5/16

6-3/8
6-3/8
6-3/8
6-3/8

Width

964.8
1117.2
1371.1
1690.0

414.2
414.2
414.2
414.2

Depth
161.9
161.9
161.9
161.9

New York City Loadcenters


NEMA Type 1 Indoor
Box
Size
A
B
C

Width

38
44
66-1/2

18-1/8
18-1/8
18-1/8

5
5
6-1/4

(965.2)
(1117.6)
(1689.1)

Width
(460.4)
(460.4)
(460.4)

Types CCM and CCB Unit Enclosures


NEMA Type 1 Indoor
Dimensions in mm

Height

Width

Height

23-1/4

8-7/8

4-1/2

590.3

Box sizes do not include covers/fronts.

CAT.73.01.T.E

(127.0)
(127.0)
(158.8)

Types CCM and CCB Unit Enclosures


NEMA Type 3R Outdoor

Dimensions in Inches
Depth

Depth

Width
225.3

Dimensions in Inches
Depth
114.3

Height
23-11/16

Width
9-5/16

Dimensions in mm
Depth
5-7/16

Height
601.4

Width
236.5

Depth
138.1

Cutler-Hammer

Type BR Loadcenters
Knockouts

C-26

October 1998

Residential Loadcenter Knockouts Dimensions in Inches (mm)


Mounting
Hole for
5/16 (7.9)
Screw

Residential NEMA Type 1 Indoor and NEMA Type 3R Outdoor Enclosures


Knockouts for Box Sizes A1, B1, B2, C1, C2, C4,
D1, G1, L1, L2, B1R, B2R, C3R, D1R, G1R, L1R,
L2R
Code
A

Diameter in Inches
1/2

1/2

1/2

Diameter in mm

3/4

1-1/4 1-1/2

1-1/4 1-1/2

12.7

12.7

19

2-1/2 12.7

Knockouts for Box Sizes 3, 4, 5, 6,


7, 9, 2R, 3R, 4R, 5R, 6R, 7R, 8R, 9R
Code Diameter in Inches
1/2

12.7

1/2

3/4

12.7 19.0

12.7 19.0 25.4

1/2

3/4

38.1

50.8

63.5

1/2

3/4

31.7

38.1

50.8

63.5

3/4

1-1/4

1-1/4 1-1/2 19.0 25.4 31.7 38.1

12.7

19.0

25.4

3/4

1/2

3/4

1-1/2

12.7

19.0

25.4

38.1

50.8

1-1/4 1-1/2

31.7

38.1

50.8

1-1/4 1-1/2

1-1/4 1-1/2 12.7

19.0

25.4

31.7

38.1

31.7

38.1

50.8

63.5

31.7

38.1

1/2

1-1/4 1-1/2

1-1/4 1-1/2

2-1/2 25.4

25.4

1-1/4 1-1/2

1/23/41
(12.719.025.4)

1/211-1/4
(12.725.431.7)

2-1/2

3/4

3/4

1/2

1-1/4 1-1/2

1-1/4 12.7 19.0 25.4 31.7

5/16 (7.9)

Diameter in mm

31.7

1/23/4
(12.719.0)
2-3/8
(60.3)

6-3/8
(161.9)

Box 2, 2R

11-1/4 KO
(25.431.7) KO

19.0 25.4 31.7

25.4 31.7 38.1

25.4 31.7 38.1 50.8

31.7 38.1 50.8

Box 3

C
A

F
2.060 (52.3) Dia.
(125A Max.)
3.062 (77.7) Dia.
(225A Max.)

Outdoor Boxes
B1R, B2R,
C3R, D1R, G1R,
L1R, L2R

Hub

A A A

B B

B
A

D
D

A
E

.450 (11.4) Dia. KO

A B B
B
B
B B

B B
B H
B

.450 (11.4) Dia. KO

A
A A A

D
A

G
A A A

B B

A A A

Box 4

B B

Box 4R

F
J

A A A

Box 3R
B

Hub

B
B

B
B

Box 5
B

A
H
A

Box 6

A A
B

B C

A A A
E

B B

Hub

A A A

E
D

G
E

B
A B

B B

B
B A
B

Box 5R
Hub

.450 (11.4) Dia. KO

.450 (11.4) Dia. KO

E
D

.450 (11.4) Dia. KO

F
B

A A A

A
H

B
B

.450 (11.4) Dia. KO

A A B B

A
H
A

B
B

B
B
B

Hub

B A
B
A
E

A B
B
A
E
D

.450 (11.4) Dia. KO


A A
E

I
B

B B

Hub

C
I

B
B
B

A
A A

A A

C B

B C

G
A

G
B

G
A

A
H

B
B

.450 (11.4) Dia. KO


B

B
B

A A A

Box 7R

D
E
A
B
A B

Box 7

A A

E
A
B
B A

B C

B B

C
A A A

.450 (11.4) Dia. KO


B

A A A

B C

Box 6R
.450 (11.4) Dia. KO

Indoor Boxes
C1, C2, C3, D1,
G1, L1, L2

B B

A A A

Indoor Boxes
B1, B2

Hub

Hub

Indoor Boxes
A1

E
A

Box 8R

Box 9

Box 9R

CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Knockouts

October 1998

C-27

Commercial Loadcenter Knockouts


Dimensions in Inches (mm)
A

B B
B B B

NEMA Type 1 Indoor Commercial Enclosures

B B
B B B

Knockouts for Box Sizes 19, 20, 22, 24


Code

Diameter in Inches

Diameter in mm

1/2

12.7

1/2

3/4

12.7

19.0

3/4

1-1/2

19.0

25.4

38.1

1-1/2

2-1/2

38.1

50.8

63.5

76.2

2-1/2

50.8

63.5

76.2

2-1/2

3-1/2

63.5

76.2

88.9

B B B
B B

B B B
B B

Box 19, 20

Box 22, 24

HUB

HUB

NEMA Type 3R Outdoor Commercial Enclosures


Knockouts for Box Sizes 42, 43, 46, 47
Code

Diameter in Inches

HUB

1/2

12.7

1/2

3/4

12.7

19.0

3/4

1-1/4

19.0

25.4

31.8

1-1/2

2-1/2

38.1

50.8

63.5

2-1/2

50.8

63.5

76.2

2-1/2

3-1/2

63.5

76.2

88.9

1-1/4

1-1/2

2-1/2

31.8

38.1

50.8

63.5

3-1/4 Sq.

82.5 Sq.

D
C

B B B
B B

C
G

Diameter in Inches

Diameter in mm

B B B
B B

Box 42

Unit Enclosure Knockouts, Types CCM and CCB Knockouts

Code

HUB

Diameter in mm

Box 43, 46, 47

HUB

NEMA Type 1 Indoor (Flush and Surface Trims)


A

1/2

12.7

1-1/4

1-1/2

1-3/4

2-1/2

31.7

38.1

44.5

50.8

63.5

NEMA Type 3R Outdoor


A

1/2

12.7

1-1/4

1-1/2

1-3/4

2-1/2

31.7

38.1

44.5

50.8

63.5

NEMA Type 1 Indoor

CAT.73.01.T.E

B
B

B
A

NEMA Type 3R Outdoor

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

C-28

October 1998

Wiring Diagrams
Figure 1

Figure 3

Figure 2

Insulated
Neutral
N

Insulated
Neutral

1
3

2
4

MAIN LUGS
A

3 4
B

EQUIP
GND
(When
Installed)

2
4

6
8

9
11

10
12

9
11

10
12

13
15

14
16

A
N

10

11

12

13

14

15
EQUIP.
GND
(When 17
Installed)

16

19

20

21

22

23

24

25

26

BONDING
STRAP

2
4

5
7

6
8

9
11

10
12

13
15

14
16

17
19

18
20 BONDING
STRAP
22
24

EQUIP.
GND
(When
Installed)

N
1

9
11

13
15

10
12 BONDING
STRAP
14
16

11

10
BONDING
STRAP
12

17
19

18
20

13

14

21
23

22
24

15

16

17
19

18
20

21
23

22
24

Figure 11
MAIN LUGS

MAIN CIRCUIT BREAKER

29

30

31

32

33

34

35

36

37

38

10

A
N

11

12

TYPE C, 1-POLE

B
1

10

11

12

N
INSULATED NEUTRAL

INSULATED NEUTRAL

4040

BONDING
STRAP

BONDING
STRAP

10

11
13

12 BONDING
STRAP
14

15
17

16
18
20
22

13

14

19
21

15

16

23
25

24
26

17
19

18
20

27
29

28
30

21
23

22
24

TYPE C, 1-POLE OR
TYPE A, 2-POLES

INSULATED NEUTRAL

28

Symbol Key

Figure 10

Figure 9

27

40

2424

39

EQUIP. GND
(When Installed)

2020

1616

18

1
3

21
23

MAIN LUGS

INSULATED NEUTRAL

INSULATED NEUTRAL

Figure 8
MAIN LUGS

INSULATED NEUTRAL

2
INSULATED NEUTRAL

EQUIP.
GND
(When
Installed)

MAIN LUGS

2
4
6
8

5
7

Figure 7

Figure 6
MAIN LUGS

Insulated
Neutral

1
3
5
7

EQUIP.
GND
(When
Installed)

Figure 5

Insulated
Neutral

1
3

6
8

5
7
1

Figure 4
MAIN LUGS

NOTCHED BUS STAB


SOLID BUS STAB
CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

C-29

Wiring Diagrams
Figure 12

Figure 13
MAIN LUGS
A

MAIN LUGS
A
B

5
7

6
8

9
11

10
12

13
15

14
16

17
19

18
20

21
23

22
24

25
27

26
28

29
31

30
32

OR
MAIN LUGS

1224

2040

1
3

2
4

5
7

6
8

9
11

10
12

13
15

14
16

17
19
21
23

18
20 BONDING
STRAP
22
24 1224

25
27

26
28

29
31

30
32

33
35

34
36

37
39

38
40

BONDING
STRAP

34
36
38
40

MAIN LUGS

N
INSULATED NEUTRAL

2
4

INSULATED NEUTRAL

1
3

EQUIP.
33
GND
35
(When
Installed)
37
39

Figure 15

Figure 14

MAIN CIRCUIT BREAKER

1632

2040

10

10

11

12

11

BONDING
12 STRAP

13

14

13

14

15

16

15

16

17

18

17

18

EQUIP.
GND
19
(When
Installed)
21
23

19

20

21

22

23

24

25
27

26
28

25

26

29
31

30
32

27

28

33
35

34
36

29

30

37
39

38
40

31

32

33

34

35

36

37

38

39

40

41

42

Figure 16

20
22
24

MAIN CIRCUIT BREAKER


A

10

11

12

13

14

INSULATED NEUTRAL

BONDING
STRAP

Figure 19

Figure 18

Figure 17

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

15

16

17

18

19

20

B
1
3

2
4
6
8

23

24

9
11

10
12

26

13
15

14 BONDING
STRAP
16

27

28

17
19

18
20

29

30

21
23

22
24

Symbol Key

TYPE C, 1-POLE

1224

816

2
4

5
7

6
8

9
11

10
12

13
15

14
16

FEED THRU LUGS

TYPE C, 1-POLE OR
TYPE A, 2-POLES

BONDING
STRAP

5
7

6
8

9
11

10
12

13
15

14
16

17
19

18
20

BONDING
STRAP

NOTCHED BUS STAB


SOLID BUS STAB

CAT.73.01.T.E

INSULATED
NEUTRAL

5
7

1
3

INSULATED
NEUTRAL

22

N
INSULATED
NEUTRAL

21

25

MAIN CIRCUIT BREAKER

C-30

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

Wiring Diagrams
Figure 20

Figure 22

Figure 21
A

MAIN LUGS
A
B

MAIN LUGS
B

Figure 23

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

A
2

10

11

12

13

14

BONDING
STRAP

B
3

7
9

8
10

11
13

12
14

15
17

16
18

10 BONDING

19
21

20
22

11

12

16

23
25

24
26

13

14

17

18

27
29

28
30

15

16

31
33

32
34

17

18

35
37

36
38

19

20

39
41

40
42

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

41

41

42

10

11

12

BONDING
STRAP

STRAP

15

19

INSULATED
NEUTRAL

INSULATED NEUTRAL

INSULATED NEUTRAL

1212

1616

2020

INSULATED NEUTRAL

Figure 24

Figure 27

Figure 26

Figure 25
MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

A
B

5
7

6
8

9
11

10
12 BONDING

13
15

14
16

STRAP

17
19

18
20

21
23

22
24

3
5

4
6

7
9

8
10

11
13

12
14

15
17

N
1

16
18 BONDING

10

19
21

20
22

11
13

12
14

23
25

24
26

15
17

27
29

29
30

TYPE C, 1-POLE

10

11

12

16
18

13

14

19
21

20
22

15

16

23
25

24
26

17

18

19
21

20
22

23
25

24
26

27
29

28
30

STRAP

27
29

Symbol Key

TYPE C, 1-POLE OR
TYPE A, 2-POLES

28
30

BONDING
STRAP

N
INSULATED NEUTRAL

INSULATED NEUTRAL

N
INSULATED NEUTRAL

INSULATED NEUTRAL

BONDING
STRAP

NOTCHED BUS STAB


SOLID BUS STAB
CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

C-31

Wiring Diagrams
Figure 28

Figure 29
MAIN CIRCUIT BREAKER
A

1
3

2
4

5
7

6
8

10

10

11

12

9
11

10
12

13
15

14
16

17
19

18
20

21
23

22
24

11

BONDING
12 STRAP

10

11

BONDING
12 STRAP

13

14

25
27

26
28

13

14

13

14

15

16

29
31

30
32

15

16

15

16

17

18

17

18

19

20

19

20

18

17

BONDING
STRAP

1632

34
36

33
35

19

20

21

22

21
23

22
24

21

22

23

24

25
27

26
28

23

24

25

26

29
31

30
32

25

26
28

38
40

37
39

2040

28

33
35

34
36

27

29

30

37
39

38
40

29

30

31

32

31

32

33

34

35

36

37

38

27

3030

Figure 33

34

MAIN LUGS

35

36

A B C

37

38
40

39

9
11

10 BONDING
12 STRAP

3
5

4
6

13
15

14
16

7
9

8
10

17
19

18
20

11
13

12
14

1
3

2
4

5
7

6
8

9
11

10
12

4040

39

40

41

42

MAIN LUGS
A B C

Figure 35
MAIN LUGS
A B C

21
23

22
24

15
17

16
18

25
27

26
28

19
21

20
22

29
31

30
32

23
25

24
26

13
15

14
16

33

34

27
29

28
30

17
19

18 BONDING
20 STRAP

35

36

31
33

32
34

21
23

22
24

37

38

37
38

38
40

25
27

26
28

39

40

39

41

29
31

30
32

41

42

41

42

33
35

34
36

TYPE C, 1-POLE

TYPE C, 1-POLE OR
TYPE A, 2-POLES

BONDING
STRAP

1224

1836

NOTCHED BUS STAB


SOLID BUS STAB

CAT.73.01.T.E

BONDING
STRAP

INSULATED NEUTRAL

Symbol Key

INSULATED NEUTRAL

Figure 34

INSULATED NEUTRAL

Figure 32

INSULATED NEUTRAL

33

N
INSULATED NEUTRAL

INSULATED NEUTRAL

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

INSULATED NEUTRAL

INSULATED NEUTRAL

Figure 31

Figure 30

MAIN CIRCUIT BREAKER

C-32

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

Wiring Diagrams
Figure 36

Figure 37

MAIN CIRCUIT BREAKER


A

MAIN LUGS

A B C

A B C

5
1

MAIN LUGS
N

INSULATED NEUTRAL

Figure 39

Figure 38
MAIN LUGS

7
9

8
10

11
13

12
14

15
17

16
18

A B C

10

11

12

11

10 BONDING
STRAPS

12

10

13

14

19
21

20
22

13

14

11

12

15

16

23
25

24
26

15

16

13

14

17

18

27
29

28
30

17

18

15

16

19

20

32
34

20

18

31
33

19

17

21

22

36
38

22

20

35
37

21

19

23

24

23

24

24

25

26

25

26

25

26

27

28

27

28

27

28

29

30

29

30

29

30

31

32

31

32

33

34

33

34

35

36

21

22

23

40
42

39
41

INSULATED NEUTRAL

35

36

37

38
40

39

42

41

31

32

33

34

35

Figure 40
MAIN LUGS

36

A B C
37

37

38

40

1
3

2
4

39

40

42

5
7

6
8

41

42

9
11

10
12

13
15

14
16

17
19

18
20

21
23

22
24

25
27

26
28

29
31

30
32

33
35

34
36

38

39
41

INSULATED NEUTRAL

INSULATED NEUTRAL

INSULATED NEUTRAL

Two bonding straps provided on 225 ampere loadcenters only.

Symbol Key

TYPE C, 1-POLE

TYPE C, 1-POLE OR
TYPE A, 2-POLES

NOTCHED BUS STAB


SOLID BUS STAB
CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

C-33

Wiring Diagrams
Figure 42

Figure 41
MAIN BREAKER
A B C

MAIN LUGS

MAIN BREAKER

A B C

Figure 44

Figure 43
MAIN BREAKER
N

4
6

INSULATED NEUTRAL

INSULATED NEUTRAL

BONDING
STRAP

1
3

2
4

5
7

6
8

9
11

10
12

13
15

14
16

17
19

18
20

21
23

22
24

BONDING
STRAPS

10
12

10

10

13
15

14
16

11

12

11

12

17
19

18
20

13

14

13

14

21
23

22
24

15

16

15

16

25
27

26
28

17

18

17

18

29
31

30
32

19

20

19

20

33

34

21

22

21

22

35

36

23

24

23

24

37

38

25

26

25

26

39

40

27

28

27

28

41

42

29

30

29

30

31

32

31

32

33

34

33

34

35

36

35

36

37

38

37

38

39

40

39

40

41

42

41

42

MAIN CIRCUIT BREAKER OR MAIN LUG BLOCK

9
11

Figure 45

A B C

INSULATED NEUTRAL

Figure 46
MAIN CIRCUIT BREAKER
A

B
BONDED
NEUTRAL

N
2

9
11
13
15

10
12
BONDING
14 STRAP
16

17
19

18
20

21
23

22
24

INSULATED NEUTRAL

1
2
3
4
INSULATED NEUTRAL

5
6
7
8

FEED THRU LUGS

Two bonding straps provided on 225 ampere loadcenters only.

Symbol Key

TYPE C, 1-POLE

TYPE C, 1-POLE OR
TYPE A, 2-POLES

NOTCHED BUS STAB


SOLID BUS STAB

CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

C-34

October 1998

Wiring Diagrams
Figure 48

Figure 47
MAIN CIRCUIT BREAKER
A

B
A

10

11

12

13

14

15

16

17

18

19

20

23

24

25

26

27

28

BONDING
STRAP

7
9

8
BONDING
STRAP
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

1
3

2
4

5
7

6
8

9
11

10
12

13
15

25

26

27

28

29

30

17
19

14
16
BONDING
18 STRAP
20

21
23

22
24

11

10
BONDING
STRAP
12

13

14

15

16

17
19

18
20

21
23

22
24

Figure 54

Figure 53
A

MAIN CIRCUIT BREAKER


A B C

OR
MAIN LUGS

34

35

36

10

11

12

13

14

15

16

17

18

40

39

Figure 52

Figure 51
MAIN
CIRCUIT OR
BREAKER
A

MAIN CIRCUIT BREAKER

MAIN
LUG
BLOCK

5
7

6
8

9
11

10
12

13
15

14
16

17
19

BONDING
18 STRAP
20

21
23

22
24

Symbol Key

OR
MAIN LUGS
A
B
1
3

2
4

5
7

6
8

9
11

10
12

13
15

14
16

FEED THRU LUGS

TYPE C, 1-POLE

N
INSULATED NEUTRAL

2
4

INSULATED NEUTRAL

1
3

19

20

21
23

22
24

25
27

26
28

29
31

30
32

33
35

34
36

37
39

38
40

BONDING
STRAP

INSULATED NEUTRAL

38

37

9
11

10
12

13
15

14
16

17
19

18
20

21
23

22
24

25
27

26
28

29
31

30
32

33

34

35

36

37

38

39

40

41

42

N
INSULATED NEUTRAL

33

32
1

31

MAIN
LUG
BLOCK

OR

30

29

MAIN
CIRCUIT
BREAKER

MAIN CIRCUIT BREAKER

22

21

OR

INSULATED NEUTRAL

INSULATED NEUTRAL

Figure 50
MAIN
LUG
BLOCK

INSULATED NEUTRAL

MAIN
CIRCUIT
BREAKER

INSULATED NEUTRAL

OR
MAIN LUGS
A

Figure 49

MAIN
MAIN
CIRCUIT OR LUG
BREAKER
BLOCK

BONDING
STRAP

TYPE C, 1-POLE OR
TYPE A, 2-POLES

NOTCHED BUS STAB


SOLID BUS STAB
CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

C-35

Wiring Diagrams
Figure 55

Figure 56
A

Figure 57

Figure 58

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

A B C

A B C

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

1
N

30

31

32

33

34

35

36

37

38

39

40

41

42

10

11

12

13

14

10

11

12

10

13

14

11

12

15

16

17

18

INSULATED NEUTRAL

INSULATED NEUTRAL

29

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

Figure 59

INSULATED NEUTRAL

INSULATED NEUTRAL

13

14

15

16

19

20

17

18

21

22

19

20

23

24

21

22

25

26

23

24

27

28

25

26

29

30

27

28

31

32

29

30

33

34

31

32

35

36

33

34

37

38

35

36

39

40

37

38

41

42

39

40

41

42

Figure 60

MAIN CIRCUIT BREAKER

MAIN CIRCUIT BREAKER

B
1
3

2
4

10
12

13
15

14
16

17
19

18
20

BONDING
STRAP

10

11

12

13
15

14
16

17
19

18
20

N
INSULATED
NEUTRAL

6
8

9
11

INSULATED
NEUTRAL

5
7

BONDING
STRAP

FEED THRU LUGS

Symbol Key

TYPE C, 1-POLE

TYPE C, 1-POLE OR
TYPE A, 2-POLES

NOTCHED BUS STAB


SOLID BUS STAB

CAT.73.01.T.E

C-36

Cutler-Hammer

Type BR Loadcenters
Wiring Diagrams

October 1998

Wiring Diagrams
Figure 62

Figure 61

3
5

4
6

7
9

8
10

11
13

12
14

15
17

16
18

19
21

20
22

23
25
27
29

1
3

2
4

9
11

10
12

13
15

14
16

24
26

17
19

18
20

28
30

21
23

22
24

BONDING
STRAP

5
7

6
8

9
11

10
12

13
15

14
16

BONDING
STRAP

FEED THRU LUGS

9
11

10
12

13
15

14 BONDING
16 STRAP

17
19

18
20

25
27

26
28

21
23

22
24

29
31

30
32

25
27

26
28

33
35

34
36

29
31

30
32

37
39

38
40

33
35

34
36

37
39

38
40

Figure 65
MAIN CIRCUIT BREAKER

N
INSULATED NEUTRAL

INSULATED NEUTRAL

MAIN LUGS

INSULATED
NEUTRAL

Figure 64
MAIN LUGS

INSULATED NEUTRAL

Figure 63
MAIN LUGS

MAIN CIRCUIT BREAKER


A
B

BONDING
STRAP

A
B
N
C

GROUND

Symbol Key

4 5

TYPE C, 1-POLE

2
4

5
7

6
8

9
11

10
12

13
15

14
16

17
19

18
20

9
10

21
23

22
24

11
12

BONDING
STRAP

TYPE C, 1-POLE OR
TYPE A, 2-POLES

Figure 67
MAIN
CIRCUIT
BREAKER

1
2

13
14

3
4

15
16

5
6

17
18

7
8

19
20

N
INSULATED NEUTRAL

2 3

NEUTRAL

1 1
1
1
MAIN

INSULATED NEUTRAL

Figure 66

1
3

NOTCHED BUS STAB


SOLID BUS STAB
CAT.73.01.T.E

Cutler-Hammer

Type BR Loadcenters
Typical Specifications

October 1998

C-37

Typical Specications
General
A. The Contractor shall furnish and
install deadfront loadcenters incorporating circuit breakers of the number,
rating and type as specied herein and
as shown on the contract drawings.
B. The loadcenter and all components
shall be designed, manufactured and
tested in accordance with the latest
applicable standards of UL, NEMA
and NEC including:
1. UL 67 Standards for Panelboards.
2. UL 50 Standards for Cabinets and
Boxes.
3. UL 489 Standards for Molded Case
Circuit Breakers.
4. UL 869 Standards for Service
Equipment.
5. Federal Specication W-C 375B
Circuit Breakers.
6. Federal Specication W-C P115b
Panel Power Distribution Type 1,
Class 2.
Qualications
A. The manufacturer of the loadcenter
shall be the manufacturer of the
circuit breaker within the loadcenter.
B. For the equipment specied herein,
the manufacturer shall be ISO 9000
certied.
C. The manufacturer of this equipment
shall have produced similar electrical
equipment for a minimum period of
seven (7) years.
Manufacturers
A. Cutler-Hammer.
Ratings
A. Loadcenters shall be rated for 120/
240V AC and shall have short circuit
ratings as shown on the drawings or
as herein scheduled, but not less than
10,000 amperes RMS symmetrical.
B. Circuit breakers shall be a minimum
of 125 ampere frame. Circuit breakers
15 through 125 amperes trip size shall
take up the same pole spacing.
C. Loadcenters shall be labeled with a
UL short circuit rating. When series
combination ratings are applied with
integral or remote upstream devices,
a label shall be provided. Series combination ratings shall cover all trip
ratings of installed frames. It shall

Note to spec writer select one (copper


available in limited ratings)

CAT.73.01.T.E

state the conditions of the UL series


ratings including:
1. Size and type of upstream device.
2. Branch devices that can be used.
3. UL series short circuit rating.
Construction
A. All interiors, with the exception of the
branch circuit breakers, shall be completely factory assembled with main
breakers, main lugs, or no main device.
B. Interiors shall be designed so that circuit breakers can be replaced without
disturbing adjacent units and without
removing the main bus connectors
and shall be designed so that circuits
may be changed without machining,
drilling, or tapping.
C. Physical means shall be provided to
prevent the installation of more overcurrent devices than that number for
which the enclosure was designed,
rated, and approved. Half-size breakers shall have a UL listed rejection tab
over the line terminals. Loadcenter
interiors must have notched stabs to
accept these rejection tab class CTL
breakers, if required and approved.
Bus
A. Bus bars for the main and cross connectors shall be [tin-plated aluminum] [copper] in accordance with
Underwriters Laboratories standards. Bussing shall be braced
throughout to conform to industry
standard practice governing short
circuit stresses in loadcenters.
B. Neutral bussing shall have a suitable
lug for each outgoing feeder requiring a neutral connection of same
ampacity as branch.
Wiring/Termination
A. All wire connectors and terminals shall
be of the anti-turn solderless type and
shall be suitable for copper or aluminum wire of the sizes indicated. All
connectors must meet the Requirements for Wire Connectors and Soldering Lugs as stated in UL 486B.
B. All loadcenters where marked shall
be suitable for use with 60C or 75C
rated wire.
Circuit Breakers
A. Circuit breakers shall be molded case
type. Circuit breakers shall have fourrivet construction (GFI Type 5 rivets).
Multipole circuit breakers shall be of a
stack pole design to provide electrical
phase isolation.

B. Each pole of the circuit breaker will


provide inverse time delay overload
and instantaneous short circuit protection by means of both thermal and
magnetic sensors.
C. The circuit breaker calibration shall
not be affected by environmental
changes in relative humidity. The thermal bimetal element shall be welded
to the steel frame and calibration shall
be set independent of the molded case
by computer controlled equipment.
D. All circuit breakers shall be operated
by a toggle-type handle and multipole
circuit breakers shall have an internal
common trip mechanism. The circuit
breakers shall incorporate trip mechanisms that are mechanically trip-free
from the handle. The handle position
shall provide visual trip indication.
E. Contacts shall be of non-welding
silver alloy.
F. All circuit breakers shall have the trip
rating inscribed on the handle on each
circuit breaker pole. Also, unique
color-coded cases that indicate the UL
listed 10 kA or 22 kA interrupting ratings. Breakers shall be able to be used
as main or branch disconnect devices.
G. Branch circuit breakers may also be
used in the 1/2-inch (12.7 mm) per pole
ratings that include 2-pole 1-inch
(25.4 mm) wide modules and 4-pole
2-inch (50.8 mm) wide modules. 2-pole
circuit breakers must incorporate a
common trip mechanism. The exclusive CTL rejection tab feature shall be
provided to limit the number of branch
devices for a loadcenter to 42, in compliance with NEC Article 384-15.
H. Circuit breakers shall be completely
enclosed in a molded case of thermoset
material. No internal aluminum parts
shall be used. All internal ferrous parts
shall be plated to prevent corrosion.
I. All terminals shall be listed for use
with copper or aluminum conductors.
Terminals shall be of the box lug or
clamp type design. The terminals
shall meet UL 486B requirements and
shall be suitable for use with either
60C or 75C wire.
J. The calibrated bimetal assembly shall
be mechanically isolated from the
load terminal using a exible braided
copper shunt wire, such that movement of the terminals due to twisting
and overtorquing does not affect
breaker calibration.
K. Breakers shall be SWD rated and/or
HACR rated as required.

C-38

Cutler-Hammer

Type BR Loadcenters
Typical Specifications

October 1998

Typical Specications, Continued


L. Arc Fault Interrupting circuit breakers,
(AFI), shall be provided on all 15 and
20 ampere single-phase 120/240V AC
circuits except those indicated as
remote controlled breakers. AFI
breakers shall be Classied for mitigating the effects of arcing faults, or
conforming to UL Standard 1699 and
as dened by Article 210-12
Section A of the 1999 NEC Code.

common point of grounding for all


connected power, telephone, and
coaxial incoming conductors. The
device shall provide, as a minimum,
the following protection:
1. Up to 39 kA surge current protection per phase for transients on the
incoming AC line
2. Up to 10 kA surge protection per
pair for telephone lines

Surge Protection Devices


All 120/240V AC single-phase loadcenters shall have surge protection
provided by a [Clipper Home Surge
Protector device] [plug-in surge
protection device].
A. The Clipper Home Surge Protector
shall be supplied in its own rugged
steel enclosure and must be suitable
for ush or surface mounting external of the loadcenter. The device shall
provide surge protection for the loadcenter as well as protection for: two
incoming telephone lines and one
incoming coaxial cable. The surge
protector shall be installed in accordance to NEC Article 280 and be
listed under UL1449, (2nd Edition),
and UL497A. The units shall be CSA
certied and be tested to meet ANSI/
IEEE Category B3 and C3 levels. The
surge protector shall incorporate a
surge plane design to facilitate a

3. Up to 5 kA line to shield (ground)


protection for coaxial conductors
OR
A. The surge protection device shall be
capable of plugging onto a maximum
of two adjacent spaces in a singlephase loadcenter. The device shall provide, as a minimum, up to 10 kA surge
current protection per phase for transients on the incoming AC line.
B. Surge protection devices must be
equipped with LEDs to indicate proper
functioning of the internal electronics.
Enclosures
A. Loadcenter shall have NEMA Type 1
general purpose or NEMA Type 3R
rainproof enclosures as indicated on
the drawings and shall be surface or
combination ush/surface mounted
except where noted.
B. Boxes shall be made from galvanized
sheet steel having multiple knockouts.
Rainproof boxes shall use galvanized
steel or an approved coating system
which meets or exceeds standards for

outdoor NEMA Type 3R enclosures.


Boxes shall be of sufcient size to provide at least a minimum code gutter
space on all sides.
C. The deadfront shall have an easy
adjustment feature for ush
applications.
D. Boxes shall be factory assembled into
a single rigid structure.
E. Unless otherwise noted on drawings,
hinged doors covering all circuit
breaker handles shall be included in
all trims. Trim doors shall not uncover
any live parts in making the circuit
breaker handles accessible. If key
locks are required, all locks shall be
keyed alike.
F. Combination trims for ush and
surface panels shall be at and shall
overlap the box by at least 5/8-inch
(15.9 mm) all around. Trims shall be
mounted by a screwdriver without
the need for special tools.
Finish
A. Trims shall be bonderized and
nished with a light gray ANSI-61
enamel. The paint nish shall be of
a type to which eld applied paint
will adhere.
Factory Testing
A. The standard factory tests shall
be performed on the equipment
provided under this section. All
tests shall be in accordance with
the latest version of UL and NEMA.

CAT.73.01.T.E