You are on page 1of 11

Sensors Technical

461

white | wiring devices

technical hotline +44 (0)1268 563720

Simple Fit PIRs


Technical specification
Maximum recommended mounting height:
1.8m to 3m

Range:
##""##!    

!""!""##""    


  !""!
Cone-shaped detection pattern,
5m radius at 2.5m mounting height

K5015
Operating voltage:
Specification
AC220~240V/50Hz
Recommended circuit protection:
Power
requirement
16A

K5016

Specification

Description

AC 220 ~ MK
240V
50Hz
requirement
AC
220 ~
/ 50Hz
Simple/Power
Fit
Sensors
offer cost effective presence
detection
for 240V
lighting control
in small to medium
areas. This one-box solution is easy to install and commission, and requires no additional parts.

Maximum load:
Lighting
load (Max)
6A or 1500W
fluorescent/incandescent
Lighting
load
(Max)
6A or 1500W fluorescent/incandescen
The following
versions are
available:
6A or 1500W fluorescent/incadescent lightling load
capacity
lighting load
capability
load
capability
Flush mounted K5015 - Spring Clips enable easelighting
of installation
in plasterboard
ceilings
Photocell:

Approx. 30~200angle
Lux
Detection
Off delay:

5sec - 40min range


Detection
Colour:
White

Mounting height
Material:
Flame retardant PC

Mounting type
IP rating:
IP20

Surface Mounted K5016 - Screw and Plug Fixings can be mounted direct to the ceiling or on to a
Up to 360 at
25C
at 2.5mangle
Up to 360 at 25C at 2.5m
square Detection
pattress box (K2160
WHI)

5m radiusFeatures
at 2.5m
mounting
height
Detection
range

5m radius at 2.5m mounting height

Recommended ceiling
height
1.8m by
topassive
3m Recommended
Mounting
height
Advanced
presence
detection
infrared (PIR) technologyceiling height 1.8m to 3
Flush mount

Mounting type

Flush mount

Isolation switch control

AUTO/OFF

Passive photocell holds lights off when area becomes occupied in bright ambient conditions

Isolation switch control

AUTO/OFF

K5015
Time
adjustment
Depth required behind ceiling:

Off delay in minutes following the last observed movement after which lights switch off
Adjustable 50-40seconds
~ 40 minutes
Time adjustment
Adjustable 5 seconds ~ 40 minutes

100mm

Lux
adjustment
Weight:
105g excluding cable

Warm up time

Detection
pattern and approx
Approx. 30 ~ 200
Luxadjustment
Lux

10m

range inApprox.
metres at 30
floor~level
for Lux
2.5m mounting height
200
(detection pattern is cone shaped).

About 1 minute Warm up time

About 1 minute

Protection degree

IP20

IP20

Safety

CE

K5016
Weight:
105g approx

Dimensions

Protection degree
K5015
Safety

Product Dimensions

CE

K5016

Product Dimensions
86
mm

76
mm

11

86
mm

76
mm

54.5
mm

86
mm

11

462

Sensors Technical

wiring devices | white

www.mkelectric.co.uk

Standard PIRs
Technical specification
Maximum recommended mounting height:
3.0m
Range:
Cone-shaped detection pattern,
diameter (at floor level) = 2.4 x mounting height

K4011
2.5m

6.0m

Operating voltage:
230V 50Hz
Recommended circuit protection:
10 Amps
Maximum load:
6 Amps resistive or fluorescent
Photocell:
Adjustable 50-5000 lux
Off delay:
20 minutes (fixed) and a 10 second Walk Test Mode
(need K4050 or K4053 to put it in a Walk test mode)
Colour:
White

K4010

Description
Standard PIRs are part of a comprehensive range of presence detection systems designed to control any
type of lighting load, particularly modular luminaires.
They provide simple, cost-effective presence detection for lighting control in small areas.
The following versions are available:

Slimline flush K4010

Surface mounted K4011

Features
Advanced presence detection by passive infrared (PIR) technology

Material:
Flame retardant PC/ABS
IP rating:
K4010: IP4X
K4011: IP3X
K4010
Depth required behind ceiling:
125mm
Weight:
Flush 70g excluding cable
Surface 200g approx
K4011
Weight:
200g approx

Passive photocell holds lights off when area becomes occupied in bright ambient conditions

20

6m

Off delay in minutes following the last observed movement after which lights switch off
Detection pattern and approx range in metres at floor level for 2.5m mounting height
(detection pattern is cone shaped).
Hand-held Controllers (K4051 and K4052) provide local user override

Dimensions
K4010 flush detector

K4011 surface detector

62mm
deep
10mm
deep

115mm

65mm

100mm

Sensors Technical

463

white | wiring devices

technical hotline +44 (0)1268 563720

Superior PIRs
Technical specification
Maximum recommended mounting height:
3.0m
Range:
Cone-shaped detection pattern,
diameter (at floor level) = 2.4 x mounting height

K4016
2.5m

6.0m

Off delay:
1 minute 96 hours (5-35 mins via K4050) and
10 second Walk Test Mode. (Off Delay 1 & 2 on K4017
and K4018 are independently adjustable.)

K4015

Features
Presence detection is by passive infrared, effectively enhanced to improve sensitivity to small
movements

Photocell:
Adjustable 50-5000 lux

Passive photocell holds lights off in bright ambient conditions. Active photocell has the
capability to switch lights off in occupied areas

Operating voltage:
230V 50Hz
Recommended circuit protection:
10 Amps
Maximum load:
6 Amps per output (not exceeding 10A in total) only in
dual circuit option
Colour:
White
Material:
Flame retardant PC/ABS

Off delay in minutes following the last observed movement after which the lights switch off
(1 minute to 96 hours via K4053)

6m

Detection pattern and approx range in metres at floor level for 2.5m mounting height
(detection pattern is cone shaped).
Dual-circuit option (1 x volt-free, 1 x switched-live output: K4017 & K4018 only). Switched-live
influenced by photocell, volt-free output by presence detection only. Independent time delays
can be programmed via K4050 or K4053

Weight:
Flush 70g excluding cable
Surface 200g approx

Hand-held Controllers (K4051 and K4052) provide local user override

IP rating:
K4015: IP4X
K4016: IP3X

Remote programming via K4050 or K4053 ensures changes can be easily accommodated
(Note that not all options are available when using HP10)

Description
Superior PIRs are part of a comprehensive range
of presence detection systems designed to control
modular luminaires with high frequency ballasts,
and other lighting loads.

Washroom mode. If no movement is detected in a 24-hour period, detector can be


programmed to switch the load on for the duration of the off delay. With suitable valve unit
can be used as urinal control

Dimensions
Brown Live In
Black Live Out
Blue Neutral
Green/Yellow Earth
(no internal connection)

They offer high-performance, programmable


presence detection for lighting control in offices
and open-plan workstations. Available in flush
and surface mount versions with single or dual
circuit options.

65mm

62mm
deep
10mm
deep

Suitable for flush mounting in a


suspended ceiling tile, maximum
115mm
100mm
54mm thick and with a minimum
clearance of 125mm between front
The housing may be secured to a
surface of tile and hard ceiling behind. hard surface or a BESA box. The
detector fits into the housing with
Cut a 50mm diameter (K4054
a simple bayonet action.
plasterboard fixing kit) circular hole
in the ceiling tile, feed the flying lead
and detector through and secure into
position with the locking ring.

464

Sensors Technical

wiring devices | white

www.mkelectric.co.uk

Superior PIRs for DSI


Technical specification
Maximum recommended mounting height:
3.0m
Range:
Cone-shaped detection pattern,
diameter (at floor level) = 2.4 x mounting height

K4020
2.5m

6.0m

Photocell:
Regulating

K4019

Features

Operating voltage:
230V 50Hz

Presence detection is by passive infrared, effectively enhanced to improve sensitivity to small


movements

Recommended circuit protection:


10 Amps

Regulating photocell ensures a minimum maintained light level, taking account of the
contribution from adjacent luminaires and daylight

Capacity:
K4019 9 ballasts
K4020 25 ballasts

Incorporates simple scene-setting - up to six scenes can be set via user remote

Output:
Digital DSI

Off delay in minutes following the last observed movement after which the lights switch off
(1 minute to 96 hours via K4053)

Colour:
White
Material:
Flame retardant PC/ABS
Weight:
Flush 70g excluding cable
Surface 200g approx
IP rating:
K4019: IP4X
K4020: IP3X

Description
Superior Self Regulating PIRs offer high
performance, programmable presence detection
for lighting control for work stations and offices.
It is designed to control groups of luminaires by
regulating DSI type ballasts.

6m

Detection pattern and approx range in metres at floor level for 2.5m mounting height
(detection pattern is cone shaped)
Hand-held Controllers (K4051 and K4052) provide local user override

Remote programming via K4050 or K4053 ensures changes can be easily accommodated

OneSwitch Dimming. Manual input to adjust light level or turn luminaires on or off

Dimensions
Supply L
230V N
50Hz

Brown
Blue
Orange
White

Red

62mm
deep
10mm
deep

Push-to-Make
Mains-Rated
Retractive Switch
OneSwitchTM
Input

100mm

115mm

Supplied with 3m cable

65mm

Sensors Technical

465

white | wiring devices

technical hotline +44 (0)1268 563720

Battenfit Sensors
Technical specification
Maximum recommended mounting height:
5.0m
Range:
Cone-shaped detection pattern,
diameter (at floor level) = 2.4 x mounting height

K4041, K4042, K4043, K4044

2.5m

Features

6.0m

Advanced presence detection by passive infrared (PIR) technology

Off delay:
1 minute 96 hours (5-35 mins via K4050) and
10 second Walk Test Mode. (Off Delay 1 & 2 on K4017
and K4018 are independently adjustable.)

5-35

Photocell:
Adjustable 50-5000 lux

Operating voltage:
230V 50Hz

Recommended circuit protection:


10 Amps

5m

Maximum load:
2A for K4041 and K4042
25 ballast for K4043 and K4044

Off delay in hours following the last observed movement after which lights switch off. Up to
96 hours with K4053. (K4042, K4043 and K4044 only) Fixed 20 minutes off delay with K4051
Passive photocell holds lights off in bright ambient conditions. Active photocell has the
capability to switch lights off in occupied areas (K4042 only)
Regulating photocell adjusts luminaire output to maintain constant light levels
(K4043 and K4044 only)
Detection pattern and range in meters under normal operating conditions
One Switch Dimming. Manual input to adjust light level or turn luminaires on or off
(K4043 and K4044 only)

Colour:
White
Material:
Flame retardant PC/ABS

Hand-held Controllers (K4051 and K4052) provide local user override

Weight:
100g

Infrared programming enables easy commissioning and re-commissioning

IP rating:
4X

Dual circuit option (switching or digital dimming) available (K4043 and K4044 only)
Scene setting lights switch on to a pre-programmed scene when area becomes occupied
(K4043 and K4044 only)

Description

Plan View
o
Detection pattern is a 360
cone shape. Diameter is
2.25 x the mounting height.

29

Dimensions (mm)

Detection Profile

14

M20 x 1.5

A range of simple to fit batten-mounted sensors


which can deliver energy savings of up to 50%.
The BattenFit sensor is a simple-to-fit control
solution for batten style luminaires.

The squares show the


arrangement of the detection
pattern. Sensitivity is greater
when approaching at a
tangent rather than heading
towards the centre.

BATTEN LUMINAIRE

14
2.5m
o

97
2.5m

5m

Direction of most
commonly used
entry into detection
zone, i.e. start of
corridor or doorway

DETECTION ZONE
5m

40

107

5.6m

600

466

Sensors Technical

wiring devices | white

www.mkelectric.co.uk

Digital Sensors Ceiling Mounted


Technical specification
Maximum recommended mounting height:
3.0m
Range:
Approx 7m dia at 2.4m ceiling height

K4025

2.4m

7.0m

Off delay:
5-60 minutes adjustable

Features
Active presence detection by microwave technology

Photocell:
Adjustable 50-5000 lux
Operating voltage:
230V 50Hz

Regulating photocell actively monitors ambient light levels and adjusts the light output
accordingly (dimmable control gear only)

Recommended circuit protection:


10 Amps

Incorporates simple scene-setting - up to six scenes can be set via user remote

Maximum load (VOLT-FREE):


6 Amps

Off delay in minutes following the last observed movement after which the lights switch off (1
minute to 96 hours via K4053)

Maximum load (DSI):


25 ballasts
Colour:
White
Material:
Flame retardant PC/ABS
Weight:
300g
IP rating:
IP3X

7m

Detection pattern and range in metres under normal operating conditions


Dual circuit control. Digital output always influenced by photocell, relay output can be
influenced by photocell if configured
Hand-held Controllers (K4051 and K4052) provide local user override

Remote programming with the K4053 ensures changes can be easily accommodated

Description
Digital sensors are part of a comprehensive range
of presence detection systems designed to control
modular luminaires with DSI, high frequency
ballasts and other lighting loads.

OneSwitch Dimming. Manual input to adjust light level or turn luminaires on or off

Dimensions

They offer superior-performance programmable


presence detection for lighting control in offices
and open-plan workstations. They use microwave
presence detection technology which enables
the range to be adjusted to ensure a tailored
detection pattern to suit any application and is
available for flush and surface mounting with
single or dual-circuit option.

Flange
15mm deep

Digital sensors utilise microwave radar to monitor a space


for movement. This involves transmitting a very low power
microwave signal and examining the reflected signal for
frequency variations called doppler shifts. The microwave
system is extremely sensitive to small body movements and
provides effective presence detection in rooms up to 20m x 20m.
Please note that this extreme sensitivity makes it essential that
the detector be installed on a rigid surface that will not itself be
subject to movement or vibration.

100mm

Please note also that microwave technology is not recommended


for applications where there are large areas of metal, e.g. metal
ceiling or floor tiles, as unpredictable sensitivity may result.

Sensors Technical

467

white | wiring devices

technical hotline +44 (0)1268 563720

Digital Sensors Corner Mounted


Technical specification
Maximum recommended mounting height:
3.5m
Range:
Adjustable up to 20m
Off delay:
10 seconds to 20 minutes

K4033

K4032

Photocell:
Adjustable 50-5000 lux
Operating voltage:
230V 50Hz

Features

Colour:
White

Active presence detection by microwave technology

Material:
Flame retardant PC/ABS

Passive photocell holds lights off in bright ambient conditions

Weight:
250g
IP rating:
43 when ceiling mounted
4X when wall mounted

0-20

20m

Description
Digital corner mounted sensors are high
performance, directional presence detector with
built-in photocell for use in almost any internal
space. It was conceived to bridge the gap between
the Standard Series LightSpot and the Long
Range equipment. It is ideal for larger classrooms,
conference rooms, longer storage aisles etc. It is
a self-contained unit, making installation very
simple and straightforward.

Off delay in minutes following the last observed movement after which the lights switch off

Detection pattern and range in metres under normal operating conditions

Hand-held Controller (K4051) provide local user override

Dimensions

74mm

95
mm
60
mm

They utilise microwave technology and are


capable of effective presence detection in rooms
of up to 20m x 20m.

Photocell

The units are self-contained, featuring a movement


detector, photocell and 10 Amp (load switching)
element in one, easily deployed housing. The
detectors may be surface or semi-flush mounted.

Off Range
On Range
Delay
(Position of controls when
commissioning commences)

20mm
back
entry

K4032 Surface version


50.8mm

Rear view

The back-box can be secured directly to a hard


surface or to a conduit stop end box.
K4033 Semi-flush version
Use a hole saw to drill a 76mm hole into the
ceiling tile. The flush ring is designed to clamp
the tile between its two halves.

468

Sensors Technical

wiring devices | white

www.mkelectric.co.uk

Ultrasonic Sensors
Technical specification
Operating voltage:
230V 50Hz
Maximum recommended mounting height:
5 metres
Switch capacity:
10 Amps Incandescent lamps: 1500W max (230V)

K4030

K4031

Terminal capacity:
2 x 1.5mm or 1 x 2.5mm
Weight:
148g

Features

Time delay:
5, 10 or 15 mins

Active presence detection by ultrasonic technology

Power-up condition:
select ON or OFF

Passive photocell holds lights off in bright ambient conditions

Detector range:
adjustable
On/Off Ranges::
adjustable
Ultrasonic frequency:
40kHz
Photocell:
adjustable 50 to 5000 lux

Description
Ultrasonic sensors are general purpose, fully
automatic, directional presence detectors with
photocell. They save energy by switching off lights
in unoccupied areas and by holding lights off in
occupied areas which have adequate natural light.
They use a specially developed ultrasonic radar
to monitor the controlled space for movement.
This radar is sensitive enough to respond to even
very small movements thus ensuring that lights
are sustained whenever the controlled space is
occupied. If no movement has been detected
for a pre-selected period, the sensors switch the
lights off until the next visitor is detected.
The sensors control feature a movement detector,
photocell and 10 Amp load switching element
in one easily deployed housing. The technology
has been refined and improved over many years
of efficient, reliable service in a wide range of
industrial and commercial environments. The
latest designs use state-of-the-art miniaturisation
to pack the features into a small, attractive yet
rugged enclosure which gives full field-of-view
adjustment. Detectors are available for surface or
semi-flush mounting.

5-15
6m 13m

Off delay in minutes following the last observed movement after which the lights switch off

Detection pattern and range in metres under normal operating conditions

Dimensions
K4030 Surface version

K4030 Semi Flush version

The back-box can be secured directly to a hard


surface or to a conduit stop end box.

Use a hole saw to drill a 76mm hole into the


ceiling tile. The flush ring is designed to clamp
the tile between its two halves.
Flush Plate & Clamp (K4078)
For simple flush mounting of detector to
suspended ceilings.
Max clamping distance 25mm

71mm
60mm

60
mm

20mm
back
entry
knockout

83
mm
120mm

3 x side entry knockout

51mm

A sensor will fit to its own backplate or to


a standard 25mm switch sinking box.

Rear View

Ultrasonic sensors utilise ultrasonic radar to monitor a space for movement. This involves transmitting
an ultrasound signal and examining the reflected signal for frequency variations called doppler shifts.
The transmitted signal is more quickly dissipated in open space and squeezed out by constraining walls
and ceilings. The range of the detector also depends upon the type of movement being observed:
for example, walking activity can be observed at a greater distance than the slight hand or body
movement to be expected from a person working at a desk. Note that detectors can see behind
themselves slightly so must be inset in a storage aisle or corridor application.

Sensors Technical

469

white | wiring devices

technical hotline +44 (0)1268 563720

Long Range Detectors


Technical specification
CONTROL UNITS (K4039/K4040)
Operating voltage:
230v 50 hz
Switch:
10 amp x 230v (volt-free)
Incandescent lamps:
1500w max (at 230v)
Terminals:
1 x 6mm or 2 x 2.5mm
Weight:
850g approx
Power supply:
Transformer isolated 12V
Semi-automatic:
Using low voltage switch
Segregation:
None
Time-out:
0-16 minutes per channel
K4039 - 1channel
K4040 - 2channels

K4036
(K4039/K4040 required)

Description
Long Range Detectors are high performance presence detection system for use in almost any internal
space. It was conceived to bring effective energy-saving control to large areas such as warehouses,
sports halls, workshops, hangars, classrooms etc. The system offers many outstanding features and
user options, making it the natural choice for large and prestigious situations. Long Range LightSpot is
designed to the highest quality standards and performance criteria to ensure efficient and trouble-free
operation in the most exacting locations.
Long Range Detectors comprise of 230-volt control units with single or dual volt-free output relays, rated
to switch any type of load up to 10 amps.

Features

Power-up condition:
Select on or off

Active presence detection by microwave technology

Photocell:
Remote operation

Passive photocell holds lights off in bright ambient conditions (Requires K4106). Active
photocell has the capability to switch lights off in occupied areas

Dimensions:
175 x 125 x 75 mm
K4036 SURFACE DETECTOR
Voltage:
12V dc

K4035
(K4039/K4040 required)

0-16
0-32
30m

Frequency:
10.7GHz low power microwave

Off delay in minutes following the last observed movement after which the lights switch off

Detection pattern and range in metres under normal operating conditions


Dual circuit control. Relay 2 (K4040 model only) always influenced by photocell, relay 1 output
can be influenced by photocell if configured

Weight:
800g approx
On/Off Range:
Adjustable

Dimensions

Construction:
Zinc & polycarbonate

K4036 surface detector

IP rating:
IP4X
Max mounting height:
6m
Flush fixing (K4035 only):
To 2-gang sinking box

175
mm

K4035 flush detector

120
mm

170mm
125mm

145mm

80mm

470

Sensors Technical

wiring devices | white

www.mkelectric.co.uk

Universal Photocell
Technical specification
Operating voltage:
230V 50Hz
Power consumption:
<10W
Volt-free contact:
6 Amps max. Any type of lighting load

K4045

Ambient temperature range:


0 to +40C
Ballast control type:
Single master; no other masters to be connected

Features

Ballast control capacity:


25 Max (1-10V, DSI, DALI Ballasts ballast type selected
via K4053)

Regulating photocell ensures a minimum maintained light level, taking account of the
contribution from adjacent luminaires and daylight

Photocell sensitivity:
0 to 5000 Lux (with a 20% reflective workplane)

Hand-held Controllers (K4051 and K4052) provide local user override

Recommended mounting eight:


2.4m

Remote programming via K4050 or K4053 ensures changes can be easily accommodated

Incorporates simple scene-setting - up to six scenes can be set via user remote

2.4m

6.0m

Maximum mounting height:


6.0m
Material:
Flame Retardant PC/ABS

5-60

Passing cloud timer prevents nuisance switching when light levels fluctuate rapidly, can be
set from 5-60 minutes

Dimensions

WHITE CABLE:
Brown Live
Blue Neutral
Green/Yellow Earth (no internal connection)
Black
Volt-free Output 6A Max
Grey

IP rating:
IP3X

Weight:
350g

BLACK CABLE:
Yellow Dimming Control + ve
Green Dimming Control - ve

Description
The K4045 is a high performance regulating
and switching photocell for DSI, DALI, Analogue
1-10V and non-regulating ballasts.
It can be used with all common types of control
gear in almost any environment where lights
would be left on unnecessarily when there is
sufficient daylight.
The K4045 observes the controlled space, not
just daylight, and takes account of all light
contributions.
Photocell operation is extremely user-friendly:
lights will not be switched on or off until the
Passing Cloud Time delay has elapsed thus
removing the possibility of nuisance switching.
The K4045 offers more advanced features and
operational parameters than an ordinary, simple
photocell. Consequently, it requires careful and
considered commissioning and is aimed at higher
specification projects.

115mm

65mm

Sensors Technical

471

white | wiring devices

technical hotline +44 (0)1268 563720

Accessories

K4050

K4051

K4052

K4053

K4050 Hand-held Programmer


Technical specification

Description

Specification

Battery type:
6V dc (2 x CR 2032 cells)

The K4050 is a simple-to-use, low-cost


programming tool for use with MKs range of
stand-alone lighting control products.

The K4050 can also be used to set the regulating


light level in conjunction with a suitable lux meter
on supported products via a simple UP/DOWN/
STORE command.

Features

All detectors (except Standard PIRs, Digital Corner


Mounted and Long Range) are programmable via
the K4050 although not all the programmable
parameters are supported by all detectors.
Please check individual Technical Data Sheets
for details.

Typical battery life:


3 years
Dimensions:
75 x 58 x 18mm (L x W x D)
Weight:
50g

Parameters, such as time delay and semiautomatic/fully automatic operation, are chosen
via an array of 12 dil switches, the status of which
is then programmed into the MK detector.
Most programmable parameters are catered
for although not all options are available for
programming on some products (see K4053 below).

K4051 & K4052 Hand-held Controllers


Technical specification
Battery type:
3V dc (2 x AAA alkaline cells)
Typical battery life:
1 year

K4051

K4052

The K4051 provides the same functions as the


K4052 along with the ability to set and recall
up to six different lighting scenes. Supplied
with wall bracket. See Technical Data Sheets on
individual detectors to check compatibility.

This remote control offers the user temporary on/


off override and light level adjustment. Supplied
with wall bracket. See Technical Data Sheets on
individual detectors to check compatibility.

Dimensions:
120 x 56 x 22mm (L x W x D)
Weight:
115g
Operating range:
2.5m

K4053 Digital Programmer


Technical specification
Battery type:
4.5V dc (3 x AAA alkaline cells)
Display:
128 x 64 monochrome dot matrix LCD
Dimensions:
150 x 85 x 35mm (L x W x D)
Weight:
228g

Description
The K4053 Digital Programmer can be used with
all K4050-compatible products; it offers a full
range of programmable parameters and also a
Download facility.