You are on page 1of 4

TC840M1021(CDN)

Acclimate™ Multi-Sensor
Low-Profile Intelligent Detector

General
The TC840M1021(CDN) Acclimate™ detector is an intelligent, j6935ph1.jpg

addressable, multi-sensing, low-profile detector designed for


use with the XLS140-2 and XLS3000 (classic or FlashScan®
modes) Fire Alarm Control Panels.
The Acclimate detector uses a combination of photoelectric TC840M1021(CDN) in 14507371-001 base
and thermal sensing technologies that are designed to
increase immunity to false alarms. Unlike traditional intelligent
detectors, the Acclimate detector has a microprocessor in the
detector head that processes alarm data. As a result, the
Acclimate detector adjusts its sensitivity automatically, without • Listed to UL 268.
needing operator intervention or control panel programming. • Capable of heat-only alarm mode, enabled by a special
Areas where the Acclimate detector is especially useful command from the panel. Smoke alarms are ignored.
include office complexes, schools, college campuses, manu- • Backwards-compatible on most panels.
facturing and industrial facilities, and anywhere else the use of • Low-temperature signal at 45°F +/– 10°F (7.22°C +/–
a particular area may change. The Acclimate detector auto- 5.54°C).
matically adjusts its sensitivity to the environment.
FlashScan (U.S. Patent 5,539,389) is a communication proto- Specifications
col developed to greatly enhance the speed of communication
between analog intelligent devices and compatible systems. Sensitivity: auto-adjusting levels: 1 to 2%/ft. and 2 to 4%/ft.
Intelligent devices communicate in a grouped fashion. If one of with classic CLIP systems; 1 to 2, 2 to 3, and 3 to 4%/ft. with
the devices within the group has new information, the panel’s FlashScan systems; fixed-sensitivity levels: 1, 2, and 4%/ft.
CPU stops the group poll and concentrates on single points. with classic CLIP systems; 0.5, 1, 2, 3, and 4%/ft. with Flash-
The net effect is response speed greater than five times that of Scan systems.
earlier designs. Size: 2.1" (5.3 cm) high x 4.1" (10.4 cm) diameter installed in
14506414-002 base, 6.1" (15.5 cm) diameter installed in
Features 14507371-001 base.
• Automatically adjusts sensitivity levels without the need for Shipping weight: 5.2 oz. (147 g).
operator intervention or programming. Sensitivity increases Operating temperature: 0°C to 38°C (32°F to 100°F).
with heat.
UL-Listed velocity range: 0 – 4000 ft./min. (1219.2 m/min.),
• Microprocessor-based, combination photo and thermal suitable for installation in ducts.
technology.
Relative humidity: 10% – 93% noncondensing.
• FlashScan (XLS140-2 and XLS3000) and classic system
(XLS140, XLS3000, XLS1000/200, and FS90 Plus) com- Thermal sensing rating: fixed-temperature setpoint 135°F
patible. (57°C).
• Addressable-analog communication. ELECTRICAL SPECIFICATIONS:
• Sleek, low-profile design. Voltage range: 15 – 32 volts DC peak.
• Two-wire SLC connection.
Standby current (max. avg.): 250 μA @ 24 VDC (without
• Rotary, decimal addressing (1 – 99 on current classic sys- communication); 360 μA @ 24 VDC (one communication
tems; 1 – 159 on FlashScan systems). every 5 seconds with LED enabled).
• Addresses can be viewed and changed without the need for Loop resistance: 40 ohms maximum; varies according to
electronic programmers. control panel used. Refer to panel installation manuals.
• Dual bi-color LED design provides 360° viewing angle.
LED current (max.): 6.5 mA @ 24 VDC (“ON”).
• LEDs lock red when in Alarm. In FlashScan, LEDs flash
green in standby for normal condition. BASES AVAILABLE:
• Built-in tamper-resistant feature. 14507371-001: 6.1" (15.5 cm) diameter.
• Sealed against back pressure. 14506414-002: 4.1" (10.4 cm) diameter.
• Constructed of off-white Bayblend®, designed to commer- B501BH or B501BHT: Sounder base assembly. Includes
cial standards, and offers an attractive appearance. 14506414-002 base.
• 94-5V plastic flammability rating.
B224RB Relay Base: Screw terminals: up to 14 AWG (2.0
• SEMS screws for wiring of the separate base. mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive;
• Several base options, including relay, isolator, and sounder. 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
• Remote test feature from the panel. Dimensions: 6.2" (15.748 cm) x 1.2" (3.048 cm).
• Built-in functional test switch activated by external magnet. 14507371-005 Isolator Base: Dimensions: 6.2" (15.748 cm) x
1.2" (3.048 cm). Maximum: 25 devices between isolator bases.
Installation
The TC840M1021(CDN) plug-in detector uses a separate
base to simplify installation, service, and maintenance. A spe-
cial tool allows maintenance personnel to plug-in and remove
detectors without using a ladder. Mount base on an electrical
backbox at least 1.5" (3.81 cm) deep. Suitable mounting base
boxes include:
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box (except relay or isolator base).
• With B501BH or B501BHT base, use a 4.0" (10.16 cm)
square box. 4762wir1.tif
Wiring Diagram
• With B224RB or 14507371-005 base, use a 3.5" (8.89 cm)
octagonal box, or a 4.0" (10.16 cm) octagonal or square
box.
NOTE: 1) Because of the inherent supervision provided by the 6833addr.wmf
SLC loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult data sheet 77-4555
(TC811A-1006) for device limitations between isolator modules
and isolator bases.
APPLICATION NOTE: The TC840M1021(CDN) detector has the
unique ability to adjust sensitivity according to the environment,
based on heat and smoke levels. Avoid installing these detectors
in locations that are susceptible to rapid and high temperature
changes. An example of an incorrect application would be near or Address dial on back of detector
in line with the output of a self-contained heater.
DETECTOR SPACING: Honeywell recommends spacing detec-
tors in compliance with NFPA 72. In low airflow applications with
smooth ceilings, space detectors 30 feet (9.144 m). For specific
information regarding detector spacing, placement, and special
applications, refer to NFPA 72. System Smoke Detector Applica-
tion Guide, document A05-1003, is available at systemsen-
sor.com.

Agency Listings and Approvals


These listings and approvals apply to the modules specified in
this. In some cases, certain modules or applications may not
be listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
• UL Listed: S1196
• ULC Listed: S6959 (ML154)(FAPT-851A)(XLS3000 and
XLS140-2 only)
• FM Approved

Page 2 of 4 — 5/2/08 • 74-3387-2 www.honeywell.com


Ordering Information M02-09-00: Test magnet with telescope stick.
TC840M1021: Low-profile intelligent multi-sensor detector. XR2B: Detector removal tool. Allows installation and/or
Must be mounted to one of the bases listed below. removal of FlashScan® Series detector heads from base in
high ceiling installations.
TC804M1021CDN: Same as TC840M1021 but with ULC List-
ing. T55-127-000: Detector removal tool without pole.
XP-4: Extension pole for XR2B. Comes in three 5-ft. sections.
BASES:
14507371-001BP: Standard U.S. low-profile base, pkg. of 10. DETECTOR GUARDS:
14506414-002BP: Standard European flangeless base, pkg. NOTE: Some guards listed below may not be applicable.
of 10. SDG-773: Smoke detector guard; cover is 7.0" (17.78 cm)
B501BH: Sounder base, includes B501 base above. square x 3.0" (7.62 cm) deep. This guard, although mechani-
cally compatible, is NOT UL-compatibility Listed with the
B501BHT: Same as B501BH, but includes temporal sounder. TC840M1021.
B224RB: Intelligent relay base. STI9601: Low-profile, flush-mount smoke detector guard,
14507371-005: Intelligent isolator base. Isolates SLC from wire.*
loop shorts. STI9602: Low-profile, surface-mount, smoke detector guard,
wire.*
ACCESSORIES:
F110: Retrofit replacement flange for older high profile bases. STI9609: High-profile, flush-mount, smoke detector guard,
Converts bases for use with FlashScan® detectors. wire.*

RA400Z: Remote LED annunciator. 3 – 32 VDC. Fits U.S. sin- STI9605: High-profile, surface-mount, smoke detector guard,
gle-gang electrical box. Supported by 14507371-001 and wire.*
14506414-002 bases only. STI9604: Flush-mount heat detector guard, wire.*
SMK400: Surface mounting kit provides for entry of surface STI9610: Surface-mount heat detector guard, wire.*
wiring conduit. For use with 14506414-002 base only.
* For dimensions and additional information on STI Steel Web
RMK400: Recessed mounting kit. For use with 14506414-002 Stoppers, see data sheet 85-3093.
base only. STI8200-SS: Flush-mount stainless steel smoke detector
SMB600: Surface mounting kit for use with 14507371-001BP. guard (compatibility pending).
BCK-200B: Black detector covers, box of 10. STI8230-SS: Surface-mount stainless steel smoke detector
guard (compatibility pending).
M02-04-01: Test magnet.

www.honeywell.com 74-3387-2 • 5/2/08 — Page 3 of 4


This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to change without notice.
FlashScan® is a registered trademark and Acclimate™ is a trademark of Honeywell International Inc. Bayblend® is a registered trademark of Bayer Corp.
©2008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Automation and Control Solutions


Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
www.honeywell.com 74-3387-2 Rev. 05/08
May 2008
Made in the U.S.A.
® U.S. Registered Trademark
© 2008 Honeywell International Inc.
Page 4 of 4
74-3387-2