Electrical Distribution
GE Overcurrent Device
Instantaneous Selectivity Tables
Contents
Introduction........................................................................................................................... 3
Summary Tables................................................................................................................. 8
Overcurrent Device Tables ............................................................................................ 11
Upstream (Mains)
Downstream (Feeders)
Stored Energy Mains
ANSI/ICCB................................................ 11
SK ................................................................ 13
SG................................................................ 14
Spectra Circuit Breakers ................... 15
Record Plus Circuit Breakers........... 16
THK, TK...................................................... 17
TJ, THF, TF................................................ 18
Lighting Panel Circuit Breakers ..... 19
MCPs with Current Limiters............. 20
Electronic Trip MCCBs
Spectra with MVT Trip........................ 21
SK ................................................................ 23
SG................................................................ 24
SF................................................................. 25
SE................................................................. 26
THJK, TJK, TJJ, TJD .............................. 27
THFK, TFK, TFJ ....................................... 29
THQD, TQD .............................................. 30
TEY .............................................................. 31
THHQB, THQB ....................................... 32
Record Plus FB ...................................... 33
TECL ........................................................... 34
Record Plus FG ...................................... 35
Spectra RMS
SK ................................................................ 36
SG................................................................ 37
SF................................................................. 38
SE................................................................. 40
TEY .............................................................. 42
THHQB, THQB ........................................ 44
TECL ........................................................... 46
Thermal Magnetic MCCBs THQD, TQD .............................................. 48
TEY & THHQB, THQB ........................... 49
THQB, TEY, FB ........................................ 51
200
100
Assumptions:
Fault values are expressed in 60 Hz RMS.
Selectivity short circuit values are valid at the voltage described and
any lower voltage. Selectivity at voltages in excess of those
specifically noted is not implied in these tables. For selectivity at
higher voltage, please consult your local GE representative.
Selectivity values for paired circuit breakers are valid for X/R ratios
equal to, or less, than those for which the OCPDs were tested or
analyzed. A fault X/R ratio higher than the test X/R ratio will require
that the selectivity be de-rated by the ratio of the prospective peak
currents. A table of X/R ratios, Power Factors and expected peak
currents is provided. These de-rating methods are the same as those
used to de-rate the interrupting rating of any overcurrent protection
device whose test X/R ratio is less than the X/R ratio of the available
fault current where the device is applied.
50
20
TIME IN SECONDS
10
5
2
1
.5
.2
.1
.05
GE Spectra RMS
Frame = 100A (100AT)
Plug = 100
Inst = Ma x (1250A)
.02
.01
.5
10
100 2
1000
Figure 1
Breaker operation can also be caused by, but not limited to: over-voltage,
under-voltage, current-imbalance, phase loss, and excessive stray
voltages. Over time, unusual system conditions such as component
degradation, significant load changes and changes in environmental
conditions may also adversely affect system reliability. Some of these
the first circuit breaker is important to determine the short circuit rating
required for that device, however it is the fault value at the downstream
circuit breaker that determines the selectivity need.
A
50kA
B
30kA
13kA
4.2kA @ 208V
Figure 2
Multiple Circuit Breaker Selectivity
Figure 3
Through Transformer Selectivity
For the example shown in Figure 3, the 125A transformer primary main
should be selective with the 1200A panel main. Selectivity would be
required up to fault current value at the 125A device, or 40kAIC (kA
Interrupting Current). The 125A primary main and the 250A secondary
main need not be selective with each other. Loss of either device has the
same effect on power continuity at the secondary loads. However, the
250A secondary main needs to be selective with the 1200A primary panel
main for the maximum available secondary fault current. The secondary
fault current is limited by the transformer impedance. The secondary
fault current as seen by the primary circuit is further limited by the
transformer ratio. In this example, the calculated, bolted three-phase fault
current at the transformers secondary terminals is 4.2kAIC. At the
secondary panel, the fault current is 3.9kAIC due to the secondary cable
impedance. Selectivity between the 30A feeder and the 250A secondary
main is required. A maximum fault current of 3.9kA below the secondary
feeder defines the selectivity requirement for that pair of devices. For a
480/208V, delta - wye transformer, the transformer ratio is 2.31:1. The
3.9kA available fault current divided by the transformer ratio is
(3.9kA/2.31) 1.7kA. Hence, the 30A secondary feeder and the transformer
primary main only need to be selective to 1.7kAIC.
5
Test Ranges
>20kA
<20kA,>10kA
<10kA
Chart 1
Power
Factor
4
5
6
7
8
8.5
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
X/R ratio
24.9790
19.9740
16.6230
14.2510
12.4600
11.7230
11.0660
9.9501
9.0354
8.2733
7.6271
7.0721
6.5912
6.1695
5.7967
5.4649
5.1672
4.8990
4.6557
4.4341
4.2313
4.0450
3.8730
3.7138
3.5661
3.4286
3.3001
3.1798
3.0669
2.9608
2.8606
2.7660
2.6764
2.5916
2.5109
2.4341
2.3611
2.2913
2.2246
2.1608
2.0996
2.0409
1.9845
1.9303
1.8780
1.8277
1.7791
1.7321
Maximum
Peak
2.663
2.625
2.589
2.554
2.520
2.504
2.487
2.455
2.424
2.394
2.364
2.336
2.309
2.282
2.256
2.231
2.207
2.183
2.160
2.138
2.110
2.095
2.074
2.054
2.034
2.015
1.996
1.978
1.960
1.943
1.926
1.910
1.894
1.878
1.863
1.848
1.833
1.819
1.805
1.791
1.778
1.765
1.753
1.740
1.728
1.716
1.705
1.694
Non-current limiting1 (GE THQB, TEY, TE, TF, TJ, TK families and related
frames)
Electronic trip
Current limiting, adjustable instantaneous pick-up (I PU) only (GE
Spectra frames E through G and Record Plus G)
Non-current limiting1, adjustable I PU only (GE Spectra K frame)
Current limiting, fully adjustable trips (GE Spectra G frame)
Non-current limiting1, fully adjustable trips (GE Spectra K frame and
ABB S7)
Fully adjustable electronic trips allow setting of the long time pick-up,
long time delay, short time pick-up, short time delay and whether the
short time characteristic will have an I squared T response or not. These
electronic trips allow for separate adjustments of instantaneous and
ground fault protection.
Current limiting circuit breakers as load side devices will provide greater
levels of selectivity if the current limiting molded case circuit breaker
downstream has a current limiting threshold lower than the
instantaneous pick-up setting of the circuit breaker above.
Many MCCBs not labeled as current limiting may be current limiting under some fault
conditions. It cannot be assumed that any CB not labeled current limiting always takes
any specific amount of time to clear. Time current curves may show clearing times in
excess of or 1 cycle, however the circuit breaker may interrupt in less than one half
cycle regardless. This is one reason the up-over-and-down method should not be used to
develop series ratings.
Thermal magnetic
Current limiting (GE Record PlusTM , FC and FB families)
Summary
Switchboards and Power Panels
Upstream Mains
Amperes
Description
LVPCB(1)
LVPCB(1)
LVPCB
LVPCB/ICCB
LVPCB
ICCB(2)
ICCB
LVPCB/ICCB
LVPCB/ICCB
LVPCB/ICCB
MCCB S7
MCCB S7
CL MCCB(6) FG
CL MCCB FG
CL MCCB FG
Mounting
(5)
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
S
S
S
S
S
Frame
Sensor
3200-5000A Frame
800-2000A Frame
5000
5000
4000
4000
3200
3200
3000
3000
3000
2500
2000
2000
1600
1600
800
800
1200
1200
1200
1000
600
600
600
400
600
250
Plug or
Trip
5000
4000
3200
3000
2500
2000
1600
800
None
None
600
400
250
Trip type
Adj. (3)
Adj. (3)
Adj. (4)
Adj
Adj
Adj
Adj
Adj
Adj
Adj
Adj
Adj
IPU Only
IPU Only
IPU Only
Max. Inst.
Pickup
(X Plug)
None
None
7
9
13
13
13
15
15
15
1.5-12+ (8)
1.5-12+ (8)
10 (7)
10
10
1
2
3
ABB S7
1200
1200
1000
3P
3P
65,000 65,000
65,000 65,000
31,500 31,500
32,400 32,400
37,440 37,440
35,100 35,100
29,250 29,250
27,000 27,000
21,600 21,600
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
Downstream Feeders(7)(8)
FG
FE
600
250
600
400
250
250
3&2P
3&2P
3&2P
3&2P
100,000 100,000 100,000 100,000
65,000
65,000
65,000
65,000
64,700
64,700
64,700 100,000
69,000
69,000
69,000 100,000
100,000 100,000 100,000 100,000
85,000
85,000
85,000 100,000
54,000
54,000
54,000 100,000
44,000
44,000
44,000 100,000
25,000
25,000
25,000
71,300
NIS
11,000
11,000
14,200
65,000
65,000
65,000
65,000
65,000
65,000
65,000
65,000
NIS
TCC
TCC
100,000
NIS
NIS
TCC
TCC
NIS
NIS
NIS
NIS
SF
250
250
3&2P
100,000
65,000
97,500
100,000
100,000
100,000
81,600
67,400
40,000
11.000
65,000
65,000
TCC
TCC
NIS
SE
150
150
3&2P
100,000
65,000
100,000
100,000
100,000
100,000
90,000
73,000
40,000
13,000
65,000
65,000
TCC
TCC
TCC
LVPCB = Low Voltage Power Circuit Breakers, GE types WavePro or Entelliguard. UL listed to UL 1066.
ICCB= Insulated Case Circuit Breaker, GE Type PowerBreak II. UL listed to UL 489.
LVPCB are available with or without instantaneous trips. If provided without instantaneous trips they may be selective up to their short circuit rating or the rating of the device below.
Trips typicaly designated as LS or LSG.
4 Adj = Adjustable trip with LS, LSI, LSG or LSIG characteristics.
5 D/O = Draw out mounting. S = Stationary mounting.
6 CL MCCB = Current Limiting Molded Case Circuit Breaker.
7 For FG the maximum adjustment to the IPU (Instantaneous Pick Up) is based on sensor size. All other devices are based on plug size. For trip ratio less than 2 between FG to FB, TEY or
THQB, use TCC to determine if there is a short time or long time overlap.
8 S7 instantaneous adjustment is 1.5-12 and off. When off, a 16kA override provides instantaneous protection.
NIS = Not instantaneously selective. Selectivity is not expected as the LT and ST portions of the curve probably overlap.
TCC = Selectivity is best determined by examination of overlaid trip-time-curves and will probably be dependent on specific device settings. Some level of selectivity is possible but may be low.
Summary
Lighting Panels
Mounting
(5)
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
S
S
S
S
S
S
Frame
Sensor
3200-5000A Frame
800-2000A Frame
5000
5000
4000
4000
3200
3200
3000
3000
3000
2500
2000
2000
1600
1600
800
800
1200
1200
1200
1000
600
600
600
400
600
250
250
250
Plug
or Trip
5000
4000
3200
3000
2500
2000
1600
800
None
None
600
400
250
250
Trip type
Adj. (3)
Adj. (3)
Adj. (4)
Adj
Adj
Adj
Adj
Adj
Adj
Adj
Adj
Adj
IPU Only
IPU Only
IPU Only
Adj
Max. Inst.
Pickup
(X Plug)
None
None
7
9
13
13
13
15
15
15
1.5-12+ (9)
1.5-12+ (9)
10 (7)
10
10
13
1
2
3
FB
100
100
3,2&1P
100,000
65,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
35,000
65,000
65,000
65,000
65,000
65,000
TCC
100
100-70
3,2&1P
65,000
65,000
14,000
14,000
14,000
14,000
14,000
14,000
14,000
12,800
14,000
14,000
6,000
4,000
2,500
TCC
Downstream Feeders(7)(8)
TEY
100
100
100
100
60-35
30-15
60-35
30-15
3&2P
3&2P
1P
1P
65,000 65,000 65,000 65,000
65,000 65,000 65,000 65,000
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
12,800 12,800 12,800 12,800
14,000 14,000 14,000 14,000
14,000 14,000 14,000 14,000
10,000 14,000 10,000 14,000
10,000 14,000 10,000 14,000
2,500
14,000
2,500
14,000
TCC
10,000
TCC
10,000
TEYF
100
100
100-35
30-15
3,2&1P 3,2&1P
65,000 65,000
65,000 65,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
14,000 14,000
TCC
14,000
LVPCB = Low Voltage Power Circuit Breakers, GE types WavePro or Entelliguard. UL listed to UL 1066.
ICCB= Insulated Case Circuit Breaker, GE Type PowerBreak II. UL listed to UL 489.
LVPCB are available with or without instantaneous trips. If provided without instantaneous trips they may be selective up to their short circuit rating or the rating of the device below.
Trips typicaly designated as LS or LSG.
4 Adj = Adjustable trip with LS, LSI, LSG or LSIG characteristics.
5 D/O = Draw out mounting. S = Stationary mounting.
6 CL MCCB = Current Limiting Molded Case Circuit Breaker.
7 For FG the maximum adjustment to the IPU (Instantaneous Pick Up) is based on sensor size. All other devices are based on plug size. All other devices are based on plug size. For trip ratio
less than 2 between FG to FB, TEY or THQB, use TCC to determine if there is a short time or long time overlap.
8 FG to FB selectivity for circuit breaker pairs with a trip ratio of less than 2 should be verified with time current curves. FG to TEY selectivity for circuit breaker pairs with a trip ratio of less
than 1.6 should be verified with time current curves.
9 S7 instantaneous adjustment is 1.5-12 and off. When off, a 16kA override provides instantaneous protection.
NIS = Not instantaneously selective. Selectivity is not expected as the LT and ST portions of the curve probably overlap.
TCC = Selectivity is best determined by examination of overlaid trip-time-curves and will probably be dependent on specific device settings. Some level of selectivity is possible but may be low.
Summary
Lighting Panels (continued from previous page)
Upstream Mains
Amperes
Description
LVPCB(1)
LVPCB(1)
LVPCB
LVPCB/ICCB
LVPCB
ICCB(2)
ICCB
LVPCB/ICCB
LVPCB/ICCB
LVPCB/ICCB
MCCB S7
MCCB S7
CL MCCB(6) FG(8)
CL MCCB FG(8)
CL MCCB FG(8)
CL MCCB FE
Mounting
(5)
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
D/O, S
S
S
S
S
S
S
Frame
Sensor
3200-5000A Frame
800-2000A Frame
5000
5000
4000
4000
3200
3200
3000
3000
3000
2500
2000
2000
1600
1600
800
800
1200
1200
1200
1000
600
600
600
400
600
250
250
250
Plug or
Trip
5000
4000
3200
3000
2500
2000
1600
800
None
None
600
400
250
250
Trip type
Max. Inst.
Pickup
(X Plug)
Adj. (3)
Adj. (3)
Adj. (4)
Adj
Adj
Adj
Adj
Adj
Adj
Adj
Adj
Adj
IPU Only
IPU Only
IPU Only
Adj
None
None
7
9
13
13
13
15
15
15
1.5-12+ (9)
1.5-12+ (9)
10 (7)
10
10
13
1
2
3
125
125
2P
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
22,000
22,000
22,000
22,000
2,500
TCC
125
100-70
3,2&1P
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
22,000
22,000
22,000
22,000
2,500
TCC
Downstream Feeders(7)(8)
THQB, THHQB
125
125
60-35
30-15
3&2P
3&2P
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
18,100
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
10,000
22,000
4,000
6,000
125
60-35
1P
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
22,000
22,000
22,000
22,000
10,000
TCC
125
30-15
1P
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
22,000
22,000
22,000
22,000
22,000
14,000
LVPCB = Low Voltage Power Circuit Breakers, GE types WavePro or Entelliguard. UL listed to UL 1066.
ICCB= Insulated Case Circuit Breaker, GE Type PowerBreak II. UL listed to UL 489.
LVPCB are available with or without instantaneous trips. If provided without instantaneous trips they may be selective up to their short circuit rating or the rating of the device below.
Trips typicaly designated as LS or LSG.
4 Adj = Adjustable trip with LS, LSI, LSG or LSIG characteristics.
5 D/O = Draw out mounting. S = Stationary mounting.
6 CL MCCB = Current Limiting Molded Case Circuit Breaker.
7 For FG the maximum adjustment to the IPU (Instantaneous Pick Up) is based on sensor size. All other devices are based on plug size.
8 FG to THQB selectivity for circuit breaker pairs with a trip ratio of less than 1.6 should be verified with time current curves.
9 S7 instantaneous adjustment is 1.5-12 and off. When off, a 16kA override provides instantaneous protection.
NIS = Not instantaneously selective. Selectivity is not expected as the LT and ST portions of the curve probably overlap.
TCC = Selectivity is best determined by examination of overlaid trip-time-curves and will probably be dependent on specific device settings. Some level of selectivity is possible but may be low.
10
11
ANSI
3,200A
TCC
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
ICCB
3,000A
TCC
TCC
TCC
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
ANSI
3,000A
31,500
32,400
TCC
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
ICCB
2,500A
TCC
TCC
TCC
37,440
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
ANSI
2,400A
TCC
TCC
TCC
37,440
35,100
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
12
1,600A
1,200A
1,000A
800A
400A
150A
31,500
32,400
29,160
37,440
35,100
TCC
29,250
28,080
27,000
TCC
NIS
NIS
NIS
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
TCC
NIS
NIS
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
TCC
TCC
NIS
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
TCC
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
TCC
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
5,400
TCC
800A
700A
600A
500A
450A
400A
350A
300A
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
NIS
NIS
NIS
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
TCC
NIS
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
NIS
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
TCC
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
NIS
NIS
31,500
32,400
29,160
37,440
35,100
24,300
29,250
28,080
27,000
21,600
16,200
13,500
10,800
TCC
NIS
13
500A
450-300A
250A
225-125A
100-60A
36,700
38,700
32,000
54,200
46,000
24,400
32,100
30,000
28,300
21,600
16,200
TCC
NIS
NIS
NIS
36,700
38,700
32,000
54,200
46,000
24,400
32,100
30,000
28,300
21,600
16,200
13,500
TCC
NIS
NIS
36,700
38,700
32,000
54,200
46,000
24,400
32,100
30,000
28,300
21,600
16,200
13,500
10,800
NIS
NIS
36,700
38,700
32,000
54,200
46,000
24,400
32,100
30,000
28,300
21,600
16,200
13,500
10,800
TCC
NIS
36,700
38,700
32,000
54,200
46,000
24,400
32,100
30,000
28,300
21,600
16,200
13,500
10,800
5,400
NIS
36,700
38,700
32,000
54,200
46,000
24,400
32,100
30,000
28,300
21,600
16,200
13,500
10,800
5,400
TCC
14
Max.
Inst.
Pickup
(X Plug)
Plug
Trip
or trip
ANSI
5,000
5,000
5,000 7
ANSI & ICCB
4,000
4,000
4,000 9
ANSI & ICCB
4,000
3,600
3,600 9
ANSI
3,200
3,200
3,200 13
ICCB
3,000
3,000
3,000 13
ANSI
4,000
3,000
3,000 9
ICCB
3,000
2,500
2,500 13
ANSI
3,200
3,200
2,400 13
ANSI & ICCB
2,000
2,000
2,000 15
ANSI & ICCB
1,600
1,600
1,600 15
ANSI & ICCB
1,600
1,600
1,200 15
ANSI & ICCB
1,600
1,600
1,000 15
ANSI & ICCB
800
800
800
15
ANSI & ICCB
800
800
400
15
ANSI & ICCB
800
800
150
15
NIS = not instantaneously selective. TCC = refer to time current curve.
ANSI = AKR, WavePro & Entelliguard
ICCB = Power Break II
MCP = motor circuit protector
Frame
Sensor
150A
60-35A
30-15A
97,500
100,000
81,000
100,000
100,000
52,500
81,600
74,000
67,400
40,000
21,200
14,600
TCC
TCC
TCC
100,000
100,000
93,700
100,000
100,000
52,500
90,000
81,300
73,000
39,600
23,100
17,400
12,800
TCC
TCC
100,000
100,000
100,000
100,000
100,000
64,400
100,000
100,000
100,000
48,100
27,000
19,300
13,700
TCC
TCC
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
43,500
27,300
17,600
TCC
TCC
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
80,100
41,900
23,400
TCC
TCC
15
16
250A Sensor FG
100-15A FB
64,700
69,000
53,000
100,000
85,000
34,000
54,000
49,000
44,000
25,000
16,200
13,500
11,000
TCC
TCC
64,700
69,000
53,000
100,000
85,000
34,000
54,000
49,000
44,000
25,000
16,200
13,500
11,000
TCC
TCC
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
71,200
44,100
35,000
TCC
TCC
17
300A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
TCC
NIS
NIS
TJ6
500A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
TCC
NIS
NIS
NIS
18
TJ6
450A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
TCC
NIS
NIS
TJ4
400A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
TCC
NIS
NIS
TJ4
350-300A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
10,800
NIS
NIS
TJ4
250A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
10,800
TCC
NIS
TF
225-200A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
10,800
TCC
NIS
TF
175-70A
31,500
32,400
29,160
37,440
35,100
24,300
28,080
29,250
27,000
21,600
16,200
13,500
10,800
5,400
NIS
19
TEY
15-60A
1/2/3
14,000
14,000
14,000
14,000
14,000
14,000
14,000
14,000
14,000
14,000
14,000
14,000
12,800
5,400
TCC
THHQB
125A
2
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
5,400
TCC
THHQB
15-100A
1/2/3
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
22,000
18,100
5,400
TCC
THQB
125A
2
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
5,400
TCC
THQB
15-100A
1/2/3
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
5,400
TCC
150A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
45,800
26,600
13,700
5,400
NIS
20
100A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
59,200
30,400
5,400
TCC
TECL
50A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
12,400
2,025
30A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
61,000
3,100
15A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
13,700
3A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
100,000
90,000
Amperes
SK
Frame
Sensor
Plug
Frame
1,200A
Sensor
1,200A
Plug
1,000A
1,200A SK
1,200
1,200
TCC
1,200A SK
1,200
1,000
NIS
1,200A SK
1,200, 800
800
NIS
1,200A SK
1,200, 800
700
NIS
1,200A SK, 600A SG 1,200, 800, 600 600
NIS
1,200A SK, 600A SG 800, 600
500
NIS
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Continued on next page
1,200A
1,200A
1,200,
800A
800A
10,800
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
1,200,
800A
700A
10,800
9,000
NIS
NIS
NIS
NIS
NIS
NIS
NIS
21
SK & SG
1,200,
1,200,
600A
600A
1,200,
800, 600A
800, 600A
600A
500A
10,800
10,800
9,000
9,000
TCC
7,200
NIS
6,300
NIS
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
SG
600A
600A
450A
10,800
9,000
7,200
6,300
TCC
NIS
NIS
NIS
NIS
SK & SG
1,200,
600, 400A
1,200,
800, 600A
400A
10,800
9,000
7,200
6,300
5,400
TCC
NIS
NIS
NIS
SG
600A
400A
350A
10,800
9,000
7,200
6,300
5,400
4,500
TCC
NIS
NIS
SK & SG
1,200,
600A
1,200,
800, 600A
300A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
TCC
NIS
Amperes
SG
600A
400A
250A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
4,050
1,200A SK, 600A SG 800, 600, 400
400
3,600
1,200A SK, 600A SG 800, 600, 400
350
3,150
1,200A SK, 600A SG 800, 600, 400
300
TCC
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
600A SG
150
125
NIS
600A SG
150
100
NIS
600A SG
150
80
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Frame
Sensor
Plug
Frame
Sensor
Plug
600A
400A
225A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
22
600A
400A
200A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
TCC
NIS
NIS
NIS
NIS
NIS
NIS
600A
400A
175A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
TCC
NIS
NIS
NIS
NIS
NIS
600A
400, 150A
150A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
TCC
NIS
NIS
NIS
NIS
600A
150A
125A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
TCC
NIS
NIS
NIS
600A
150A
100A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
TCC
NIS
NIS
600A
150A
80A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
TCC
NIS
600A
150A
60A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
TCC
Amperes
SK
1,200A
1,200A
1,200A
1,200A SK
1,200
1,200
NIS
1,200A SK
1,200
1,000
NIS
1,200A SK
1,200, 800
800
NIS
1,200A SK
1,200, 800
700
NIS
1,200A SK, 600A SG 1,200, 800, 600 600
NIS
1,200A SK, 600A SG 800, 600
500
NIS
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Frame
Sensor
Plug
Frame
Sensor
Plug
1,200A
1,200A
1,000A
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
23
800A
800A
800A
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
800A
800A
700A
10,800
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
800A
800A
600A
10,800
9,000
NIS
NIS
NIS
NIS
NIS
NIS
NIS
800A
800A
500A
10,800
9,000
7,200
NIS
NIS
NIS
NIS
NIS
NIS
800A
800A
450A
10,800
9,000
7,200
TCC
NIS
NIS
NIS
NIS
NIS
800A
800A
400A
10,800
9,000
7,200
6,300
TCC
NIS
NIS
NIS
NIS
800A
800A
350A
10,800
9,000
7,200
6,300
5,400
NIS
NIS
NIS
NIS
800A
800A
300A
10,800
9,000
7,200
6,300
5,400
4,500
TCC
NIS
NIS
Amperes
SG
600A
600A
600A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
NIS
1,200A SK
1,200, 800
700
NIS
1,200A SK, 600A SG 1,200, 800, 600 600
NIS
1,200A SK, 600A SG 800, 600
500
NIS
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
NIS = not instantaneously selective. TCC = refer to time current curve
.
Frame
Sensor
Plug
Frame
Sensor
Plug
600A
600A
500A
10,800
9,000
7,200
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
600A
600A
450A
10,800
9,000
7,200
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
24
400A
400A
400A
10,800
9,000
7,200
6,300
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
400A
400A
350A
10,800
9,000
7,200
6,300
5,400
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
400A
400A
300A
10,800
9,000
7,200
6,300
5,400
4,500
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
400A
400A
250A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
NIS
NIS
NIS
NIS
NIS
NIS
400A
400A
200A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
TCC
NIS
NIS
NIS
NIS
400A
400A
175A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
NIS
NIS
NIS
NIS
400A
400A
150A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
TCC
NIS
NIS
400A
400A
125A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
Amperes
SF
250A
250A
250A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
4,050
1,200A SK, 600A SG 800, 600, 400
400
3,600
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
600A SG
150
125
NIS
600A SG
150
100
NIS
600A SG
150
80
NIS
NIS = not instantaneously selective. TCC = refer to time current curve
.
Frame
Sensor
Plug
Frame
Sensor
Plug
250A
250A
225A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
25
250A
250A
200A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
250A
250A
175A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
NIS
NIS
NIS
NIS
NIS
NIS
NIS
250A
250A
150A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
TCC
NIS
NIS
NIS
NIS
NIS
250A
250A
125A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
250A
250A
110A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
250A
250A
100A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
TCC
NIS
NIS
NIS
250A
250A
90A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
NIS
NIS
NIS
250A
250A
70A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
NIS
NIS
Amperes
SE
150A
150A
150A
125A
150A
125A
1,200A SK
1,200
1,200
10,800 10,800
1,200A SK
1,200
1,000
9,000 9,000
1,200A SK
1,200, 800
800
7,200 7,200
1,200A SK
1,200, 800
700
6,300 6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400 5,400
1,200A SK, 600A SG 800, 600
500
4,500 4,500
1,200A SK, 600A SG 800, 600
450
4,050 4,050
1,200A SK, 600A SG 800, 600, 400
400
3,600 3,600
1,200A SK, 600A SG 800, 600, 400
350
3,150 3,150
1,200A SK, 600A SG 800, 600, 400
300
2,700 2,700
600A SG
400
250
2,250 2,250
600A SG
400
225
TCC
2,025
600A SG
400
200
NIS
1,800
600A SG
400, 150
150
NIS
NIS
600A SG
150
125
NIS
NIS
600A SG
150
100
NIS
NIS
600A SG
150
80
NIS
NIS
600A SG
150
60
NIS
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Frame
Sensor
Plug
Frame
Sensor
Plug
150A
125A
110A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
NIS
26
150A
100A
100A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
TCC
NIS
NIS
NIS
NIS
150A
100A
90A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
NIS
NIS
NIS
NIS
150A
80A
80A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
TCC
NIS
NIS
NIS
150A
80A
70A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
NIS
NIS
NIS
150A
60A
60A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
NIS
NIS
150A
50A
50A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
720
NIS
150A
50A
40A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
720
TCC
150A
30A
30A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
720
540
Amperes
Frame
Sensor
Trip
600A
1,200A SK
1,200
1,200
TCC
1,200A SK
1,200
1,000
NIS
1,200A SK
1,200, 800
800
NIS
1,200A SK
1,200, 800
700
NIS
1,200A SK, 600A SG 1,200, 800, 600 600
NIS
1,200A SK, 600A SG 800, 600
500
NIS
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Continued on next page
500A
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
27
450A
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
400A
10,800
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
350A
10,800
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
300A
10,800
9,000
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
250A
10,800
9,000
7,200
TCC
TCC
TCC
NIS
NIS
NIS
NIS
Amperes
Frame
Sensor
Trip
400A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
TCC
1,200A SK
1,200, 800
800
TCC
1,200A SK
1,200, 800
700
NIS
1,200A SK, 600A SG 1,200, 800, 600 600
NIS
1,200A SK, 600A SG 800, 600
500
NIS
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Continued on next page
350A
10,800
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
28
300A
10,800
9,000
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
250A
10,800
9,000
7,200
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
225A
10,800
9,000
7,200
6,300
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
200A
10,800
9,000
7,200
6,300
5,400
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
175A
10,800
9,000
7,200
6,300
5,400
TCC
TCC
TCC
TCC
NIS
NIS
NIS
NIS
NIS
150A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
TCC
TCC
TCC
NIS
NIS
NIS
NIS
125A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
TCC
TCC
TCC
NIS
NIS
NIS
Amperes
Frame
Sensor
Trip
225A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
TCC
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
600A SG
150
125
NIS
600A SG
150
100
NIS
600A SG
150
80
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Continued on next page
200A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
175A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
29
150A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
125A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
TCC
NIS
NIS
NIS
NIS
NIS
NIS
110A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
TCC
NIS
NIS
NIS
NIS
NIS
100A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
TCC
NIS
NIS
NIS
NIS
90A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
80A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
70A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
TCC
NIS
NIS
NIS
Amperes
Plug or
trip
Trip
225A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
600A SG
150
125
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Frame
Sensor
200A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
30
175A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
NIS
NIS
NIS
NIS
NIS
NIS
NIS
150A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
NIS
NIS
NIS
NIS
NIS
NIS
125A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
NIS
NIS
NIS
NIS
NIS
100A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
NIS
NIS
NIS
Amperes
Frame
Sensor
TEY
Plug
Trip 100/90A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
4,050
1,200A SK, 600A SG 800, 600, 400
400
3,600
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
600A SG
150
125
NIS
600A SG
150
100
NIS
600A SG
150
80
NIS
600A SG
150
60
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Continued on next page
80A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
70A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
31
60A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
NIS
NIS
NIS
NIS
NIS
NIS
NIS
50-40A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
NIS
35A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
NIS
NIS
NIS
NIS
30A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
NIS
NIS
NIS
25A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
NIS
NIS
20A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
720
NIS
15A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
720
540
Amperes
Frame
Sensor
Trip 100/90A
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
TCC
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
600A SG
150
125
NIS
600A SG
150
100
NIS
600A SG
150
80
NIS
600A SG
150
60
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
80A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
70A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
32
60A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
50A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
NIS
NIS
NIS
NIS
NIS
NIS
NIS
45A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
NIS
NIS
NIS
NIS
NIS
NIS
40/35A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
NIS
30A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
NIS
NIS
NIS
NIS
25A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
NIS
NIS
NIS
20A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
NIS
NIS
15A
10,800
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
720
NIS
Amperes
Frame
Sensor
Trip 100/90A
80A
1,200A SK
1,200
1,200
25,900 25,900
1,200A SK
1,200
1,000
9,000
9,000
1,200A SK
1,200, 800
800
7,200
7,200
1,200A SK
1,200, 800
700
6,300
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
5,400
1,200A SK, 600A SG 800, 600
500
4,500
4,500
1,200A SK, 600A SG 800, 600
450
TCC
4,050
1,200A SK, 600A SG 800, 600, 400
400
NIS
3,600
1,200A SK, 600A SG 800, 600, 400
350
NIS
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
NIS
600A SG
400
250
NIS
NIS
600A SG
400
225
NIS
NIS
600A SG
400
200
NIS
NIS
600A SG
400, 150
150
NIS
NIS
600A SG
150
125
NIS
NIS
600A SG
150
100
NIS
NIS
600A SG
150
80
NIS
NIS
600A SG
150
60
NIS
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
33
70A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
60A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
50A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
NIS
NIS
NIS
NIS
NIS
NIS
NIS
45A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
NIS
NIS
NIS
NIS
NIS
NIS
40/35A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
NIS
NIS
NIS
NIS
NIS
30A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
NIS
NIS
NIS
NIS
25A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
NIS
NIS
NIS
20/15A
25,900
9,000
7,200
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
1,350
1,125
900
TCC
NIS
Downstream: Circuit breakers for motor control application with fused limiters
Amperes
TECL
Plug or
trip
Trip
150A
1,200A SK
1,200
1,200
13,658
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
6,300
1,200A SK, 600A SG 1,200, 800, 600 600
5,400
1,200A SK, 600A SG 800, 600
500
4,500
1,200A SK, 600A SG 800, 600
450
4,050
1,200A SK, 600A SG 800, 600, 400
400
3,600
1,200A SK, 600A SG 800, 600, 400
350
3,150
1,200A SK, 600A SG 800, 600, 400
300
2,700
600A SG
400
250
TCC
600A SG
400
225
TCC
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
Frame
Sensor
100A
30,432
17,667
9,081
6,300
5,400
4,500
4,050
3,600
3,150
2,700
2,250
2,025
1,800
TCC
34
50A
100,000
59,300
29,900
19,900
12,400
7,100
5,100
3,600
3,150
2,700
2,250
2,025
1,800
1,350
30A
100,000
100,000
100,000
97,300
61,000
35,100
25,500
17,900
11,900
7,500
4,300
3,100
2,200
1,350
15, 7 & 3A
100,000
100,000
100,000
100,000
100,000
100,000
100,000
84,700
55,500
34,000
19,100
13,700
9,400
3,800
Amperes
Plug or
Frame
Sensor
trip
600A Sensor, 600-350A Plugs
1,200A SK
1,200
1,200
10,800
1,200A SK
1,200
1,000
9,000
1,200A SK
1,200, 800
800
7,200
1,200A SK
1,200, 800
700
NIS
1,200A SK, 600A SG 1,200, 800, 600 600
NIS
1,200A SK, 600A SG 800, 600
500
NIS
1,200A SK, 600A SG 800, 600
450
NIS
1,200A SK, 600A SG 800, 600, 400
400
NIS
1,200A SK, 600A SG 800, 600, 400
350
NIS
1,200A SK, 600A SG 800, 600, 400
300
NIS
600A SG
400
250
NIS
600A SG
400
225
NIS
600A SG
400
200
NIS
600A SG
400, 150
150
NIS
NIS = not instantaneously selective. TCC = refer to time current curve.
35
36
400A
9,772
8,144
6,964
5,936
TCC
NIS
NIS
300A
9,772
8,144
6,964
5,936
4,956
4,016
NIS
37
150A
9,772
8,144
6,964
5,936
4,956
4,016
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
NIS
NIS
NIS
125A
9,772
8,144
6,964
5,936
4,956
4,016
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
NIS
NIS
38
90A
9,772
8,144
6,964
5,936
4,956
4,016
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
NIS
70A
9,772
8,144
6,964
5,936
4,956
4,016
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
1,020
39
90A
2,000
1,800
1,600
1,400
1,200
NIS
NIS
NIS
NIS
70A
2,000
1,800
1,600
1,400
1,200
1,000
TCC
NIS
NIS
40
40A
9,772
8,144
6,964
5,936
4,956
4,016
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
1,020
30-15A
9,772
8,144
6,964
5,936
4,956
4,016
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
1,020
41
40A
2,000
1,800
1,600
1,400
1,200
1,000
880
800
720
560
1,593
1,312
1,141
1,024
910
799
690
TCC
NIS
NIS
NIS
30-15A
2,000
1,800
1,600
1,400
1,200
1,000
880
800
720
560
1,593
1,312
1,141
1,024
910
799
690
622
510
NIS
NIS
70A
60A
50/45A
40A
35A
30-15A
9,772
8,144
6,964
5,936
4,956
4,518
3,212
NIS
4,860
4,048
3,644
3,264
2,856
NIS
NIS
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
NIS
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
1,020
42
40A
35A
30A
25A
20A
15A
2,000
1,800
1,600
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
NIS
NIS
NIS
NIS
NIS
1,593
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
NIS
NIS
NIS
NIS
1,593
1,312
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
880
800
NIS
NIS
1,593
1,312
1,141
1,024
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
880
800
720
NIS
1,593
1,312
1,141
1,024
910
799
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
880
800
720
560
1,593
1,312
1,141
1,024
910
799
690
622
NIS
NIS
NIS
43
70A
60A
50/45A
40A
35A
30A
25-15A
9,772
8,144
6,964
5,936
4,956
4,518
3,212
NIS
4,860
4,048
3,644
3,264
NIS
NIS
NIS
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
NIS
4,860
4,048
3,644
3,264
2,856
NIS
NIS
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
NIS
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
NIS
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
NIS
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
NIS
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
NIS
9,772
8,144
6,964
5,936
4,956
4,518
3,212
2,412
4,860
4,048
3,644
3,264
2,856
2,448
2,040
1,632
1,428
1,224
1,020
44
40A
35A
30A
25A
20A
15A
2,000
1,800
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
NIS
NIS
NIS
NIS
NIS
1,593
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
NIS
NIS
NIS
NIS
1,593
1,312
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
880
800
NIS
NIS
1,593
1,312
1,141
1,024
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,000
1,800
1,600
1,400
1,200
1,000
880
800
720
NIS
1,593
1,312
1,141
1,024
910
799
NIS
NIS
NIS
NIS
NIS
45
46
15-3A
100,000
100,000
100,000
100,000
100,000
100,000
59,000
23,800
100,000
100,000
88,000
62,100
40,600
24,900
14,000
6,900
4,500
2,800
47
15-3A
13,100
9,400
6,500
4,200
2,600
1,500
1,000
700
720
560
6,400
3,500
2,200
1,600
1,100
799
690
622
510
401
332
Amperes
175A
150A
125A
100A
7,968
8,000
5,120
5,096
4,800
4,000
3,600
TCC
NIS
NIS
4,800
4,000
3,600
TCC
NIS
NIS
NIS
NIS
NIS
7,968
8,000
5,120
5,096
4,800
4,000
3,600
3,200
TCC
NIS
4,800
4,000
3,600
3,200
TCC
NIS
NIS
NIS
NIS
7,968
8,000
5,120
5,096
4,800
4,000
3,600
3,200
2,800
TCC
4,800
4,000
3,600
3,200
2,800
TCC
NIS
NIS
NIS
7,968
8,000
5,120
5,096
4,800
4,000
3,600
3,200
2,800
2,400
4,800
4,000
3,600
3,200
2,800
2,400
TCC
TCC
NIS
7,968
8,000
5,120
5,096
4,800
4,000
3,600
3,200
2,800
2,400
4,800
4,000
3,600
3,200
2,800
2,400
2,000
1,800
NIS
48
Max. Inst.
Pickup
(X Plug)
49
40-15A
7,968
8,000
5,120
5,096
4,800
4,000
3,600
3,200
2,800
2,400
4,800
4,000
3,600
3,200
2,800
2,400
2,000
1,800
1,000
Amperes
80A
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
NIS
50
30A
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
TCC
TCC
25A
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
723
TCC
20A
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
723
722
15A
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
723
722
Trip
Max.
Inst.
Pickup
(X Plug)
10070A
80A
225
10
TCC
1,800
200
10
NIS
TCC
175
10
NIS
TCC
150
10
NIS
NIS
125
10
NIS
NIS
TF, THF
225
125
10
NIS
NIS
110
12
NIS
NIS
100
12
NIS
NIS
90
12
NIS
NIS
80
12
NIS
NIS
70
12
NIS
NIS
225
NIS
2,025
200
NIS
NIS
TQD
225
175
NIS
NIS
150
NIS
NIS
125
NIS
NIS
NIS = not instantaneously selective. TCC = refer to time current curve
.
Trip
60A
50A
45A
40A
35A
30A
25A
20A
15A
1,800
1,600
TCC
TCC
NIS
NIS
NIS
NIS
NIS
NIS
NIS
2,025
1,800
NIS
NIS
NIS
1,800
1,600
1,400
1,200
TCC
TCC
NIS
NIS
NIS
NIS
NIS
2,025
1,800
1,575
1,350
NIS
1,800
1,600
1,400
1,200
TCC
TCC
TCC
NIS
NIS
NIS
NIS
2,025
1,800
1,575
1,350
NIS
1,800
1,600
1,400
1,200
1,000
1,000
TCC
TCC
TCC
NIS
NIS
2,025
1,800
1,575
1,350
1,125
1,800
1,600
1,400
1,200
1,000
1,000
1,003
TCC
TCC
TCC
NIS
2,025
1,800
1,575
1,350
1,125
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
TCC
TCC
2,025
1,800
1,575
1,350
1,125
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
723
TCC
2,025
1,800
1,575
1,350
1,125
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
723
722
2,025
1,800
1,575
1,350
1,125
1,800
1,600
1,400
1,200
1,000
1,000
1,003
1,000
864
723
722
2,025
1,800
1,575
1,350
1,125
51
This information is based on data available at the time of printing (August 2008) and is believed
to be accurate, but GE makes no warranty or guarantee regarding the accuracy of the
information.
DET-537B (09/08)