FB22M 22kVA

Blue Force Series POWERED BY: BAUDOUIN - MARELLI

POWER PARAMETERS

Generating Rates STANDBY PRIME POWER

Power kVA 22 20
Power kW 17.6 16
Standard Voltage V 400/230
Rated at power factor Cos Ø 0,8

1500 50 3 Three phase Water cooled Soundproof Diesel

Standby Rating (ESP) Prime Rating (PRP)


According to ISO 8528-1:2005, Emergency standby power is According to ISO 8528-1:2005, Prime power is the maximum
the maximum power available during a variable electrical power power which a generating set is capable of delivering
sequence, under the stated operating conditions, for which a continuously whilst supplying a variable electrical load when
generating set is capable of delivering in the event of a utility operated for an unlimited number of hours per year under the
power outageor under test conditions for up to 200h of operation agreed operating conditions with the maintenance intervals
per year with the maintenance intervals and procedures being and procedures being carried out as prescribed by the
carried out as prescribed by the manufacturers. The permissible manufacturer. The permissible average power output (Ppp)
average power output over 24h of operation shall not exceed over 24h of operation shall not exceed 70% of the PRP.
70% of the ESP
G2 class load acceptance in accordance with ISO 8528-5:2005

DIMENSION / WEIGHT / FUEL TANK


Dimension W x L x H (mm) Weight (kg) Tank Capacity (lt)

Canopy 1100 x 1900 x 1270 728 140

H Open Type 1100 x 1900 x 1170 584 140


H
NOTE: For reference only, do not use for installation design. Please contact your local dealer for exact weight and dimensions.

L w
L w NOISE db(A) 7mt@70-75db(A)

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 1 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
Blue Force Series POWERED BY: BAUDOUIN - MARELLI

BLUE FORCE SERIES


The FMT Group Blue Force generator was
created to fulfill the needs of middle range business
needed. Blue Force generators are available
in three phase specification.
Our engineers and the projection department created
this product to fulfill the special needs of all the
clients. FMT engineers has researched about more
solution to regenerate electric power from Baudouin
Diesel Engines.
They decide that Baudouin Engines has perfect match
with Marelli Alternators. Blue Force is one of the
best solution in the market to have a power without
any problem.

BASE FRAME
FMT Group produces her our base frames for all
ranges in accordance with international standards.
Base frames are made of plates or special profiles of
steel providing high endurance against to
vibration and stress

FUEL TANKS
Fuel tanks for the generator sets up to 1000 kVA are Fmt fuel tanks are equipped with:
designed to be included by base frame. Larger sets • Filling cap
require a free standing fuel tank. Fuel tanks are made • Tank ventilation
• Fuel outlet valve
of plate steel or other suitable materials.FMT Group • Fuel return point
Low fuel-level
ensures that the fuel tanks to be produced in • Tank drainage plug warning sensor
accordance with relevant standard. • Sediment trap section
• Level gauge pipe

BODY DESIGN
Our mechanical engineers improved the compact respond to all you emergencies. It is safe and fulfills
design of these generators and as such now due to your need for uninterrupted energy. This compact
the thin modular design the compact series diesel design has visual and environmental features that
generators carry inside all the main parts starting make it easy to adapt everywhere. This generator
from the engine, alternator, cooling system, electric was designed keeping in mind the environment and
system, exhaust system and fuel system. the ecological system. The cabin of the compact
This generator is easy to transport and to install to series generators is soundproof and weatherproof.

EXHAUST SYSTEM
In our generators all the exhaust system and the gases FMT Group made this special design to protect you
coming form it are placed inside the cabin (the body of and everyone that maintains the generator from getting
the generator). This special design makes it possible hurt.
for the gases to come out easily and without noise.

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 2 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
Blue Force Series POWERED BY: BAUDOUIN - MARELLI

Low fuel consumption High efciency Easy lift Low noise


ISO 9001:2008
registered company

engine alternator control panel

Baudouin panel
Power Solutions since 1891
GEN-A

FEATURES
• Galvanized steel that provides extra strength, durability and protection
• Tightly structure, excellent design
• Easy access to serviceable parts
• Double swinging doors for ease of service
• Doors have high quality gaskets to avoid leakage of sound
• LCD display shows system status and setup information
• Adequate ventilation to meet air requirement for combustion and heat removal

STANDARD SPECIFICATION
• Diesel engine • Antivibration shock absorbers
• Water cooled • Flexible fuel connection hoses
• Radiator with mechanical fan • Single bearing, class H alternator
• ATS automatic transfer switch 4P • Industrial exhaust silencer and steel bellows supplied separately
• Protective grille for rotating and hot parts • Static battery charger
• Electric starter and charge alternator • Starting battery (with lead acid) including rack and cables
• Engine coolant heater • Battery isolator
• Base frame with integrated fuel tank • Manual for application and installation

SAFETY FEATURES

High water temperature Protective earth point

Low lube oil pressure Emergency stop push-button

A R R A N T Y .. ! 2 YE
ARS W
W AR RANTY..! 2 YE
TY..! 2 YEARS FMT GROUP SYSTEMS CARRY A STANDARD TWENTYFOUR-MONTH
WARRANTY, WHICH IS ONE OF THE LONGEST STANDARD
WARRANTIES IN THE ELECTRICITY AND GENERATOR INDUSTRIES

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 3 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
Blue Force Series POWERED BY: BAUDOUIN - MARELLI

HORSE POWER
Durable Energy
Unique design Baudouin
The diesel engine is the most important part of the genset. Is the prime mover that drives the generator (alternator) to produce
electricity. All diesel engines are similar to each other in the concept but they different in many aspects such as the number of
cylinders, if the cylinders are inline or Vtype, how the fuel is delivered to the cylinders, governing system, cooling system, air
charging system, air intake system. All these details affect the decision of which engine to use and which performance is expected.
Engines are rated in KW or HP. Their performance is measured in their fuel consumption in filters or gallons per KWh produced,
its thermal effciency, noise level, lube oil consumption and exhaust gas emissions.

ENGINE SPECIFICATION

GENERAL DATA
Model 4M06G20/5
No. of cylinder / Configuration IN-LINE 4
Displacement 2.3 lt
Bore / Stroke 89mm x 92mm
Compression ratio 17.5:1
Aspiration Naturally Aspirated
Governor type Electronic
Cooling system Water
Coolant capacity 16 lt
Speed / Frequency 1500 rpm / 50Hz
Fuel consumption 100% power used 4.8 lt/h
Fuel consumption 75% power used 3.7 lt/h
Fuel consumption 50% power used 2.6 lt/h

LUBRICATION SYSTEM
Oil capacity 11.5 lt

VENTILATION SYSTEM
Intake air flow 1.38 m3/min
Radiator cooling air 48 m3/min

EXHAUST SYSTEM
Exhaust outlet temperature 530 0C
Exhaust gas flow 4.5 m3/min

+ -
ELECTRICAL SYSTEM
VDC 12 V

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 4 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
Blue Force Series POWERED BY: BAUDOUIN - MARELLI

SELF EXCITED
STRONG ROTOR
Isolated Stator Power Solutions since 1891

Marelli alternator has been designed for three phase and mono phase.
They are brushless type and are controlled by AVR card. The windings have
been industrially produced to give maximum efficiency in the production of
energy. Throughout the AVR card system the output voltage is always stable.
The smart AVR is a professional controller than enables the whole operation
of excitement. Marelli alternator is protected by a special cabin that enables
the electrical connections.

ALTERNATOR SPECIFICATION

GENERAL DATA
Model MXB-E 160 LA4
No. of Phase 3
Power Factor 0.8
No of Bearing SINGLE
No of Poles 4
No of Leads 12
Insulations Class H
Voltage Regulation (Steady State) ±1%
Degree of Protection IP 23
Excitation System Self excited, AVR, Brushless
Connection System STAR
Frequency 50 Hz
Voltage Output 400/230VAC
Rated Power (standby) 22 kVA
Efficiency 85.4%

Alternator Structure
AVR Terminal outgoing

Exciter
Fan Ectier
Rotor
Coupling Disc
Stator

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 5 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
GEN-A SMART LOGIC SUPER CONTROL FULL PROTECTION

DESCRIPTION
The GEN-A series are next generation genset control GEN-A GENSET
AMF CONTROL UNIT

u n i t s c o m b i n i n g mu l t i - f u n c t i o n a l i t y a n d w i d e
communication possibilities together with a reliable STATUS MAINS

and low cost design. The unit complies and mostly ALARM

exceeds world’s tightest safety, EMC, vibration and WARNING

SERVICE
REQUEST

environmental standards for the industrial category. LOAD

Software features are complete with easy firmware


GENSET
upgrade process through USB port. The Windows PGM

based PC software allows monitoring and programming


A
through USB, serial and GPRS. The PC based Rainbow
Scada software allows monitoring and control of an TEST RUN AUTO STOP

unlimited number of gensets from a single central location.

FEATURES

• Diesel and gas genset support • Weekly operation schedule • Combat mode support
• 400Hz operation support • Dual mutual standby with equal • Multiple nominal conditions
• 400 event logs,full snapshot aging of gensets • Contactor & MCB drive
• All parameters front panel editable • Manual “speed fine adjust” on • 4 quadrant genset power counters
• 3 level configuration password selected ECUs • Mains power counters
• 128x64 graphical LCD display • Automatic fuel pump control • Fuel filling counter
• Downloadable languages • Disable protections feature • Fuel consumption counter
• Waveform display of V & I • Excess power protection • Modem diagnostics display
• Harmonic analysis of V & I • Reverse power protection • Configurable through USB,RS-485
• 16Amp MCB & GCB outputs • Overload IDMT protection and GPRS
• 8 configurable digital inputs • Load shedding, dummy load • Free configuration program
• Inputs expandable to 40 • Multiple load management • Allows SMS controls
• 6 configurable digital outputs • Current unbalance protection • Ready for central monitoring
• Outputs expandable to 38 • Voltage unbalance protection • Mobile genset support
• 3 configurable analog inputs • Fuel filling & fuel theft alarms • Automatic GSM geo-location
• Both CANBUS-J1939 & MPU • Battery back-up real time clock • GPS connectivity (RS232)
• 3 configurable service alarms • Idle speed control • Easy USB firmware upgrade
• Multiple automatic exerciser • Battery chargerun enabled • IP65 rating with standard gasket

MEASUREMENTS FUNCTIONALITIES TOPOLOGIES


• Mains & genset PN/PP voltages • AMF unit • 3 ph 4 w, star & delta
• Mains & genset frequency • ATS unit • 3 ph 3 w, 2 CTs
• Mains & genset phase currents • Remote start controller • 2 ph 3 w
• Mains & genset neutral currents • Manual start controller • 1 phase 2 wires
• Mains & genset, phase & total, • Engine controller
kW, kVA, kVAr, pf • Remote display panel
• Engine speed • Harmonic analysis of V & I
• Battery voltage

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 6 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
GEN-A SMART LOGIC SUPER CONTROL FULL PROTECTION

COMMUNICATIONS

• 4-band GPRS modem (optional)


• USB Device
• RS-485 (2400-57600baud)
• RS-232 (2400-57600baud)
• J1939-CANBUS
• Geo-locating through GSM
• GPS support (RS-232) SUPPLY

• Internet Central Monitoring SIM


CARD
GPRS
MODEM
GEN-A GENSET
AMF CONTROL UNIT

• SMS message sending


MAINS
STATUS
• E-mail sending RS 232 ALARM

• Free PC software: Rainbow Plus


WARNING

SERVICE
REQUEST
LOAD

• Modbus RTU
GENSET

PGM

TEST RUN AUTO STOP

GEN-A GENSET
AMF CONTROL UNIT

MAINS
STATUS

ALARM

WARNING

SERVICE
REQUEST
LOAD

GENSET

PGM

TEST RUN AUTO STOP

TECHNICAL SPECIFICATIONS
Alternator voltage: 0 to 300 V-AC (Ph-N) Storage temperature: -40°C to 80°C (-40 to +176°F)
Alternator frequency: 0-600 Hz. Maximum humidity: 95% non-condensing.
Mains voltage: 0 to 300 V-AC (Ph-N) IP Protection: IP65 from front panel, IP30 from the rear
Mains frequency: 0-600 Hz. (with gasket)
Topology: 1-2-3 phases, with or without neutral Dimensions: 200 x 148 x 46mm (WxHxD)
DC Supply Range: 8.0 to 36.0 V-DC. Panel Cut-out Dimensions: 176 x 121 mm minimum.
V-A-cos Accuracy: 0.5% + 1 digit Weight: 450 g (approx.)
kW-kVA-kVAr Accuracy: 1.0% + 1 digit Case Material: High Temperature, non-flammable ABS/PC
Current consumption: 500 mA-DC max. Installation: Flat surface mounting on a Type 1 enclosure.
Current Inputs: from current transformers. ../5A. Rear retaining plastic brackets.
Digital inputs: input voltage 0 to 36 V-DC.
Analog input range: 0-5000 ohms.
Mains and genset contactor outputs: 16Amps@250V
CONFORMITY
DC Outputs: Protected mosfet semiconductor outputs, EU Directives Conformity
rated 1Amp@28V-DC -2006/95/EC (low voltage)
Cranking dropouts: survives 0V for 100ms. -2004/108/EC (electro-magnetic compatibility)
Magnetic pickup voltage: 0.5 to 50Vpk. Norms of reference:
Magnetic pickup frequency: 0 to 20000 Hz. EN 61010 (safety requirements)
Charge Alternator Excitation: 2W.
EN 61326 (EMC requirements)
Display Screen: 2.9”, 128x64 pixels
UL & CSA Compatibility:
USB Device: USB 2.0 Full speed
RS-485 Port: selectable baud rate (2400-57600baud) -UL 6200, Controls for Stationary Engine Driven
RS-232 Port: selectable baud rate (2400-57600baud) Assemblies (Certificate# - 20140725-E314374)
Operating temperature: -20°C to 70°C (-4 to +158 °F) -CAN/CSA C22.2 No.14-13–Industrial Control Equipment

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 7 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
SMART LOGIC SUPER CONTROL FULL PROTECTION

GEN-A
L1
L2
L3
MAINS

*1 Connect to the engine body, close to the senders.


N

To BMS
RS-232

USB-DEVICE
26 485-A
25 485-B
MN-C 72

*2
24 PGND

To ECU

*2 Ground from one end only.


FUSE MN-L1 71
70
FUSE

*2
MN-L2 69 CANL 23
FUSE J1939-L
68 CANH 22
MN-L3 J1939-H
67 21
MPU- / PGND

MPU
66 MPU+ 20

*2
MN-N 65
MC

IN 8 19

8 to 36Vdc, 500mA max


Low Coolant Level
IN 7 18
Force OFF Mode

300Vac, 0-600 Hz
IN 6 17
L1L2 L3 N

Spare Input 3

0.2 to 6.0 Aac


64 I 3- IN 5 16
Spare Input 2
LOAD

63 I 3+ IN 4 15
Spare Input 1
62 I 2- IN 3 14
Emergency Stop
61 I 2+ IN 2 13
High Temp
60 I 1- 12 IN 1
Low Oil Pressure
59 I 1+
!
GC

SGND 11 *1 Sender Gnd


SND 3 10
Fuel Lev. Sender
ANTENNA
G-N 58 SND 2 9
57 Temp. Sender
SND 1 8
GSM

G-L3 56 Oil Press. Sender


FUSE CHG 7
ALTERNATOR

D+ / WL Charge Alternator
55 OUT 4 6 Preheat
FUSE G-L2 54
CARD

OUT 3 5 Alarm
SIM

53 4
OUT 2 Fuel
FUSE G-L1 52 OUT 1 3
EXTENSION

G-C 51 Crank

Starter
BAT - 2

Motor
BAT + 1 Fuse

S
I/O

BATTERY 12/24V
N
L1
L2
L3

Display Fleet Display on Map, online monitoring

Waveform Display Graphical Harmonics Display Digital Harmonics Display

Real time monitoring

Harmonic analysis & Waveform Smartphone Support

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 8 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
FB22M 22kVA
SMART LOGIC SUPER CONTROL FULL PROTECTION

eletric ats system


Automatic Transfer Switches
An ATS is a device that interfaces with a generator and the yours electrical system. It monitors the
utility power and signals the generator to start if the utility power goes out of spec or drops out
entirely (blackout). Backup power is now fed to the main utility panel or an emergency panel via the
ATS. All FMT group generators has the ATS system.
NEMA LS1

Generating Rates STANDBY PRIME POWER

Power kVA 22 20
Voltage 400/230 VAC Current A 31.8 28.9
Rated at power factor Cos Ø 0,8

MODEL ATS Dimension (mm)


VOLTAGE CAPACITY AMPS
CONFIGURATION PANEL MODEL WxLxH

400/230 VAC 3P5-V400-GENA ATSXP 63A 4P 63A 4P 275 x 500 x 605

A
1 2 3

LED INDICATOR
4 5 6

OPEN
Electric

MAIN STANDBY
POWER ON

ATS professional XP series


POWER
OFF

Manual

ATS XP 63A 4P

Warning, Live Terminal


s

ATSXP 63A 4P
H

L w

Mob: +355 (0) 69 40 09 355 e-mail: info@fmtgroup.al web: www.fmtgroup.al DATA SHEET 9 of 10
Address: “Rruga e Aeropor t SH60”, 2km from Tirana Interna onal Airport, Rinas - Fushe Kruje - Albania
These details shown on this data sheet are intended for guidance only. Fmt Group reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
ALBANIA:
Address: “Rruga e Aeroportit SH60”,
2km from Tirana International Airport,
Rinas - Fushe Kruje
Mob: +355 (0) 69 20 64 458
Mob: +355 (0) 69 40 09 193
Mob: +355 (0) 69 70 57 620
e-mail: info@fmtgroup.al
KOSOVO:
Str. Magjitralja Prishtine - Ferizaj, Km5
Cagllavice-Prishtine
MONTENEGRO:
Str. Tuzi BB - Podgorice
FOR MORE INFORMATION CLICK ON OUR SITE’s

www.fmtgroup.al www.fmtgenerator.com www.fmtengine.com www.fmtalternator.com

You might also like