SITE INSPECTION AND TEST RECORD

Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 1 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

1. RELAY CHARACTERISTICS
Type No.:

P545
P545311A3M0510
K
30068149

Model No :
Serial Number
Firmware Version :

Designation :

87L/21/67N /79

Nominal Current :

1/5 A

Nominal Voltage :Vn


Aux. Volts : Vx

100- 120 VAC 50/60 HZ

110-250 VDC 100-240 VAC

2.1 CT & VT DATA


CT rated primary current set as
CT rated secondary current set as
Ignd-CT rated primary current set as
Ignd-CT rated secondary current set as
Rated primary voltage (L-L) set as
Rated secondary voltage (L-L) set as

1200 A
1.0A
1200 A
1.0A
110 KV
100 V

3. PRELIMINARY CHECKS
Relay damaged?
Rating information correct for installation?
Case earth installed?
External wiring checked against diagram?
Test block connections checked?
LCD front panel display
Clock set to local time?

4. GENERAL CHECKS

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 2 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1
Checking

Results

Dry cell battery voltage (Remove battery isolation strip)


Auxiliary voltage value on terminals M2 ( + ) and M1 ( - )

Measured FIELD SUPPLY Voltage M7 M9 and M8 M10


Watchdog contact
when relay OFF

Terminals M11 and M12

Closed

Terminals M13 and M14

Open

Watchdog contact
when relay ON

Terminals M11 and M12

Open

Terminals M13 and M14

Closed

Check if the frequency is set on required value


Clock set-up, remove auxiliary supply for 30 seconds check date & time
Trip relay LED operation check
Alarm relay LED operation check
Out of service relay LED operation check
Healthy relay LED operation check

5. DISPLAY READINGS
Circuit

Injected value

VOLTAGE
57.73

CURRENT

Tested by:
Name : Eng. Mohamed
Signature & Date :

1.0 A
Phase A / 0
Phase B / -120
Phase C / 120

Shokry

Phases

Expected value

VAN

63.51 KV

VBN

63.51 KV

VCN

63.51 KV

VAB

110 KV

VBC

110 KV

VCA

110 KV

IA

1200

IB

1200

IC

1200

IN

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Displayed value
PRIMARY

SECANDRY

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 3 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

FUNCTIONAL TESTS

Current differential bias characteristic (87-1)


Item
1
2
3
4
5

Description

Setting

IS1
Is2
K1
K2
T

0.20 A
2.0 A
30 %
150 %
0 Sec

Pick-up & Time test:*NOTE:.


The Relay will be tested at loopback internal mode
It should be noted that the minimum operating current is related, but not equal to, the Is1 SETTING
Consider a single end fed fault with no load but fault current, I:|Idiff| = I
|Ibias| = I
Assuming |Ibias| < Is2, then, using the equations from section 2.1(from manual), the relay will operate if:|Idiff| > k1.| Ibias| + Is1 or
I > k1.I + Is1 or
I> Is1 / (1 - 0.5 k1)
The minimum operating current is therefore a function of the Is1 and k1 settings. Since k1 is
Recommended to be set to 30%, the minimum operating current will be:Imin = 1.176 1s1

I Diff I > ( k1 * I I Bias I + Is1 )/2 = 0.118 A


Fault
Type

Expected Pickup
In Amp

Actual Pickup
In Amp

Drop-off
In Amp

Expected Trip
Time
in m-sec

Actual Trip Time


in m-sec at
2 x I Pickup

A-N

0.118 A

0.12

0.087

<40 ms

29.5 ms

B-N
C-N

0.118 A
0.118 A

0.119
0.119

0.088
0.088

<40 ms
<40 ms

26.3 ms
28.7 ms

Lower slope test (Injected current < Is2)


|diff| > ( k1.| bias| + s1)/2 = 0.25 A

Bias current
injected in
phase (Amps)

Differential
current injected
in phase

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Expected
differential
current for
tripping
(Amp)

Measured value
of diff. current
(Amp)

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Expected Trip
Time
in m-sec

Actual Trip Time


in m-sec at
2 x I Pickup

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

ISKAN S/S 380 KV /110 KV


A
1.0

Page 4 of 14

Panel / Designation / Location no.:

B
X

1.0

R08.1

C
X

1.0

Project no.:

0.25 A
0.25 A
0.25 A

<40 ms
<40 ms
<40 ms

Upper slope test (Injected current > Is2)


|diff| > (k2.| bias| - (k2 - k1). s2 + s1)/2=1.15A

Bias current
injected in
phase (Amps)
A
3.0

Differential
current injected
in phase

B
X

3.0

Measured value
of diff. current
(Amp)

Expected Trip
Time
in m-sec

Actual Trip Time


in m-sec at
2 x I Pickup

1.15 A
1.15 A
1.15 A

1.155
1.155
1.156

<40 ms
<40 ms
<40 ms

30.7
32.8
33.5

C
X

3.0

Expected
differential
current for
tripping
(Amp)

7-Distance protection (21-1) AttachmentsResistive Zone Reach check (quadrilateral characteristics only
Item
1

Description
Print out from FREJA attached

Checked
Ok

Impedance tolerance: +/- 5% for zone 1 and +/- 10 % for other zones.
PH-E (G): - Resistive reach: Rn (/Loop) = RGn ()/ (1+Kz).
- Reactive reach: Xn (/Loop) = Zn () * sin (LG)
- Compensation factor KZ = 1/3((Zo-Z1)/Z1).
- Line impedance ZLG = RLG+J XLG = 1/3(2*ZLph +ZOL)
PH-PH (PH): - Resistive reach: Rphn (/ph) = Rphn (/Loop) / 2.
- Reactive reach: Xn () = Zn () * sin (Lph).
- Line impedance ZLph = RLph+J XLph.

Distance OPERATING TIME TESTING:


Item

Tested by:
Name : Eng. Mohamed
Signature & Date :

Description

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Checked
Witnessed by: SEC-WOA-CSD
Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 5 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV


1

.2.3

Project no.:

R08.1

Print out from FREJA attached

Ok

Distance protection scheme testing

Setting:
Aid Dist delay

I.

0.0

m sec

Permissive Under Reach Scheme:


Send logic: CS = ZM1
:
Trip logic: Trip = ZM2 + CR :
Trip logic: Trip = ZM2 w/o CR :

II.

Permissive Over Reach Scheme:


Send logic: CS = ZM2
:
Trip logic: Trip = ZM2 + CR :
Trip logic: Trip = ZM2 w/o CR : :

III.

29
14
414

m sec
m sec
m sec

14 m sec
29 m sec
427 m sec

Current Reversal Logic Check (Permissive Over Reach Scheme):


Apply a reverse / forward fault to check: t rev guard:
Fault type
Reverse/
forward

IV.

V.

t rev guard setting (m sec)

t rev guard measured (m sec)

150

162.1

Weak End Infeed Echo (Permissive over reach Scheme):

Apply a short pulse to DIST Channel Receive Input Without any fault Injection and check
Channel send is given: [ Ok ]

Operating time

26.7

m sec

Weak End Infeed Trip (Permissive over reach Scheme):

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 6 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

Setting
WI V< V thresh = 45 V
WI trip delay
= 60 m sec
phase

R
S
T

U ph setting
(V)

U ph measured
(V)

Remark

45

45.07
45.05
45.04

OK
OK
OK

Start at ph voltage more than setting value and go down gradually and apply send signal each time and check at
which value will come ECHO trip

Measured WI Trip time =

73.4

m sec

VI. Blocking 1 Scheme:


Send logic: CS = ZM4
: 36
Trip logic: Trip = ZM2 w/o CR : 21
Trip logic: Trip = ZM2 with CR : 427
.4

m sec
m sec
m sec

Distance protection Power Swing Blocking - PSB


Blocked zone for Power Swing Blocking
Power swing blocking delay time

.4

Z1-Z2-Z3 =OK
Set

Measured

0.5 Sec.

0.55 Sec

Distance protection Switch On To Fault - SOFT


1-SOTF BY C.B CLOSING BI:SETTING:Zone concerned by sotf: Z1,Z2
Sotf pulse time set=500 ms
Check sotf work with concerned zone
Check sotf trip time at fault at Z1= 21
ms
Z2= 28
ms
Sotf pulse time measured
= 498
ms
Configure BI. (set

SOTF) DDB# 488 as CB manual close command to check first state

To measure SOTF pulse time configure BO as

Tested by:
Name : Eng. Mohamed
Signature & Date :

(OK)

Shokry

SOTF ACTIVE and use it as dual contact

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 7 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

2- SOTF BY DEAD POLE DETECTED :SOTF DELAY TIME SETTING = 1.0

SEC

SOTF DELAY TIME MEASURED = 1.04

SEC

Inject first page normal current and voltage. 2nd page inject zero current zero voltage and stop freja by
contact (SOTF ACTIVE) the time till freja stop by contact will be the delay time

SOTF BY DEAD POLE DETECTED TRIP TIME =

14.9

ms

Inject direct at page two any fault at zone concerned by SOTF stop injection by SOTF trip contact

NOTE:
When the line is healthy once it become dead so SOTF will be activated after this delay time while the line still dead
The line identifications for line dead is setting at CB FAIL SETTING I< =80 m

.4

VTS FUNCTION TEST:

.2.5.2 Loss of one or two phases test:


Fixed setting V2=10V
-Apply 3 Phase rated voltage (Ur V) with balanced angles.
-Apply 3 Phase rated current (Ir A) with balanced angles.
-for the phase under test start decrease the voltage on one phase and / or two phases
till you get Internal fuse fail (fuse fail without time lag).
- For time test inject voltage more than V2.and stop freja BO. VTF alarm
Fixed setting: V2 = 10 volt, I2> inhibit less than setting.=100 mA
Phase

Pick up

Drop Off

One phase
Two phase

10.01
10.00

9.47
9.50

Set Time

Measured Time

(sec)

(Sec)
1.013
1.012

1.0

- CHECK THE FUSE FAIL BLOCKING BY I2> inhibit (simulate 3 phase voltage to get fuse Fail,
for I2> Apply 3 Phase equal current (Ir A) with balanced angles and increase one phase to get I2 more than the setting
Value it will inhibit fuse fail then decrease again phase till you get fuse fail
- [I2> inhibit measured >
= 99.59
mA].
-Check the relay trip unblocking during the internal fuse fail by any fault
[ OK ].
Simulate 2 stages: - stage 1; inject 3 phase voltage to get fuse fail and zero current.
- stage 2; inject the same voltage as in stage 1, inject 3 phase current
to get a value grater than I2> inhibit.

.2.5.2 Loss of all 3 phase voltages under load condition test(detect 3p):
Fixed Setting:
Tested by:
Name : Eng. Mohamed
Signature & Date :

a- for fuse fail pick up; V1=10 volts.

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 8 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

b- for fuse fail reset; V1=30 volts.


Pick up measurement
voltage(v)

Reset measurement
voltage(v)

10.03

30.05

8.1.2.4 Check the blocking of the relay when the general block functions (VT MCB TRIP) is activated [

Fault Locator Function:

Line Length:

80.0 Km

Line impedance: 18.6

Fault Type

Fault Impedance Z ()

A-N(25)%
A-B(50)%
A-B-C(100)%

4.65
9.3
18.6

20
40
80

*WE INJECT Z WITH LINE ANGLE


Event and Disturbance recorder check [

.2

OK

Actual display (KM)

19.75
40.59
81.16

Directional earth fault protection - DEF (67N-1)


DEF status :

.1

L: 79 degree.

Expected display
(KM)

ENABLE

DEF VNpol set :

3V

DEF Char angle :

-60

DEF polarizing :

ZERO SEQUENCE

DEF threshold :

100 mA

Pick up current 3Io:


Pick-up current

Drop-off current
Expected
95% set
Measured
5%
95mA
96

Phases

Expected
Set 5%

100mA

103.44

100mA

102

95mA

99

100mA

103.95

95mA

98

Measured

-Apply 3 phase volts of rated value (57.73 volt) with balanced angles.
-for the phase under test start reducing voltage till you get Vn more thane vpolarizing
Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 9 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

Apply 3 phase current with balanced angles for the phase under test start increasing current till you get pick-up; then
decrease again till you get reset.

.2

Directional Test (FW)


Angle
60

Pick-up
Expected
Measured
Set 2
150
149.9

Drop-off
Expected
Measured
Hyst. < 3
330

329.6

We will inject and change the voltage angle not current angle so the angle will be as added 180

.3

POLARIZING VOLTAGE (3V0) PICKUP AND DROP OFF TEST:


Vn (3V0) measured

Vn(3V0) setting

Pick up
3.009

3V

Drop off
2.958

NOTE: -Apply balanced current at 3 phase for phase under testing up slowly till get In more than 3Io setting
-Apply 3 phase volts of rated value (57.73 volt) with balanced angles.
-for the phase under test start reducing voltage till you get pick-up; then increase
again till you get reset.

.4

DEF Scheme check:


Aid DEF delay
=

Scheme: permissive over reach


SEND: DEF STFW
DEF AIDED TRIP
DEF AIDED TRIP

II.

90

m sec

:
29.6
: DEF STFW + CR: 120
: DEF STFW w/o CR
1.53

m sec
m sec
SEC (trip with EF element. no trip with aid -2)

Current Reversal Logic Check (Permissive Over Reach Scheme):


Apply a reverse / forward fault to check: t rev guard:
Fault type
Reverse/
forward

t rev guard setting (m sec)

t rev guard measured (m sec)

150

263.9

THIS MEASURED VALUE INCLUDE DELAY TIME AND DEF PICK UP TIME

II

Weak End Infeed Echo (Permissive over reach Scheme):

Apply a short pulse to DEF Channel Receive Input Without any fault Injection and check
Channel send is given: [ OK
]

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 10 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV


Operating time

Project no.:

R08.1
25.4

m sec

Weak End Infeed Trip (Permissive over reach Scheme):


Setting
WI V< V thresh = 45 V
WI trip delay
= 60 m sec
U ph setting
(V)

U ph measured
(V)

Remark

45

45.03

OK

Start at 3ph voltage more than setting value and go down gradually and apply send signal each time and check at
which value will come ECHO/WI trip

Measured WI Trip time =

Scheme: BLOCKING reach


SEND: DEF STRV
DEF AIDED TRIP
DEF AIDED TRIP

79.2

:
: DEF STFW W/O CR :
: DEF STFW + CR

m sec
41.3
118.1
1.53

m sec
m sec
sec (trip with EF element no trip with aid-2)

OVER CURRENT PROTECTION ( NON DIRECTIONAL ) :


PICK UP VALUE:
PHASE
A
B
C

SETTING
1 A.&1 sec

OPERATING TIME STAGE (1)

CURVE

PICK UP
1.001
1.00
1.00

DROP OFF
0.951
0.950
0.950

DT TIME
1.02
1.02
1.02

(Is > 1 A)

CAL TIME
@

OPERATING TIME

A
B
C
2 Times
10.02
10.02
10.02
SI
5 Times
4.29
4.29
4.29
2 Times
13.46
13.46
13.45
VI
5 Times
3.38
3.38
3.38
Tested by:
Witnessed
by:
SEC-WOA-CONSULTANT
2 Times
26.53
26.53
26.51
EI
Name : Eng. Mohamed
Shokry
Name : ENG/ MAHMOUD HAMDI
5
Times
3.32
3.33
3.32
Signature & Date :
Signature & Date
2 Times
119
119
119
LTI
5 Times
29.88
29.90
29.87

LIMIT(as per curve)


10.03+/-5%
4.28+/-5%
13.5+/-5%
3.375+/-5%
Witnessed by:
SEC-WOA-CSD
26.67+/-5%
Name : ENG/GAMAL HAMMAM
Signature &3.333+/-5%
Date :
120+/-5%
30+/-5%

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 11 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

1) System check:-

No

Item description

Setting
values

1
2
3
4
5
6
7

Dead voltage
Live voltage
Under voltage
Over voltage
U diff
CS1 angle
CS1 freq

20
40.
43
70
6.5
20
50 mH

Measured
values
BB
LINE
20.0
20.04
40.01
40.06
43.04
42.97
70.04
69.97
6.58
6.56
19.1
19.1
50
50

Remark

2) AUTO RECLOSER
No
1
2
3
4
5

Item description
Dead time 1
CB READY
Reclaim time
A/R inhibit time
Check system time

Setting
values

Measured
values

Remark

3 Sec
5 Sec
30 Sec
7 Sec
2 Sec

3.1

First shot

5.1
30.1
7.1
2.08

Check that A/R block from Z2 , Z4 as we make in A/R setting


Check that A/R NOT block from multi phase as we make in A/R setting
Check that A/R WILL START FROM EXTERNAL BI AR START
Check that A/R WILL BLOCK FROM EXTERNAL BI AR BLOCK

[ OK ]
[ OK ]
[ OK ]
[ OK ]

1-Dead time :- start timer protection trip and stop with close command (auto close) BO
2-CB HEALTY : When AR finish dead time before giving close command go to chick CB healthy BI if not come will
wait this time to chick it .if come before time finish will make close. if not come it will make lock out after this time
Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 12 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

-A-first way start timer trip BO and stop AR LOCK OUT BO and remove CB HEALTHY BI(time=dead time + CB
healthy time
-B-other way when AR start shot it make blocking until finish shot. if condition CB HEALTHY not come at end of
dead time it will remove blocking through this time and return blocking again after this time finish
So to measure this time we can start timer by AR BLOCK BO NC and stop by AR BLOCK BO NO THIS WILL measure
CB HEALTHY time only and accurate
3-CHICK SYSTEM TIME:it will be measured same ways as CB HEALTHY TIME unless we will remove CHECK SYSTEM BI and will activate
syncrocheck with 1st shot
4-AR inhibit time:this time coming after closing the C.B. through this time inhibit AR for this time. to measure it will make freja sequence
first page will take freja BO to relay BI MANUAL CLOSE COMMAND will function it at relay (CLOSE CB) and but the
time for page one as this inhibit time setting and stage two will make fault to start the AR and change stage one duration till
get AR START so inhibit time will be the time of stage one at freja (CB.READY, SYNCROCHECK BI .must be available)
5-RECLAIM TIME:At last shot When A/R start reclaim time it make A/R LOCK OUT OR still making blocking during reclaim time
To measure it take BO close command (auto close) to start timer .and take BO A/R BLOCK NC to stop timer

8.LOGICAL INPUTS CHECK:Input

Terminal

BI-1

E1 E2

OK

BI-2

E3 E4

OK

BI-3

E5 E6

OK

BI-4

E7 E8

OK

BI-5

E9 E10

OK

BI-6

E11 E12

OK

BI-7

E13 E14

OK

BI-8

E15 E16

OK

BI-9

C1 C2

OK

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Circuit

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Result

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 13 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

BI-10

C3 C4

OK

BI-11

C5 C6

OK

BI-12

C7 C8

OK

BI-13

C9 C10

OK

BI-14

C11 C12

OK

BI-15

C13 C14

OK

BI-16

C15 C16

OK

BI-17

G1 G2

OK

BI-18

G3 G4

OK

BI-19

G5 G6

OK

BI-20

G7 G8

OK

BI-21

G9 G10

OK

BI-22

G11 G12

OK

BI-23

G13 G14

OK

BI-24

G15 G16

OK

9.OUTPUT RELAYS CHECK


Relay

Terminal

Contact

RL1

L1 L2

NO

Result
OK

RL2

L3 L4

NO

OK

RL3

L5 L6

NO

OK

RL4

L7 L8

NO

OK

RL5

L9 L10

NO

OK

RL6

L11 L12

NO

OK

RL7

L13L14L15

C/O

OK

RL8

L16L17L18

C/O

OK

RL9

K1 K2

NO

OK

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Circuit

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF
RELAY MICOM P545
Customer:

AL GIHAZ

SEC-WOA

Site:

Page 14 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

RL10

K3 K4

NO

OK

RL11

K5 K6

NO

OK

RL12

K7 K8

NO

OK

RL13

K9 K10

NO

OK

RL14

K11 K12

NO

OK

RL15

K13K14K15

C/O

OK

RL16

K16K17K18

C/O

OK

RL17

J1 J2

NO

OK

RL18

J3 J4

NO

OK

RL19

J5 J6

NO

OK

RL20

J7 J8

NO

OK

RL21

J9 J10

NO

OK

RL22

J11 J12

NO

OK

RL23

J13J14J15

C/O

OK

RL24

J16J17J18

C/O

OK

RL25

H1 H2

NO

OK

RL26

H3 H4

NO

OK

RL27

H5 H6

NO

OK

RL28

H7 H8

NO

OK

RL29

H9 H10

NO

OK

RL30

H11 H12

NO

OK

RL31

H13H14H15

C/O

OK

RL32

H16H17H18

C/O

OK

Tested by:
Name : Eng. Mohamed
Signature & Date :

Shokry

Witnessed by: SEC-WOA-CONSULTANT


Name : ENG/ MAHMOUD HAMDI
Signature & Date

Witnessed by: SEC-WOA-CSD


Name : ENG/GAMAL HAMMAM
Signature & Date :