You are on page 1of 2

H3C-R

SAFETY PRECAUTION This manual uses the following symbols to ensure safe operation of this timer.

MULTI-FUNCTION
ANALOGUE TIMER
User's Manual

WARNING
CAUTION

Warnings are indicated when mishandling this product might result in death or serious injury
to user.
Cautions are indicated when mishandling this product might result in minor injury to the user,
or only physical damage to the timer.

WARNING

RESTRICTIONS ON USE
When using this product in applications
that require particular safety or when
using this product in important facilities,
please pay attention to the safety of the
overall system and equipment. Install failsafe mechanisms, perform redundancy
checks and periodic inspections and
adopt other appropriate safety measures
when it is necessary. This product is rated
at Class
.

Note this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
been correctly wired before turning the power ON.
Before wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
electric shock.
Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
Do not disassemble the product. Doing so might cause electric shock or faulty operation.

CAUTION
Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation.
Firmly tighten the wires to the socket. Insufficient tightening of the wires to the socket might cause fire.

SPECIFICATIONS

NAMES AND FUNCTIONS OF FACEPLATE

Operating voltage

AC/DC : 24240V

Allowable operating
voltage range

85 ~ 110% of rated operating voltage

Rated frequency

50 / 60Hz

Contact rating

250VAC 5A (Resistive load)

Reset time

MAX 0.1s

Power consumption

Approx. 3VA

Life

Mechanical : 5,000,000 times / Electrical : 100,000 times

POWER

LEDs

Ambient humidity

MAX 85% RH

Weight

Approx. 100g

15

20

25

30

Scale Range Windows

sec

Time Dial

Mode Window
Mode Selector

A
10

OUT: Output indicator(Lit when


output is ON)

Ambient temperature -10+50 C

MODE

OUT

POWER: Power indicator(Flashes


when Timer operates; lit when
Timer stops operating)

Scale Selector

ANLY H3C-R

Scale Unit Window

BASIC SETTING

CONNECTION

Mode Selector

H3C-R

H3C-R11

A
Mode Window

7
1

GATE

Scale Selector
Turn the Mode Selector with a screwdriver in either
clockwise or counter-clockwise direction until the
desired operation mode (A, A4, B, B3, B4, C, E, or J) is visible through the Mode Window. Make sure
the selector snaps into a secured position, not between two modes.

5 6 7
4
8
9
3
2
10
1 11

5
START

4
3

Setting Operation Mode

RESET

Groove for
screwdriver

Setting Time Scale

Turn the Scale Selector with a screwdriver and the time scale will cycle through all values.
Stop when the desired scale range (1.2, 3, 12, 30) and the scale unit (sec, min, hrs, 10h) are visible
through the Scale Range Windows and the Scale Unit Window respectively.
Clockwise turns increment the time scale; counter-clockwise turns decrement the scale.
Make sure the selector snaps into a secured position, not between two scales.

SOURCE

SOURCE

TIMING CHART(Output mode) for H3C-R

B3 : Repeat cycle ON start (1A1C)

A : ON delay (2C)
t

Rt

Rt t - a

t - a Rt

E : Interval (1A1C)
t

SOURCE (2-7)

SOURCE (2-7)

SOURCE (2-7)

N.C. (1-4, 8-5)


N.O. (1-3, 8-6)
OUTPUT LED

N.C. (8-5)
N.O. (8-6)
OUTPUT LED

N.C. (8-5)
N.O. (8-6)
OUTPUT LED

POWER LED
Set time = t , t - a < t , Reset time = Rt

N.C. (1-4)

N.C. (1-4)

N.O. (1-3)

N.O. (1-3)

POWER LED

Rt

Rt t - a

SOURCE (2-7)

SOURCE (2-7)

N.C. (8-5)
N.O. (8-6)
OUTPUT LED

N.C. (8-5)
N.O. (8-6)
OUTPUT LED

t - a Rt

J : One shot output (1A1C)


t

0.6s

0.6s

0.6s

0.6s

N.C. (8-5)
N.O. (8-6)
OUTPUT LED

N.C. (1-4)

N.C. (1-4)

N.C. (1-4)

N.O. (1-3)

N.O. (1-3)

POWER LED
Set time = t , t - a < t , Reset time = Rt

t - a Rt

Set time = t , t - a < t , Reset time = Rt

C : Interval (2C)
t

SOURCE (2-7)

SOURCE (2-7)

N.C. (1-4, 8-5)


N.O. (1-3, 8-6)
OUTPUT LED

N.C. (1-4, 8-5)


N.O. (1-3, 8-6)
OUTPUT LED

Rt

Rt t - a

POWER LED

POWER LED
Set time = t , t - a < t , Reset time = Rt

0.5s

POWER LED
Set time = t , t - a < t , Reset time = Rt

B : Repeat cycle OFF start (2C)

Rt

Rt t - a

SOURCE (2-7)

N.O. (1-3)
POWER LED

Rt t - a

Set time = t , t - a < t , Reset time = Rt

B4 : Repeat one shot output (1A1C)

POWER LED
Set time = t , t - a < t , Reset time = Rt

A4 : ON delay (1A1C)

Rt

Set time = t , t - a < t , Reset time = Rt

Pr oduc t is s u b j e c t t o c h a n g e w i t h o u t n o t i c e .

0.5s

TIMING CHART(Output mode) for H3C-R11

A : ON delay (2C)

C : Signal ON/OFF delay (2C)


t

SOURCE (2-10)

t-a

t-a t-a

SOURCE (2-10)

START (2-6)

START (2-6)

RESET (2-7)

RESET (2-7)

N.C. (1-4, 11-8)


N.O. (1-3, 11-9)
OUTPUT LED

N.C. (1-4, 11-8)


N.O. (1-3, 11-9)
OUTPUT LED
POWER LED

POWER LED
Set time = t

Set time = t , t - a < t

E : Interval (1A1C)

A4 : ON delay (1A1C)
t

SOURCE (2-10)

t-a

t-a

SOURCE (2-10)

START (2-6)

START (2-6)

RESET (2-7)

RESET (2-7)

N.C. (11-8)
N.O. (11-9)
OUTPUT LED

N.C. (11-8)
N.O. (11-9)
OUTPUT LED

N.C. (1-4)

N.C. (1-4)

N.O. (1-3)

N.O. (1-3)

POWER LED

POWER LED
Set time = t , t - a < t

Set time = t

B : Repeat cycle OFF start (2C)


t

J : One shot output (1A1C)


t-a

t-a

t-a

SOURCE (2-10)

SOURCE (2-10)
START (2-6)

START (2-6)

RESET (2-7)

RESET (2-7)

N.C. (1-4, 11-8)


N.O. (1-3, 11-9)
OUTPUT LED

N.C. (11-8)
N.O. (11-9)
OUTPUT LED

0.5s

0.5s

N.C. (1-4)

POWER LED
Set time = t , t - a < t

N.O. (1-3)
POWER LED
Set time = t , t - a < t

B3 : Repeat cycle ON start (1A1C)


t

Application of Gate terminal :

t-a

t1

SOURCE (2-10)

SOURCE (2-10)

START (2-6)

START (2-6)

RESET (2-7)

GATE (2-5)

N.C. (11-8)
N.O. (11-9)
OUTPUT LED

RESET (2-7)

N.C. (1-4)

N.C. (11-8)
N.O. (11-9)
OUTPUT LED

N.O. (1-3)

POWER LED

t2

t-a

Set time = t = t1 + t2 , t - a < t

POWER LED
Set time = t , t - a < t

B4 : Repeat one shot output (1A1C)


t

t-a

*Note. While the start signal is ON, the timer starts when power
comes ON or when the reset input goes OFF.

SOURCE (2-10)
START (2-6)
RESET (2-7)
N.C. (11-8)
N.O. (11-9)
OUTPUT LED

0.6s

0.6s

0.6s

0.6s

N.C. (1-4)
N.O. (1-3)
POWER LED
Set time = t , t - a < t

DIMENSION(mm)

H3C-R or H3C-R11

H3C-R + Y-50 + US-08

6.5

52

14.2

51

15
6.5

37

35.7

30

45
45 +0.5
-0

13

48
48

36.7

48

45

48

48
45

45
48

36.7

3.3 X 2

45 +0.5
-0

59

ANLY ELECTRONICS CO., LTD.