INTRODUCTION
This document presents a detailed description of the Condensate From Charge Air System for the
215 MW Bauang Diesel Power Plant. It includes the function, criteria requirements, detail of
system components, instrumentation and control, operation modes, safety precautions and
maintenance requirement. The system is shown in Appendix 7.1.
1.1
System Function
The Condensate From Charge Air System (circuit 13) enables condensate from the Charge Air
Cooler of each engine unit to be recovered and directed in the Water Treatment and Make-Up Water
System (circuit 17) or in the water inlet line (0-17-001-50) of each sector.
1.2
Criteria Requirements
The system equipment, components and controls are designed in accordance with International
European Standard (IEC).
Pumps operating pressure is designed to 3 bar at a rate of 1m3/h.
1.3
2.0
2.1
Components
2.1.1
Recovery Tank
Each sector is provided with a recovery tank wherein all drained condensate from all the
engine's charged air coolers accumulate.
Equipment ID
BPPC/SDD-13
Page 2 of 6
Quantity
Capacity, ltrs
Supplier
2.1.2
Pump-motor Set
Equipment ID
Quantity
Pump Technical Specification
Operating Temperature, C
Operating Density, kg/m3
Flow rate, m3 /h
Suction pressure, bar
Delivery pressure, bar
NPSH available, m.CL
NPSH required, m.CL
Rotating Speed, rpm
Input power, KW
Efficiency, %
Atmosphere
Pump Orientation
Packing gland type
Suction Diameter, mm
Delivery Diameter, mm
Weight, Kg
Type
Supplier
45
1000
1
18
3500
32
Saline
Vertical
Mechanical
PN 25
20 kg
MTL 2-30
Sulzer Pompes France
0.5
3500
6.38
3
50
100 TC
F
Yes
flanges V18
Vertical
Class B
46010%
3 phase
60
BPPC/SDD-13
Page 3 of 6
Nominal current, A
COSo/
Efficiency, %
WR, Kgm
Protection class
Weight, kg
Type
Manufacturer
2.2
0.85
72
-
1.8
0.0028
IP55
9
80
DP Motors'
Instrumentation
a.
Limit Switches
The two (2) limit switches trigger the alarm in the OEC1 Signalizing Cubicle and
OIS console.
Equipment ID
Quantity
Type
Specification
Aluminum material casing
Square flanges 92x92 mm connection
Side mounting
Magnetic type transmission
Switch
Double pole - change over-dry contact type switch
2 SDFT Switch
8A, 440VAC/IA, 240VDC CAPACITY
M25 ISO STANDARD GLAND TYPE
Manufacturer
Bestobell Mobrey
b.
Limit/Control Switch
The control switch stops the 0-13P1 pump when the water level in the recovery tank
is low.
Equipment ID
Quantity
Type
Specification
BPPC/SDD-13
Page 4 of 6
Pressure Indicators
The inlet and discharge of 0-13P1 pumps are provided with direct reading pressure
indicators.
Equipment ID
Quantity
Type
Scale range
Manufacturer
2.2.2
PI 0-13101-1; PI 0-13101-2
PI 0-13101-3; PI 0-13102-1
PI 0-13102-2; PI 0-13102-3
6 (two per pump)
DIN, liquid filled
-1 to 3 bar (IN) and 0 to 6 bar (OUT)
HAENNI
Controls
The 0-13P1 Pumps can be locally controlled in the OBJ1 panel and remotely controlled in
the OIS console.
2.2.3
Alarms
Two alarms for the system may indicate in the OEC1 Signalizing Cubicle and Operator
Interface Station (OIS).
A.
B.
2.2.4
Protective Devices
The 0-13P1 Pumps are provided with the following protective devices in the OBJ1 Panel.
Q1
BPPC/SDD-13
Page 5 of 6
F1
3.0
MODE OF OPERATION
3.1
Start-up
A high water level alarm from 0-13V1 tank will indicate in the OIS console and the 0-13P1 Pumps
can be started from the console.
3.2
Shutdown
As the pump is started, it automatically stops when low level is reached in the 0-13V1 tank.
4.0
SAFETY PRECAUTIONS
4.1
No special hazards are considered to exist in this system except those associated with working near
the rotating equipment particularly the pumps which are remotely started when high tank water level
is detected.
5.0
MAINTENANCE
5.1
Preventive Maintenance
Refer to the Manufacturer's instruction manual for proper maintenance of all equipment.
Maintenance and test of all components should be on periodical basis.
All instrumentation, control and alarm components shall be tested and calibrated at regular intervals.
Clean the accumulated dirt and oil on pump's and tank's external.
BPPC/SDD-13
Page 6 of 6
6.0
REFERENCES
6.1
6.2
Diagrams
6.2.1
6.2.2
6.2.3
6.3
7.0
APPENDICES
7.1
7.2
Pipe Specification
7.3
List of Valves
7.4