PLC NFPA20

1. PLC

6 0 2.5MPa 0.5 4 20

2.
3.PLC
4.
a.

5
PLC

PLC
b.

PLC
PLC
PLC
c.
24

125V
6-2.3
125V

PLC
d.
PLC 7
e.
1.34MPa
1.34MPa 1.34MPa
1.24MPa 1
1.14MPa 5
1.04MPa 5
0.94MPa 10

f.
1.34MPa
1.34MPa 1.34MPa
1.24MPa 1

1.14MPa 5

1.04MPa 5
0.94MPa 10

g.
PLC
YTD1 YTD2
YTD1 YTD2
YTD1 YTD2
YTD1 YTD2

h.
1. 1.34MPa
2.

3.

4.
5.

6.

Control Logic requirements:


A. Control mode
the automatically control and the manual control both can be realized ,the manual control
comes first.
two sets of electric fire pump, can be run at the same time, if at the same time, please set 5
seconds delay.
the manual control switch is set on PLC control cabinet, when the motor operated by the
manual switch is not affected by the pressure sensor, unless the manual shutdown, the pump
group should be in a state of operation.
the automatic switching switch should be in need set on PLC control cabinet.
B. signal acquisition
To determine the pressure transmitted by the transmitter or fire hydrant button signal as
conditions to start fire pump ;
To determine the pressure transmitted by the transmitter or pressure switch action signal as
conditions to start the spray pump ;
According to the pressure transmitted by the pressure transmitter as conditions to start the
jockey pump ;
according to the above requirements to provide two groups of switch signal to the PLC
control cabinet: fire hydrant button action signal, the pressure switch signal.
The delay time that PLC control cabinet to control each motor can be operated by the
computer, on site to adjust.
The setting pressure point for PLC control cabinet to each motor can be operated by the
computer, on site to adjust.
C. remote alarm
Emergence of the following circumstances, there must be sound and light signal sent to 24
hours someone on duty site.

All fire pumps (including the jockey pump), motor operation signal, no matter when the
control cabinet put into operation state, the alarm signal should be action.
Missing phase. Any phase loss of the motor contactor into the wire must be monitored.
Exception: in the case of multiple power supply, if you want to monitor all the power,
allowing the motor contactor in the upper reaches of the line at any point to monitor the
various power of the reverse phase.
Reversed phase. The alarm circuit shall be provided by an independent reliable supervision
power supply or a fire pump motor power supply to be less than 125V.
Switch to standby power supply. when the power supply is switched to the standby power
supply, the alarm circuit should be alert at any time. The alarm circuit shall be operated by an
independent and reliable power supply to the power supply which is not more than 125V.
Diesel pump start or electric valve to perform the switch, both sound and light alarm to
remind the duty personnel on-site inspection
D. pressure recording function
PLC control cabinet must have the function to record the pressure of the pressure transmitter,
and the pressure can be recorded within 7 days.
E. Pressure setting of restarting and stopping the pumps in fire hydrant system
The pressure of safety valve off is set at 1.34MPa
Usually fire hydrant pipe network pressure transmitter to transmit the pressure maintained in
1.34MPa, higher than the 1.34MPa. All the regulator pump were immediately forced to
stopping.
When the fire hydrant pipe outlet pressure transmitter to transmit the pressure dropped to
1.24MPa. After a one second delay (tentative), fire hydrant system vertical pump start to
work.
When the fire hydrant pipe outlet pressure transmitter to transmit the pressure dropped to
1.14MPa, after 5 seconds delay (tentative), fire hydrant system horizontal regulator pump
start to work.
When the fire hydrant pipe outlet pressure transmitter to transmit the pressure dropped to
1.04MPa, 5 seconds later (tentative), electric fire hydrant pump start to work.
When the fire hydrant pipe outlet pressure transmitter to transmit the pressure dropped to
0.94MPa, the opening and closing state of electric valve will switch, the delay of 10 seconds
(tentative) and diesel fire pump start to work.
F. Pressure setting of starting and stopping pumps in automatically system.
The pressure of safety valve off is set at 1.34MPa
Usually the pressure transmitted by the transmitter of fire hydrant pipe network transmit
maintains in 1.34MPa, higher than the 1.34MPa. All the regulator pump were immediately
forced to stopping.
When the pressure drop down to 1.24MPa, after a delay of 1 second (tentative), automatic
water spray system vertical pressure pump start

When the pressure drop to 1.14MPa, 5 seconds after the delay (tentative), automatic water
spraying system horizontal pressure pump start to work.
When the pressure drop to 1.04MPa, 5 seconds after the delay (tentative), automatic water
spraying system electric fire pump start to work.
When the outlet pressure drop to 0.94MPa, the opening and closing state of the electric valve
will switch ,delay 10 seconds (tentative), diesel fire pump start
G. control of electric valve
PLC control cabinet can display two electric valve of the valve position (open to the position,
closed in place), the fault status, can control the positive reversal of the electric valve.
Fire hydrant spray side YTD1 side YTD2
Normally state YTD1 clearance in place YTD2 open in place
The fire hydrant pump as pump to determine the valve opening and closing state control,
YTD1 open place, YTD2 closed in place
Diesel pump as an automatic water spray valve when the valve open and close the state,
control YTD1 clearance in place, YTD2 open in place
H. limit case
When the pressure reaches
1 1.34MPa when the pump stops the pump failure, alarm notification duty, manual pump.
2 pressure in order to reduce the vertical pressure pump does not start when the pump does
not affect the horizontal regulated pump start, the horizontal pressure pump does not affect
the start of the electric fire pump, the electric fire pump does not start does not affect the
standby pump start.
3 when the electric pump has been started, but the display is not started, the requirement to
start the standby pump, do not affect the standby pump start. Set interlock circuit, when the
diesel pump in a fire hydrant by pump condition, and the fire hydrant pump interlock; when
the diesel pump in automatic water spraying by pump condition, and automatic water
spraying electric pump interlock.
4 when the electric valve has issued a switching command, but not action, do not affect the
standby pump start
5 when the electric valve has been implemented switch, but the feedback is not action, do not
affect the standby pump to start, that is, as long as the preparation of the pump or electric
valve to start the switch, all sound and light alarm to remind the staff on duty.