lnstallation

Mounting the SV! ll


This procedure is used to mount the SVI ll on Masoneilan rotary control valves that have less than 60
degrees rotation, such as Camflex and Varimax.
Required Tools
3/16 inch Hex Key with tee handle, 5/32 inch Hex Key, 3 mm,4mm, Smm Hex Key,7116 inch Wrench

1
2.

Mount the SVI ll rotary mounting bracket to the valve actuator using two (2) 5116 - 18 UNC flathead cap screws. The SVI Il will be mounted as shown in Figure 2-3, ATO, or in Figure 2-4, ATC,
ln the preferred mounting position the long end of the mounting bracket is on your left when facing the actuator for any position of the valve and actuator.
Bolt the extension shaft to the valve position take-off shaft using a 114 - 28 UNF socket flathead
screw.

3.

Due to internal valve pressure the plug shaft is pushed out to the mechanical stops, usually a
thrust bearing, during normal operating conditions. On valves where the valve position take-off is
mounted directly on the end of the plug shaft, Camflex for example, the shaft must be bearing on
its stops to properly set up the SVI ll positioner. During hydrostatic testing the shaft is thrust to its
stop and a normally tightened packing will retain it in that position. lf the shaft is in an unknown
position install a 114 - 28 UNF screw in the end of the shaft. Use the screw to pull the shaft out to
its fully extended position. On vacuum service, the valve shaft may be drawn into the body by the
vacuum acting on the shaft, but the magnetic coupling must be assembled flush with the mounting bracket with the shaft pulled fully out to its thrust bearing. Check that the endplay from the
vacuum position to the fully extended position is less than 0.06 inches.

4.

Slidethe magnetholderintothe extension shaft. The location of the magnets is in the ring of the
magnet holder. The magnetic axis is the line through the center of both magnets.

5.
6.
7.
8.
9.
10.

Rotate the magnet holder so that the magnet axis is vertical when the valve is in the closed position. See Figure 2-2 and Figure 2-3.
Align the end of the magnet holder flush with the end of the mounting bracket. Secure the magnet holder with two M6 set screws.
Slide the V-Seal over the magnet holder.
Secure the SVI ll onto the mounting bracket using four M6 x 20 mm Socket Head Cap Screws.
Ensure no interference exists with the position sensor protrusion.
Ensure that the V-Seal makes contact with the skirt around the position sensor protrusion on SVI
ll housing.

Extension
Lock rnagnet
assernbly
flush with tnp of
bracket

agn*t
hclder
V-seal
Figure 2 - 2 Camflex Side View

2-2

gecor.s\ Gene.g-[.o \^
M o1n
C" w*..[iout

"[t"