Professional Documents
Culture Documents
EE024-Power Measurement EMTS-Th-Inst PDF
EE024-Power Measurement EMTS-Th-Inst PDF
Training Unit
No: EE 024
Training Unit
Power Measurement EMTS
Theoretical Part
No.: EE 024
Edition:
2008
All Rights Reserved
Editor:
CONTENTS
Page
POWER MEASUREMENTS.........................................................................................5
1.1
1.2
1.2.1
1.2.2
1.2.3
Apparent power................................................................................................7
1.3
1.3.1
1.3.2
1.4
1.4.1
1.4.2
1.4.3
1.4.4
1.4.5
Determining the power factors from current, voltage and true power ................15
2.2
3.1.1
3.1.2
3.1.3
3.2
3.2.1
3.2.2
3.2.3
energy .......................................................................................................................23
3.3
3.3.1
LEARNING OBJECTIVES
1.1
POWER MEASUREMENTS
P=VxI
current
unit = Watt (W)
The following formula, based on Ohm 's law can also be used to determine electrical
power:
P = I x R
P = V
R
Here the correct current would be measured but the voltage drop across the ammeter
would increase the voltage measured. Therefore the appropriate type of circuit connection
must be used so that the energy consumed by the ammeter or the voltmeter is the least.
It can be accepted that with a variable current and a constant voltage an ammeter with the
scale divisions indicated in Watts could be used for making power measurements.
However, if both current and voltage are subjected to variation then only a suitable
electro-dynamic power meter may be used for making power measurements.
1.2
1.2.1
The active power in AC (alternating current) circuits differs from that in direct current
circuits in that the active power to be measured is the product (cos is the power factor,
cosine of the phase angle between current and voltage).
This indicates that, with a load which is not purely resistive and where the current and
voltage are not in phase, only the part of the current which is in phase with the voltage will
produce power.
1.2.2
Reactive power
1.2.3
Apparent power
With apparent power S = V x /, the measurement can be made in the same way as for
direct current with a voltmeter and ammeter. The power factor is not indicated in the
measurements.
1.3
1.3.1
1.3.2
10
With direct current it must be accepted that a small error will exist, as a residual flux will
remain in the iron core.
The disadvantage is that the frequency range of this meter is limited to 40 - 60 Hz.
By mounting several meter movements an the same spindle, power measurements of two
or three circuits can be totalled an a single scale.
1.4
1.4.1
11
1.4.2
In a balanced three-phase four-wire circuit the total power can be measured with a singlepower meter.
The power in one phase is measured. The total power is therefore three times as large as
that value of power indicated on the measuring device. Calibration of the scale for the total
power is possible.
1.4.3
If the voltage coil of the meter is not suitable for connection between two lines (380 V), but
is suitable for connection between one line and the neutral (220 V), then a measurement
may be made, by producing an artificial neutral point.
The resistance of the voltage path (plus any dropping resistance) (= Ri) and the two other
resistances must be of equal resistance.
12
1.4.4
In both cases the individual valves are added together to give the total power.
13
By the three wattmeter method the resistance of the three voltage coils must be of equal
value, otherwise an exact measurement cannot be made.
When using the two wattmeter method the two voltage coils must be so designed that
they can withstand the line voltage applied from the mains (example 380 V).
1.4.5
These
measurements
must
be
conducted
by
making
three
separate
power
measurements. The total power is the result of adding the three readings from the three
meters. The three separate meters may be installed in the same housing, with the voltage
coil of each meter movement mounted on one spindle. The torque is added together and,
therefore, the measuring device will indicate the power of the three-phase circuit.
14
2.1
Determining the power factors from current, voltage and true power
In all cases the power factor cos can be obtained mathematically from the sinusoidal
quantities, similarly in balanced three-phase three-wire circuits by measurement of
current, voltage, and active power.
For single-phase alternating current the following applies:
cos =
active power
apparent power (V x /)
P_
Pa
active power
apparent power (V x / x 3)
2.2
The method of operation for the moving coil quotient-meter is as follows. The indicator
(pointer) movement depends on the difference between the torques produced by the
voltage coils. Both coils are cut by the magnetic field produced by current flow through the
fixed coil. The first turning force is produced by the current flow through the fixed coil and
the in-phase voltage and current in one moving coil.
15
The second turning force is caused by the current flow through the stationary coil and the
current in the moving coil connected through L, which will lag the voltage by 90.
Power factor measurements in a one-phase system
2.3
The total power factor of a three-phase system is also referred to as a "commercial power
factor". The direct measurement of the total power factor is not possible in a three-phase
system at any time without a balanced lad. Therefore, the power factor of each individual
circuit must be found separately.
16
17
Electrical energy is the product of power and the time during which the power is
consumed.
Electrical work W
1Wh =
true power P x
time t
1W
1h
3.1
Almost all of the meters used today are of the motor type. Through an electro-mechanical
arrangement a spindle is driven at a speed proportional to the power and the electrical
work is indicated by a revolution counter mechanism.
3.1.1
Its principle of operation is similar to that of the moving coil meter and is, therefore, used
for direct current only.
A disc armature winding turns within the field of a permanent magnet.
18
The current is taken to the winding through a collector, fastened to the meter spindle. The
instrument is fundamentally an ampere-hour meter, but with a supply voltage which is
sufficiently constant, this meter can also be used as a kilowatt hour meter.
3.1.2
With this type of meter a drum armature in series with a dropping resistor acts as a
voltage path from the voltage supply. The current flows through the fixed coil of the load.
The electrical energy is proportional to the revolutions of the drum which are indicated on
a counter. The method of function for this system can best be compared with the electrodynamic meter. The meter can be used for direct or alternating current.
19
3.1.3
This is used today in AC circuits. The operation of this meter depends on the induction
principle. The fixed components consist of two iron cores, one carries the voltage coil
while the other carries the current coil. In the air gap between these two iron cores is a
rotatable aluminium disc, called the rotating disc. Fixed permanently to this disc is a worm
gear, which transfers the revolutions of the disc to the recording device.
The movement of the rotating disc is damped by a permanent magnet which serves as a
stop mechanism and prevents the meter from rotating after the circuit has been broken.
This damping is caused by the generation of eddy currents.
current coil
permanent magnet
voltage coil
aluminium disc
worm gear
supply terminals
recording mechanism
load terminals
20
If there is only pure resistance in the circuit being measured, current will flow through the
current coil, which has only a few windings. Due to the low inductance this current is in
phase with the supply voltage. The voltage coil because of its high number of windings
has a large inductance.
For this reason the current in the voltage coil is almost 90 out of phase with the voltage.
With the help of a balancing resistance the phase lag between current and voltage can be
adjusted to exactly 90. The magnetic field produced by the voltage and current coils will
produce a voltage across the rotating disc. Current will flow through the disc, which is
almost a short-circuited conductor. A magnetic field will be produced (a rotating field). The
turning speed of the rotating disc is dependent on the strength of this rotating field.
The proper movement of the meter, especially under a small load, will be impaired by the
initial permeability of the core material and friction of the bearings. To eliminate these
influences an adjustable booster is wound on the core of the voltage coil. The meter is
stopped from running freely by means of a small brake which is magnetized by the voltage
coil.
With an induction meter only AC can be measured.
With a three-phase meter, three single-phase meters are mounted in the same housing.
The turning moment produced is developed on a single spindle and the reading will be
indicated on a single recorder.
With an induction meter only true energy is metered.
With the help of an induction meter the power consumed by a load can be found.
21
The constant of the meter gives the number of revolutions per kilowatt hour (kWh).
Old indication: U/kWh
Example
To calculate the power consumed by an electric stove the running disc has 10 revolutions
in 20 seconds. On the dial of the meter, the constant of the motor, 1200 KWh-1, is
indicated. Calculate the power consumed by this electric stove.
22
3.2
3.2.1
3.2.2
3.2.3
23
3.3
3.3.1
24
25
QUESTIONS:
1. Give the formulae for the active, reactive and apparent power.
2. For which type of current is the ironless electro-dynamic meter suitable.
3. State the advantages and disadvantages of an ironless electro-dynamic meter.
4. Describe the method of operation of an iron-cored electro-dynamic meter.
5. Name the basic parts of an iron-cored electro-dynamic meter.
6. For what type of current are electrolytic type energy meters suitable?
7. State a formula for the determination of the power factor for:
a) Single-phase AC circuit
b) Three-wire three-phase circuit
8. Give a formula for the determination of electrical energy.
9. Name the main parts of an induction meter.
10. State the procedure for measuring the power consumed by a load, using an induction
meter.
26
QUESTIONS:
1. Draw the circuit diagram for power measurements in a sing le-phase alternating
current circuit.
2. Draw the circuit diagram for power measurement in an unbalanced three-phase threewire circuit using two-wattmeter circuit.
3. Name the instrument which has the following circuit diagram
4. Draw the circuit diagram for power factor measurements in a three-w ire system.
5. State the definition of electrical energy.
6. Name two types of direct current electrical energy meters.
7. For what type of current is the magnetic motor meter suitable?
27
28
SOLUTION:
1. Active power:
P = V I cos
active power
apparent power
b) cos q) =
active power
P
S
apparent power
P
5
29
30
SOLUTION:
1.
31
5. Electrical work is understood to be the product of power and time during which power
is consumed.
Electrical energy
6. a) Electrolytic type
b) The magnetic motor meter
7. DC current.
8. a) The induction meter
b) The electro-dynamic motor meter
9. After the circuit has broken it prevents the meter from running past this point, i.e. as a
stop mechanism.
10. No.
32
KEY TO EVALUATION
PER CENT
MARK
88 100
75 87
62 74
50 61
0 49
33