You are on page 1of 34

INDUSTRIETECHNIK

SRI LANKA INSTITUTE of ADVANCED TECHNOLOGICAL EDUCATION

ELECTRICAL and ELECTRONIC


ENGINEERING
Instructor Manual

Training Unit

Power Measurement EMTS


Theory

No: EE 024

Training Unit
Power Measurement EMTS
Theoretical Part
No.: EE 024

Edition:

2008
All Rights Reserved

Editor:

MCE Industrietechnik Linz GmbH & Co


Education and Training Systems, DM-1
Lunzerstrasse 64 P.O.Box 36, A 4031 Linz / Austria
Tel. (+ 43 / 732) 6987 3475
Fax (+ 43 / 732) 6980 4271
Website: www.mcelinz.com

POWER MEASUREMENT EMTS

CONTENTS

Page

LEARNING OBJECTIVES ...................................................................................................4


1

POWER MEASUREMENTS.........................................................................................5
1.1

Power measurements in direct current (DC) circuits............................................5

1.2

Alternating current (AC) power measurements....................................................6

1.2.1

Active (working) power.....................................................................................6

1.2.2

Reactive power ................................................................................................7

1.2.3

Apparent power................................................................................................7

1.3

Electro-dynamic meter (instrument) .....................................................................7

1.3.1

Ironless (no iron-core) electro-dynamic instrument..........................................7

1.3.2

Iron-cored electro-dynamic instrument...........................................................10

1.4

Circuits for power measurements ......................................................................11

1.4.1

Power measurements in a single-alternating current circuit ..........................11

1.4.2

Power measurements in a balanced three-phase four-wire circuit ................12

1.4.3

Power measurements in a balanced three-phase three-wire circuit using an

artificial neutral point...................................................................................................12

1.4.4

Power measurements in an unbalanced three-phase three-wire circuit ........13

1.4.5

Power measurements in an unbalanced three-phase four-conductor circuit .14

POWER FACTOR MEASUREMENTS.......................................................................15


2.1

Determining the power factors from current, voltage and true power ................15

2.2

Measuring power factors with an electro-dynamic meter (ratio meter) in a single-

phase system .................................................................................................................15


2.3

Measuring the power factor with an electro-dynamic quotient-meter in a

multiphase (two or more phases) system ......................................................................16

MEASUREMENTS OF ELECTR1CAL ENERGY.......................................................18


3.1

The motor meter ................................................................................................18

3.1.1

The magnetic motor meter .............................................................................18

3.1.2

The electro-dynamic motor meter ..................................................................19

3.1.3

The induction meter .......................................................................................20

3.2

Circuit connections for an energy meter ............................................................23

3.2.1

Circuit connection of single-phase AC energy meter .....................................23

3.2.2

Circuit connection of a three-phase meter in a four wire circuit .....................23

3.2.3

Circuit connection of a two watt-hour meter unit to measure three-phase

energy .......................................................................................................................23
3.3
3.3.1

Circuit connection of a reactive watt-hour meter................................................24


Circuit connection of a three-phase meter in a four-wire circuit .....................24

POWER MEASUREMENT EMTS

LEARNING OBJECTIVES

The student should


state the three formulas for calculating electrical power in DC circuits
describe the basic circuits for measuring power in DC circuits and explain the errors
produced by each circuit
explain "active power", "apparent power", and "reactive power" of an AC circuit
explain the method of operation for an ironless, electro-dynamic meter movement and
state the advantages and disadvantages
explain the method of operation of an iron core electro-dynamic meter movement and
state the advantages and disadvantages
derive the formula for finding the power factor in a single-phase AC and in a threewire, three-phase circuit
explain the term "commercial power factor" in a three-phase system

POWER MEASUREMENT EMTS


(Power and Work)*

1.1

POWER MEASUREMENTS

Power measurements in direct current (DC) circuits

Electrical power (for DC) is understood to be the product of:


voltage

P=VxI

current
unit = Watt (W)

The following formula, based on Ohm 's law can also be used to determine electrical
power:

P = I x R

P = V
R

Based on the above formula power measurements of DC may be accomplished by


making voltage and current measurements either simultaneously or consecutively.
For this purpose there are two basic circuit possibilities:

Here the correct voltage is measured across the load.


However, the current taken by the voltmeter would cause a higher current to be
measured.
* NOTE: Work is accomplished and expressed in terms of POWER multiplied by time.

Here the correct current would be measured but the voltage drop across the ammeter
would increase the voltage measured. Therefore the appropriate type of circuit connection
must be used so that the energy consumed by the ammeter or the voltmeter is the least.
It can be accepted that with a variable current and a constant voltage an ammeter with the
scale divisions indicated in Watts could be used for making power measurements.
However, if both current and voltage are subjected to variation then only a suitable
electro-dynamic power meter may be used for making power measurements.

1.2

1.2.1

Alternating current (AC) power measurements

Active (working) power

The active power in AC (alternating current) circuits differs from that in direct current
circuits in that the active power to be measured is the product (cos is the power factor,
cosine of the phase angle between current and voltage).
This indicates that, with a load which is not purely resistive and where the current and
voltage are not in phase, only the part of the current which is in phase with the voltage will
produce power.

1.2.2

Reactive power

With reactive power (wattless


power) Q = V x I x sin .
Only that part of the current which is 90 out of phase (90 phase shift) with the voltage is
used in the measurement.

1.2.3

Apparent power

With apparent power S = V x /, the measurement can be made in the same way as for
direct current with a voltmeter and ammeter. The power factor is not indicated in the
measurements.

1.3

1.3.1

Electro-dynamic meter (instrument)

Ironless (no iron-core) electro-dynamic instrument

1.3.1.1 Method of operation


A rotating voltage coil is mounted within the magnetic field of the fixed current coil. This
voltage coil has a large number of windings with a very small conductor cross section, as
a result of which the resistance is very large.
When connected into the circuit, current will flow through the current coil as well as
through the voltage coil. Due to the presence of the magnetic field produced by both
current coil and voltage coil, the latter will be forced to rotate (left-hand rule), and as a
result the pointer will then be deflected.
For control torque two spiral springs are attached. They serve as a current path as well as
a control string for the voltage coil.
The meter movement damping is accomplished primarily by the use of an air chamber.
The meter deflection is proportional to the product of the currents in the fixed and moving
coils.
Based an this type of design the meter movement can be used to measure current or
voltage as well as power. With direct current the product
and, therefore, the power is given by V x I With alternating current the product is given by
V x I x cos which corresponds to the alternating current active power.
The electro-dynamic meter is suitable for direct as well as alternating current.
The reading for alternating current is the true effective value.
With an ironless, electro-dynamic meter the magnetic lines flow purely in the air. This has
the advantage that no error can result from residual induction or eddy currents.
The disadvantage of this type of construction is that external electrical and magnetic fields
can greatly affect the indication of the meter.

1.3.2

Iron-cored electro-dynamic instrument

1.3.2.1 Method of Operation


The method of Operation is principally the same as with the ironless electro-dynamic
meter, with the difference that most of the magnetic lines (field) cut the laminated Iran
core of the fixed coil.
As a result of this the magnetic field (flux) is amplified many times and the turning torque
of the moveable coil will be much larger.
Through the use of an Iran core construction the effect of external fields will be practically
eliminated.
Instruments of this type are used mostly in plant operations (test panel mounting).
They are useable for measuring alternating as well as direct current quantities.

10

With direct current it must be accepted that a small error will exist, as a residual flux will
remain in the iron core.
The disadvantage is that the frequency range of this meter is limited to 40 - 60 Hz.
By mounting several meter movements an the same spindle, power measurements of two
or three circuits can be totalled an a single scale.

1.4

1.4.1

Circuits for power measurements

Power measurements in a single-alternating current circuit

Current path: thick wires


Voltage path: thin wires
Ri = resistance of volt coil circuit

11

1.4.2

Power measurements in a balanced three-phase four-wire circuit

In a balanced three-phase four-wire circuit the total power can be measured with a singlepower meter.

The power in one phase is measured. The total power is therefore three times as large as
that value of power indicated on the measuring device. Calibration of the scale for the total
power is possible.

1.4.3

Power measurements in a balanced three-phase three-wire circuit using an


artificial neutral point

If the voltage coil of the meter is not suitable for connection between two lines (380 V), but
is suitable for connection between one line and the neutral (220 V), then a measurement
may be made, by producing an artificial neutral point.
The resistance of the voltage path (plus any dropping resistance) (= Ri) and the two other
resistances must be of equal resistance.

12

1.4.4

Power measurements in an unbalanced three-phase three-wire circuit

This measurement can be made with two or three watt meters.


Circuit for three watt meters

Circuit for two watt meters

In both cases the individual valves are added together to give the total power.

13

By the three wattmeter method the resistance of the three voltage coils must be of equal
value, otherwise an exact measurement cannot be made.
When using the two wattmeter method the two voltage coils must be so designed that
they can withstand the line voltage applied from the mains (example 380 V).

1.4.5

These

Power measurements in an unbalanced three-phase four-conductor circuit

measurements

must

be

conducted

by

making

three

separate

power

measurements. The total power is the result of adding the three readings from the three
meters. The three separate meters may be installed in the same housing, with the voltage
coil of each meter movement mounted on one spindle. The torque is added together and,
therefore, the measuring device will indicate the power of the three-phase circuit.

14

2.1

POWER FACTOR MEASUREMENTS

Determining the power factors from current, voltage and true power

In all cases the power factor cos can be obtained mathematically from the sinusoidal
quantities, similarly in balanced three-phase three-wire circuits by measurement of
current, voltage, and active power.
For single-phase alternating current the following applies:
cos =

active power
apparent power (V x /)

P_
Pa

For three-wire three-phase circuits the following applies:


cos =

active power
apparent power (V x / x 3)

2.2

Measuring power factors with an electro-dynamic meter (ratio meter) in a


single-phase system

The method of operation for the moving coil quotient-meter is as follows. The indicator
(pointer) movement depends on the difference between the torques produced by the
voltage coils. Both coils are cut by the magnetic field produced by current flow through the
fixed coil. The first turning force is produced by the current flow through the fixed coil and
the in-phase voltage and current in one moving coil.

15

The second turning force is caused by the current flow through the stationary coil and the
current in the moving coil connected through L, which will lag the voltage by 90.
Power factor measurements in a one-phase system

2.3

Measuring the power factor with an electro-dynamic quotient-meter in a


multiphase (two or more phases) system

The total power factor of a three-phase system is also referred to as a "commercial power
factor". The direct measurement of the total power factor is not possible in a three-phase
system at any time without a balanced lad. Therefore, the power factor of each individual
circuit must be found separately.

16

In a delta-connected three-phase, three-wire system with balanced loads, all voltage


paths with equal resistance are connected to an artificial neutral point (ground). The 120
phase shift of the voltage in a three-phase circuit provides the required shift of the current
in the two voltage paths.

Power factor measurements in a three-wire system

17

MEASUREMENTS OF ELECTR1CAL ENERGY

Electrical energy is the product of power and the time during which the power is
consumed.
Electrical work W

1Wh =

true power P x

time t

1W

1h

A measuring device which measures electrical energy is referred to as an ENERGY


METER.
Energy meters are normally motor meters but for measurement of DC power it is possible
to measure energy, in circuits where the voltage is constant, by electrolytic means.

3.1

The motor meter

Almost all of the meters used today are of the motor type. Through an electro-mechanical
arrangement a spindle is driven at a speed proportional to the power and the electrical
work is indicated by a revolution counter mechanism.

3.1.1

The magnetic motor meter

Its principle of operation is similar to that of the moving coil meter and is, therefore, used
for direct current only.
A disc armature winding turns within the field of a permanent magnet.

18

The current is taken to the winding through a collector, fastened to the meter spindle. The
instrument is fundamentally an ampere-hour meter, but with a supply voltage which is
sufficiently constant, this meter can also be used as a kilowatt hour meter.

3.1.2

The electro-dynamic motor meter

With this type of meter a drum armature in series with a dropping resistor acts as a
voltage path from the voltage supply. The current flows through the fixed coil of the load.
The electrical energy is proportional to the revolutions of the drum which are indicated on
a counter. The method of function for this system can best be compared with the electrodynamic meter. The meter can be used for direct or alternating current.

19

3.1.3

The induction meter

This is used today in AC circuits. The operation of this meter depends on the induction
principle. The fixed components consist of two iron cores, one carries the voltage coil
while the other carries the current coil. In the air gap between these two iron cores is a
rotatable aluminium disc, called the rotating disc. Fixed permanently to this disc is a worm
gear, which transfers the revolutions of the disc to the recording device.
The movement of the rotating disc is damped by a permanent magnet which serves as a
stop mechanism and prevents the meter from rotating after the circuit has been broken.
This damping is caused by the generation of eddy currents.

current coil

permanent magnet

voltage coil

aluminium disc

worm gear

supply terminals

recording mechanism

load terminals

20

If there is only pure resistance in the circuit being measured, current will flow through the
current coil, which has only a few windings. Due to the low inductance this current is in
phase with the supply voltage. The voltage coil because of its high number of windings
has a large inductance.
For this reason the current in the voltage coil is almost 90 out of phase with the voltage.
With the help of a balancing resistance the phase lag between current and voltage can be
adjusted to exactly 90. The magnetic field produced by the voltage and current coils will
produce a voltage across the rotating disc. Current will flow through the disc, which is
almost a short-circuited conductor. A magnetic field will be produced (a rotating field). The
turning speed of the rotating disc is dependent on the strength of this rotating field.
The proper movement of the meter, especially under a small load, will be impaired by the
initial permeability of the core material and friction of the bearings. To eliminate these
influences an adjustable booster is wound on the core of the voltage coil. The meter is
stopped from running freely by means of a small brake which is magnetized by the voltage
coil.
With an induction meter only AC can be measured.

With a three-phase meter, three single-phase meters are mounted in the same housing.
The turning moment produced is developed on a single spindle and the reading will be
indicated on a single recorder.
With an induction meter only true energy is metered.
With the help of an induction meter the power consumed by a load can be found.

21

Measuring procedure for power


a) Switch on the device to be measured.
b) Count the revolutions of the rotating disc for a determined period of time.
c) Using this number, determine the revolutions of the rotating disc per hour. This value
will be divided by the constant (c) of the meter, which is indicated on the dial of each
individual meter.

The constant of the meter gives the number of revolutions per kilowatt hour (kWh).
Old indication: U/kWh

new indication: 1/kWh or kWh-1

The calculation gives the power consumed by the load in kW.


P (kW) =

revolutions of the meter per hour____


the meter constant ( C )

Example
To calculate the power consumed by an electric stove the running disc has 10 revolutions
in 20 seconds. On the dial of the meter, the constant of the motor, 1200 KWh-1, is
indicated. Calculate the power consumed by this electric stove.

22

3.2

Circuit connections for an energy meter

3.2.1

Circuit connection of single-phase AC energy meter

3.2.2

Circuit connection of a three-phase meter in a four wire circuit

3.2.3

Circuit connection of a two watt-hour meter unit to measure three-phase energy

23

3.3

3.3.1

Circuit connection of a reactive watt-hour meter

Circuit connection of a three-phase meter in a four-wire circuit

24

EE024 - Power Measurement EMTS


Theoretical Test

25

POWER MEASUREMENT EMTS


TEST 1

QUESTIONS:
1. Give the formulae for the active, reactive and apparent power.
2. For which type of current is the ironless electro-dynamic meter suitable.
3. State the advantages and disadvantages of an ironless electro-dynamic meter.
4. Describe the method of operation of an iron-cored electro-dynamic meter.
5. Name the basic parts of an iron-cored electro-dynamic meter.
6. For what type of current are electrolytic type energy meters suitable?
7. State a formula for the determination of the power factor for:
a) Single-phase AC circuit
b) Three-wire three-phase circuit
8. Give a formula for the determination of electrical energy.
9. Name the main parts of an induction meter.
10. State the procedure for measuring the power consumed by a load, using an induction
meter.

26

POWER MEASUREMENT EMTS


TEST 2

QUESTIONS:
1. Draw the circuit diagram for power measurements in a sing le-phase alternating
current circuit.
2. Draw the circuit diagram for power measurement in an unbalanced three-phase threewire circuit using two-wattmeter circuit.
3. Name the instrument which has the following circuit diagram

4. Draw the circuit diagram for power factor measurements in a three-w ire system.
5. State the definition of electrical energy.
6. Name two types of direct current electrical energy meters.
7. For what type of current is the magnetic motor meter suitable?

27

Test 2 - questions continued


8. Name two types of alternating current electrical energy meter.
9. What is the function of the rotating disc in an induction meter?
10. Is it possible to use the induction motor type of meter for DC current electrical work
measurement?

28

POWER MEASUREMENT EMTS


TEST 1

SOLUTION:

1. Active power:

P = V I cos

Reactive power: Q = V I sin


Apparent power: S = V I
2. AC and DC.
3. No error due to residual induction or eddy current.
Disadvantage: external influences greatly affect the indication of the meter.
4. In a closed circuit current will flow through both fixed and rotating coils. The magnetic
lines produced by the two coils cut in laminated iron core of the fixed coil to a high
extent and the magnetic flux is amplified many times. This flux will force the moving
coil and, therefore, the pointer to move. The iron core is used to eliminate external
influences.
5. Fixed coil, rotating coil, fixed iron core, laminated iron core, damping mechanism,
pointer, scale.
6. DC current.
7. a) cos =

active power

apparent power
b) cos q) =

active power

P
S

apparent power

P
5

29

Test 1 - answers continued


8. Electrical work = true power x time
W=Pxt
units Wh (or Joules).
9. Current coil, voltage coil, worm gear, recording mechanism, permanent magnet,
aluminium disc, power connections (inlet, outlet).
10. a) Switch on the device (load).
b) For a determined period of time count the revolutions of the rotating disc.
c) With this value determine the revolutions of the rotating disc for one hour. This
value is then divided by the constant (c) of the meter.

30

POWER MEASUREMENT EMTS


TEST 2

SOLUTION:
1.

2. Circuit for two power measurements


(Two-wattmeter circuit)

3. Power factor meter.

31

Test 2 - answers continued


4.

5. Electrical work is understood to be the product of power and time during which power
is consumed.
Electrical energy

W = true power P x time t

6. a) Electrolytic type
b) The magnetic motor meter
7. DC current.
8. a) The induction meter
b) The electro-dynamic motor meter
9. After the circuit has broken it prevents the meter from running past this point, i.e. as a
stop mechanism.
10. No.

32

KEY TO EVALUATION

PER CENT

MARK

88 100

75 87

62 74

50 61

0 49

33

You might also like