You are on page 1of 1

Envent Engineering Ltd.

Factory Calibration Data

2012-09-07

Opsco Energy Industries Ltd.


Contact/Site Information
Contact: Thuy Vo
W Phone #: 403-723-3434
Email: thuy.vo@ansignengry.com
C Phone #: ***
Billing Address: 285175 Kleysen Way Rockyview, AB
Fax #: ***
Shipping Address: 285175 Kleysen Way Rockyview, AB
LSD:
Site Info: ***
Administration Information
Order Date:
PO#:

Due Date:
Ship Date:

28. Aug. 2012


PO0025676

28. Sep. 2012


***

Model Specifications
Model:

331

Power:

240VAC

Serial #:
Range:
Aperture:

0-50
1/32

SCS:
# Streams:

ppm

331-0825
Standard
1

Custom Options: Comm Card, LT, Heated Med Blue Encl, 72 Free Standing Rack
Factory Calibration Data
Mainboard
Sensor
MBC 1206-003
SBC 1208-013

Serial Numbers:

Software:

GUI
8.9

Display
DBC 1207-052

Embedded
8.6

Config #
Custom

Configuration:
Gain:

11.91

Flowmeter:

F65-AV1 (100049)

I/O Configurations

AO-1:
AO-2:

Raw Values
Zero
Span
0
50
0
50

Eng Units.
Zero
Span
763
3831
762
3810

Description
Low Tape

Setpoint
FAIL

Solenoid
-

Relay
4

Virtual
1

LED
Fault

Full Scale AO
-

Alarm Configurations
Description
H Alm
HH Alm
RRA
Sensor Low
Sensor High
Low Temp

Setpoint
13 ppm
25 ppm
50 ppm
500 mV
1200 mV
0.0 C

Solenoid
1
1
-

Relay
1
2
1&2
4
4
4

Virtual
2
3
4

LED
1
2
1&2
Fault
Fault
Fault

Full Scale AO
AO-1
-

DI-1:

Other Information
Project Info:
Notes: SOL #1 = NE (Active State Closed)
REL #1, REL #2 & REL #4 = ND (Active State Open)

Tested By: GN & RT


Printed By: RT
Envent Engineering Ltd. 7060E Farrell Road. S.E., T2H 0T2 Calgary, Alberta, Telephone +1 403 253 4012 | Fax +1 403 253 4016 | Email info@envent-eng.com