Professional Documents
Culture Documents
1 of 3
print | close
07-03-15 2:26 PM
2 of 3
07-03-15 2:26 PM
3 of 3
circuit [110.14(C)]. Unless the equipment is listed and marked otherwise, conductor sizing for equipment
terminations must be based on Table 310.15(B)(16) in accordance with (a) or (b):
(a) Equipment Rated 100A or Less [110.14(C)(1)(a)].
Conductors must be sized using the 60C temperature column of Table 310.15(B)(16) [110.14(C)
(1)(a)(1)].
Conductors terminating on terminals rated 75C are sized in accordance with theampacitieslisted in the
75C temperature column of Table 310.15(B)(16) [110.14(C)(1)(a)(3)], as shown in Fig. 2.
(b) Equipment Rated Over 100A.
Conductors must be sized using the 75C temperature column of Table 310.15(B)(16) [110.14(C)
(1)(b)(1)].
Separate connector provisions. Conductors can be sized to the 90C column of Table 310.15(B)(16) if
the conductors and pressure connectors are rated at least 90C [110.14(C)(1)(b)(2)].
Q. What are the installation requirements for equipment disconnecting means?
A. Switches and circuit breakers used as switches must be capable of being operated from a readily accessible
location. They must also be installed so the center of the grip of the operating handle of the switch or circuit
breaker, when in its highest position, isnt more than 6 ft,7in. above the floor or working platform [240.24(A)
and 404.8(A)].
The disconnecting means for a mobile home must be installed so the bottom of the enclosure isnt less than 2 ft
above the finished grade or working platform [550.32(F)].
Exception No. 1: Onbusways, fusible switches and circuit breakers can be located at the same level as
thebuswaywhere suitable means is provided to operate the handle of the device from the floor.
Exception No. 2: Switches and circuit breakers used as switches can be mounted above 6 ft - 7 in. if theyre next
to the equipment they supply, and are accessible by portable means [240.24(A)(4)].
Q. What are the grounding requirements for a building supplied by a feeder?
A. Each building/structures disconnect must be connected to an electrode of a type identified in 250.52
[250.32(A)]. The grounding of the building/structure disconnecting means to the earth is intended to help in
limiting induced voltages on the metal parts from nearby lightning strikes [250.4(A)(1)].
The Code prohibits the use of the earth to serve as an effective ground-fault current path [250.4(A)(5) and
250.4(B)(4)].
Exception: A grounding electrode isnt required where the building/structure is served with a 2-wire, 3-wire, or
4-wiremultiwirebranch circuit.
Source URL: http://ecmweb.com/qampa/stumped-code-conductors-tamper-resistant-receptacles-raceways
07-03-15 2:26 PM