Professional Documents
Culture Documents
Installation without permit maybe allowed if not more than two additional general
purpose branch circuits for lighting and convenience outlets.
1. 760 mm x 1000 mm
2. 600 mm x 900 mm
3. 500 mm x 760 mm
b. Convenience Layout Plan –is the arrangement of small appliance outlets and special
Outlets in the different rooms and parts of the building. It also includes the location of the
service equipment such as the main switch, kWHr Meter and panel boards.
c. Fire Detection and Alarm Layout plan – Arrangement of signaling and alarm system in the
different parts of the building.
5. Schedule of Loads –is a table of the expected loads of the building being designed. It includes the ff.
a. Number of branch circuit of the electrical wiring system.
b. Number of lighting/Convenience outlets per branch circuit
c. Number of switch per circuit
d. Total load wattage per circuit
e. Size of wire used in each circuit
f. Total current load per circuit
g. Branch circuit rating
6. Design Analysis –
7. One Line Diagram –is an schematic drawing of the service entrance, service equipment and the different circuits.
PEC (PHILIPPINE ELECTRICAL CODE)
Article 1.10 – Requirement for Electrical Installation
What are the considerations to be evaluated on Electrical Installations?
All splices and joints and free ends shall be covered with an insulation equivalent to
that of the conductors or with an insulating device identified for the purpose.
At what voltage of live parts be guarded against accidental contact?
Live parts of electric equipment operating at 540 volts or more shall be guarded against
accidental contact by approved enclosures.
PEC (PHILIPPINE ELECTRICAL CODE)
Article 2 – Use and Identification of Grounded Conductors
What is the standard color for grounding conductor?
shall be identified by a continuous white or natural gray outer finish or by three continuous
white stripes on other than green insulation along its entire length.
The rating for other than individual branch circuit shall be 15, 20, 30, 40, and 50 amperes.
where conductors of higher ampacity are used for any reason, the ampere rating of the
specified overcurrent device shall determine the circuit rating.
When the voltage is 120v and/or 250v single phase, 15-20A receptacles and in locations:
1. Bathrooms
2. Garages
3. Outdoors
4. Crawl spaces
5. Unfinished basements
6. Kitchens
7. Wet bar sink
PEC (PHILIPPINE ELECTRICAL CODE)
What is the maximum floor area or wattage to be serve on a single 20A, 2-wire branch circuit?
If the dwelling unit it not more than 50 sq meters and does not exceed 3680 volt-amperes.
What is the minimum branch circuit rating for any household coking appliances of 8 ¾ kW or more?
40 Amperes
15 or 20 15 12
20 20 16
30 30 24
PEC (PHILIPPINE ELECTRICAL CODE)
Can more than 50A branch circuit be used to supply non-lighting load?
No, branch circuit larger than 50A shall supply only non-lighting outlet loads.
3 meters 3 meters
In dwelling units,
Hallways of
3000mm
0r ore in length hallway S3W
shall S3W
Have at least one
receptacle
Outlet.
PEC (PHILIPPINE ELECTRICAL CODE)
The Ampacity of feeder conductors shall not be less than 30A where the load supplied consist of
any of the following number and types of circuits:
The floor area for each floor shall be computed from the outside dimension of the
building, dwelling unit, or other area involved. For dwelling units, the computed floor area shall not
Include open porches, garages, or unused or unfinished spaces not adoptable for furniture use.
PEC (PHILIPPINE ELECTRICAL CODE)
What are the Clearances of Service Drop Prescribe by PEC?
It can be installed either inside or outside of the building served or where the
conductors pass trough the building. It shall be mounted at a readily accessible location
nearest the point of conductor entrance.
What is the minimum vertical clearance to the point of attachment of service
entrance conductors?
it shall not be smaller than 8.0mm2 (3.2mm dia.) copper or 14mm2 aluminum or
copper-clad aluminum. Exception: Conductors supplying limited loads of a single branch
circuit such as small polyphase power, controlled water heater shall no be smaller than
3.5mm2 (2.0 mm dia) hard-drawn copper or equivalent.
PEC (PHILIPPINE ELECTRICAL CODE)
How do you protect service cables subject to physical damage?
Support by strap or other approved means within 300 mm of every service head,
gooseneck, or connection to a raceway or enclosure and at interval not exceeding 760 mm.
15 25 30 35 40
45 50 60 70 80
90 100 110 125 150
175 200 225 250 300
350 400 450 500 600
700 800 1000 1200 1600
2000 2500 3000 4000 5000
6000 Amperes
No, unless the overcurrent device opens all conductors of the circuit, including the
grounded conductor, and is designed so that no pole can operate independently;
where required by section 4.30.3.6 or 4.30.3.7 for motor overload protection.
1. Metal underground water pipe –a buried metal water pipe is s suitable electrode if there is
3000 mm (10’) or more of it in direct contact with the earth but by itself is not an adequate
grounding electrode and must be supplemented by at least one other electrode to provide a
grounding system.
2. Metal Frame of the building –may be used as grounding provided it is effectively grounded
and would give the same protection as the other methods of grounding.
3. Concrete-Encased Electrode –an electrode encased by at least 50 mm of concrete, located
w/in and near the bottom of a concrete foundation or footing that is direct contact w/ the
earth, consisting of at least 6000 mm of one or more steel reinforcing bars, rods of not less
than 13 mm diameter or consisting at least 6000 mm of bare solid copper conductor not
smaller than 760 mm.
4. Ground ring –consisting of at least 6000 mm of bare copper conductor not smaller than 30
mm2 encircling the building in direct contact w/ the earth at a depth below earth surface not
less than 760 mm.
5. Made other electrodes
a. Metal underground GAS piping system shall not be used as a grounding electrode.
b. Local metal underground system susch as piping system and underground tanks
c. Rod and pipe electrodes –shall not be less than 2400 mm inlength and shall consist
of the following material: steel or iron (not less than 16 mm or 5/8”) conduit (not
smaller than 20 mm or ¾” trade size..
PEC (PHILIPPINE ELECTRICAL CODE)
Article 2.5 -Grounding
Plate electrode –shall expose not less than 1/5 square meter of surface to exterior soil.
Electrode of iron or steel plates shall at least 6.4 mm or ¼” thickness.
Electrodes of non-ferrous metal shall be at least 1.5 mm or 0.06” in thickness. These are
often used by utilities at the bottom of a hole.
Aluminum electrodes is not permitted
¼” or 6.4 mm
1/5
PEC (PHILIPPINE ELECTRICAL CODE)
What must be the resistance of made electrodes?
a single electrode consisting of a rod, pipe, or plate which does not have a
resistance to ground of 25 ohms or less shall be augmented by one additional electrode.
When a resistance is greater than 25 ohms, two or more electrodes maybe connected in
parallel, and they shall not be less than 1900 mm or 6’ apart.
used ground Megger, which is a battery operated ground tester that uses vibratir
to produce pulsating AC, or transistor type ground megger.
PEC (PHILIPPINE ELECTRICAL CODE)
What is the minimum diameter/length of a Ground Rod?
What is a chimney?
What is the allowance or free length of conductors on outlets, junction boxes, and switch points?
Atleast 150 mm or 6”
How is 6” wire allowance measured ?
It is measured from the point in the box where it emerges from its raceway or sheath
6”
PEC (PHILIPPINE ELECTRICAL CODE)
What is the minimum radius bend for conductors?
The conductor shall not be bent to a radius less than 8 times the overall diameter for
nonshielded conductors or 12 times the diameter for shielded or lead-covered
conductors during or after installation.
Can we install solid conductors inside raceway with sizes 8.0 mm2 or larger?
No, against PEC. For conductors installed inside raceway of sizes lager than 8.0
mm2 used only stranded conductors
PEC (PHILIPPINE ELECTRICAL CODE)
1. Ambient temperature
2. Heat generated internally in the conductor as the result of load current flow, including
fundamental and harmonic currents
3. The rate at which generated heat dissipates into ambient medium
4. Adjacent load carrying conductors
The mm2 size stranded or mm diameter for solid shall be repeatedly marked at an
Interval of not exceeding 600 mm. All other markings shall be repeated at interval not
exceeding 1, 000 mm.
Interval is 600 mm
Ungrounded conductors shall be distinguished by colors other than white, natural gray,
or green; or by a combination of color plus distinguishing markings.
PEC (PHILIPPINE ELECTRICAL CODE)
What are the different wiring methods?
1. Armored cable or BX cable
2. Electrical Metallic Tubing (EMT)
3. Electrical Nonmetallic Tubing (ENT)
4. Fire Alarm Cables
5. Flexible Metal Conduit
6. Flexible Metallic Tubing
7. Instrumentation Tray Cable
8. Intermediate Metal Conduit (IMC)
9. Liquidtight Flexible Metal Conduit
10. Liquidtight Flexible Nonmetallic Conduit
11. Metal-clad Cable
12. Meneral-insulated, metal-sheathed cable
13. Multiconductor service-entrance cable
14. Multiconductor underground feeder and branch-circuit cable
15. Multipurpose and communication Cable
16. Nonmetallic Sheathed Cable or NM cable
17. Power-limited tray cable
18. Power and Control Tray Cable
19. Optical fiber cables
20. Other factory-assembled, multiconductor control, signal, or power cables that are
specifically approved for installation in cable trays
21. Rigid Metal Conduit (RMC)
22. Rigid Nonmetallic Conduit
PEC (PHILIPPINE ELECTRICAL CODE)
connector
Metal-clad cable
Mineral-insulated cable
PEC (PHILIPPINE ELECTRICAL CODE)