How to handle the CB close command in

Feeders with Busbar/Breaker/CT arrangements

ABB Switzerland Ltd - 1


2003 ABB. All rights reserved.

REB500 Busbar
Protection System

ABB

ABB Switzerland Ltd - 2


2003 ABB. All rights reserved.

Basic Arrangement of a Feeder Bay




Busbar /Breaker /CT Feeder

Breaker position is configured and


therefore taken into account in order
to have selective tripping in case of
an End-Fault.

By only taken the aux. contacts of the


breaker it is possible that an Arc
causes tripping in case the Arc is
coming earlier as the aux. contacts.
Therefore the Close-Command is
also taken into account for the
measurement. This ensures that the
CT is already assigned to the busbar
protection before the arc occurs

ABB

ABB Switzerland Ltd - 3


2003 ABB. All rights reserved.

REB500: Breaker Closed

Busbar (Protection) zone till CT

CT is assigned to the Busbar Protection

End-Fault blocked as Breaker is closed

ABB

ABB Switzerland Ltd - 4


2003 ABB. All rights reserved.

REB500: Breaker Open

Busbar (Protection) zone till open Breaker

CT is NOT assigned to the Busbar Protection

End-Fault causes tripping of the REMOTE END

ABB

REB500: Breaker Open to Closed with CB_Close




Breaker Open,


CB Close Command applied towards REB500




No problem as CT is already assigned

Aux. contacts report closed ,




ABB Switzerland Ltd - 5


2003 ABB. All rights reserved.

CT is assigned towards the busbar

Possibility of an Arc before aux. contacts report


closed


CT NOT assigned

CT will remain being assigned to busbar.

ABB

REB500: Breaker Open to Closed without CB_Close




Breaker Open,


CB Close Command applied towards REB500




Current in Feeder and CT is NOT assigned -> TRIP

Aux. contacts report closed ,




ABB Switzerland Ltd - 6


2003 ABB. All rights reserved.

CT is assigned towards the busbar

Possibility of an Arc before aux. contacts report


closed


CT NOT assigned

CT is assigned towards the busbar.

ABB

Conclusion
Close Command should be applied in case


Busbar /Breaker /Feeder arrangements,

AND


Breaker position is configured and used by


the BBP. From version 7.0x it can be selected
that the Breaker position is either used not
used for the BBP. In older versions the
breaker position is always used in case it is
engineered in the set-file.

ABB Switzerland Ltd - 7


2003 ABB. All rights reserved.

Close Command can be initiated by:




Local Manual Close Command Switch

Auto-Reclosing Device

SCS

Therefore make sure that all this commands


are applied towards REB500.

ABB