User Manual: HGM400 Automatic Genset Controller
User Manual: HGM400 Automatic Genset Controller
(HGM410/HGM420)
USER MANUAL
Smartgen Technology
Chinese trademark
English trademark
Version
1.0
1.1
1.2
Note
Original release.
Modify typical application.
Modify some details.
INSTRUCTION
Highlights an essential element of a procedure to ensure
NOTE
correctness.
Indicates a procedure or practice, which, if not strictly observed,
CAUTION! could result in damage or destruction of equipment.
ISSUE 2012-10-30
Version 1.2
Page 3 of 30
Table of Contents
1
SUMMARY.................................................................................. 5
SPECIFICATION ......................................................................... 6
OPERATION ............................................................................... 7
4.1 PANEL KEYS ........................................................................................... 7
4.2 PANEL DESCRIPTION ............................................................................ 8
4.3 AUTOMATIC START/STOP OPERATION ............................................... 8
4.4 MANUAL START/STOP OPERATION ................................................... 10
PROTECTION .......................................................................... 10
5.1 WARNINGS ........................................................................................... 10
5.2 SHUTDOWN ALARM ............................................................................. 11
CONNECTIONS ....................................................................... 13
10 COMMISSIONING .................................................................... 25
11 TYPICAL APPLICATION ........................................................... 26
12 INSTALLATION ......................................................................... 28
12.1 FIXING CLIPS ....................................................................................... 28
12.2 OVERALL DIMENSION AND PANEL CUTOUT..................................... 29
ISSUE 2012-10-30
Version 1.2
Page 4 of 30
1 SUMMARY
HGM400 series automatic controller, integrating digital, intelligent and network
techniques, is used for automatic control system of generator. It can achieve automatic
start/stop, data measuring and three remote functions (SG485 module is needed).
The controller uses LCD display, optional Chinese, English, Spanish and Russian
display interface with easy and reliable operation.
HGM400 series automatic controller uses micro-processing technique which can carry
out precision measuring, constant value adjustment, timing and threshold setting and
etc.. All the parameters can be adjusted from front panel or through programmable
interface (USB to LINK, can use SG72 adaptor) via PC. It can be widely used in all
types of generator automatic control system for compact structure, simple connections
and high reliability.
Generator
Line Voltage (Uab, Ubc, Uca)
Phase Voltage (Ua, Ub, Uc)
Frequency (HZ)
Load
Current (IA, IB, IC)
Active Power (KW)
Reactive Power (KVar)
Apparent Power (KVA)
Power Factor (PF)
Accumulated Energy (kWh)
For mains: Over/under voltage, lack of phase; for generator: over/under voltage,
over/under frequency, over current;
Precision measure and display engine parameters,
HGM400 Series Genset Controller
ISSUE 2012-10-30
Version 1.2
Page 5 of 30
Temperature (WT),
C/ F both are display
Oil pressure (OP),
kPa/Psi/Bar all be display
Speed (SPD),
RPM (unit)
Voltage of Battery (VB) V (unit)
Voltage of Charger (VD)
V (unit)
Hours counter (HC): Max. 999999 hours.
Start times: Max.999999 times.
Control protection: Automatic start/stop, switch on/off (ATS control) and fault
display;
With ETS, idle control, pre-heat control, acceleration and deceleration control, all
are relay output;
Parameters setting: Allow user to modify parameters and store them in internal
FLASH, which cannot be lost even when power off. All the parameters can be
adjusted from the front panel, or by PC via an SG72 adaptor;
Types of temperature and pressure sensor can be directly used and user defined;
Conditions of crank disconnect can be selected.(magnetic pickup, oil pressure,
generator);
Power supply range is (8~35)VDC, accommodating to different starting voltage;
All parameters use digital modulation, abandoning analog modulation of
conventional potentiometer, more reliability and stability;
Modular design, flame retardant ABS shell, plug-in terminals, embedded mounting,
compact structure, easy installation.
3 SPECIFICATION
Items
Contents
Working Voltage
Power Consumption
AC voltage Input:
3 Phase 4 Wire
2 Phase 3 Wire
Single phase 2 Wire
3 Phase 3 Wire
Alternator Frequency
50Hz/60 Hz
10,000 Hz (max)
5A
5A
5A
ISSUE 2012-10-30
Version 1.2
Page 6 of 30
5A
Overall Dimensions
Panel Cutout
110mm x 90mm
CT Secondary Current
5A (rated )
Working Condition
Temperature: (-25~70)C;
Humidity: (20~93)%RH
Storage Condition
Temperature: (-30~+80)C
Protection Level
Insulation Intensity
Weight
0.26kg
4 OPERATION
4.1 PANEL KEYS
Stop/ Reset
Start
Manual
Pressing this and up key
Automatic
Set/Confirm
Up/Increase
Pressing this key will set the module into auto mode.
Enter into Set menu after pressing this key;
Shift cursor to confirm.
Turning pages up;
In parameter setting, shift cursor and increase values.
ISSUE 2012-10-30
Version 1.2
Page 7 of 30
Down/Decrease
ISSUE 2012-10-30
Version 1.2
Page 8 of 30
ISSUE 2012-10-30
Version 1.2
Page 9 of 30
not.
7) When genset has stopped, enters into standby mode; if failed to stop, controller will
alarm (Fail to Stop alarm will be displayed in LCD).
4.4
key, choose Manual Test Mode. Under the two modes, press
key to
start genset, it can automatically judge crank disconnect and accelerate to hi-speed
running. If high temperature, low oil pressure, over speed and abnormal voltage
occur during genset running, controller can effectively protect genset to stop (detail
procedures please refer to No.4~9 of Auto start operation). Under Manual Mode
if mains normal, load switch wont transfer; if mains abnormal, load switch will transfer
to gens. Under Manual Test Mode, after genset normally runs in high speed, no
matter mains normal or not, load will be transferred to gens.
2) HGM410: Manual Mode is activated when press
Then press
accelerate to hi-speed running. If hi-temperature, low oil pressure, over speed and
abnormal voltage occur during genset running, controller can effectively protect
genset to stop (detail procedures please refer to No.4~9 of Auto start operation).
Controller will send closing signal when genset runs in high speed.
3) Manual stop: pressing
5 PROTECTION
5.1 WARNINGS
When controller detects the warning signal, only alarm and not stop genset. The alarms
are displayed in LCD.
Warnings as following,
No.
1
Items
High
Temperature
Description
When controller detected the temperature is higher than
preset and shutdown is prohibited, it will send a stop alarm
signal and it will be displayed in LCD.
ISSUE 2012-10-30
Version 1.2
Page 10 of 30
Oil
Charge Failure
Battery
Voltage
Battery Over
Voltage
Auxiliary
Warning
Low
10
Loss Of Speed
Signal
11
Low Coolant
Level
12
Temp. Sensor
Open
13
Oil Pressure
Sensor Open
ISSUE 2012-10-30
Version 1.2
Page 11 of 30
No
Items
Description
High
Temperature
Low
Pressure
Over Speed
Under Speed
Loss Of Speed
Signal
Gens
Voltage
Over
Gens
Voltage
Under
Gens
Current
Over
10
Fail To Start
11
Over Frequency
12
Under
Frequency
13
Genset Failed
14
15
Low
Level
Liquid
16
Temp.
Open
Sensor
17
Oil
Oil
Pressure
be displayed in LCD.
When controller detected the temperature of water/cylinder
is higher than preset, it will send a stop alarm signal and it
will be displayed in LCD.
When controller detected oil pressure is lower than the
preset, it will send a stop alarm signal and it will be displayed
in LCD.
When controller detected genset speed is over the preset, it
will send a stop alarm signal and it will be displayed in LCD.
When controller detected genset speed is under the preset, it
will send a stop alarm signal and it will be displayed in LCD.
When controller detected genset speed is 0 (the delay is not
0), it will send a stop alarm signal and it will be displayed in
LCD.
When controller detected genset voltage is over the preset, it
will send a stop alarm signal and it will be displayed in LCD.
When controller detected genset voltage is under the preset,
it will send a stop alarm signal and it will be displayed in
LCD.
When controller detected genset current is over the preset
and delay is not 0, it will send a stop alarm signal and it will
be displayed in LCD.
During the start attempt times, if genset start failed, it will
send a stop alarm signal and it will be displayed in LCD.
When controller detected genset frequency is over the
preset, it will send a stop alarm signal and it will be displayed
in LCD.
When controller detected genset frequency is under the
preset, it will send a stop alarm signal and it will be displayed
in LCD.
When controller detected genset frequency is 0, it will send a
stop alarm signal and it will be displayed in LCD
When controller detected genset fuel level low input is active,
it will send a stop alarm signal and it will be displayed in
LCD.
When controller detected genset water level low input is
active, it will send a stop alarm signal and it will be displayed
in LCD.
When temperature sensor opens circuit and the input is
active, controller will send a stop alarm signal and it will be
displayed in LCD.
When oil pressure sensor opens circuit and the input is
ISSUE 2012-10-30
Version 1.2
Page 12 of 30
No
Items
Sensor Open
Description
active, controller will send a stop alarm signal and it will be
displayed in LCD.
CONNECTIONS
Description
Connect battery negative.
Connect battery positive. If longer than
30m, parallel connection with 2 cables.
Recommend using maximum 20A fuse.
Plant Supply B+ from pin 2, 5 A rated.
DC Power Supply B+
1.5mm2
Programmable
Output 1
1.0mm2
1.0mm2
Programmable Relay
Output 2
Programmable Relay
Output 3
Auxiliary Input 1
Auxiliary Input 2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
5
6
7
8
Relay
ISSUE 2012-10-30
Version 1.2
See Table 3
Page 13 of 30
Pin
Function
9
10
Auxiliary Input 3
Auxiliary Input 4
Temperature
Sensor
Input
11
Cable
Size
1.0mm2
1.0mm2
1.0mm2
12
1.0mm2
13
CT A Phase Sensing
1.5mm2
14
CT B Phase Sensing
1.5mm2
15
CT C Phase Sensing
1.5mm2
16
CT Common
1.5mm2
2
17
0.5mm
18
Charger D+ Input
1.0mm2
19
20
21
22
23
24
25
26
27
28
29
Programmable
Output 4
Programmable
Output 5
Relay
1.0mm2
Relay
1.0mm2
Common Port
1.5mm2
Generator U Phase
Sensing
Generator V Phase
Sensing
Generator W Phase
Sensing
Generator N2 Output
Mains
R
Phase
Sensing
Mains
S
Phase
Sensing
Mains
T
Phase
Sensing
1.0mm2
Mains N1 Sensing
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
Description
Connect to GND (B-)
Connect to GND (B-)
Connect a temperature
resistance sensor.
See Table 4
Connect to a pressure
resistance sensor.
Connect current transformer secondary
coil (rated 5A)
Connect current transformer secondary
coil (rated 5A)
Connect current transformer secondary
coil (rated 5A)
See INSTALLATION in the manual.
Connect magnetic pickup.
Recommend using screen.
Connect battery negative at one end.
Connect D+ terminal. If there is no, this
input remains Not Connect.
Terminal 19 and 21 are relay N/O contact,
rated 5A.
Terminal 20 and 21 are relay N/O contact,
rated 5A.
Common port of programmable relay
output 4 and 5.
Connect U phase of generator
Recommend 2A fuse
Connect V phase of generator
Recommend 2A fuse
Connect W phase of generator
Recommend 2A fuse
Connect neutral output of generator.
Connect R phase of mains
Recommend 2A fuse (HGM410 without)
Connect S phase of mains
Recommend 2A fuse (HGM410 without)
Connect T phase of mains
Recommend 2A fuse (HGM410 without)
Connect neutral line of mains
(HGM410 without)
ISSUE 2012-10-30
Version 1.2
Page 14 of 30
programmed by PC via an SG72 adapter. If there is need to remote start the genset,
please use the SG485 module.
Range
Items
Mains
Delay
Mains
Delay
Normal
Abnormal
Mains
Voltage
Under
Mains
Voltage
Over
Transfer
Time
Rest
(0-3600)s
Default
Description
10
Mains transient delay, suitable for
ATS (automatic transfer switch).
(0-3600)s
(30-620)V
184
(30-620)V
276
(0-99.9)s
1.0
Start Delay
(0-3600)s
Stop Delay
(0-3600)s
Start Times
(1-10)times
Preheat Time
(0-300)s
10
Crank Time
(3-60)s
11
(3-60)s
10
ISSUE 2012-10-30
Version 1.2
Page 15 of 30
No
Range
Items
12
Safety
Time
13
Run
On
Default
(1-60)s
10
(0-3600)s
14
Warm Up Time
(0-3600)s
10
15
Cooling Time
(3-3600)s
10
16
Stop Idle
ETS
Solenoid
Hold
(0-3600)s
(0-120)s
20
18
(0-120)s
19
Switching On
(0-10)s
5.0
20
Flywheel Teeth
(10-300)
118
21
Generator
Abnormal Delay
(0-20.0)s
10.0
22
Generator
Voltage
(30-620)V
264
23
Generator Under
Voltage
(30-620)V
196
24
Under Speed
(0-6000)RPM
1200
25
Over Speed
(0-6000)RPM
1710
17
Over
ISSUE 2012-10-30
Description
During this period, Low Oil
Pressure, High Temperature,
Under Speed, Under Frequency
and Charge Failure alarms are
inactive.
Idle running time when starting.
Delay for warming up before
closing.
Delay of cooling time before
stopping.
Idle running time when stopping.
Its the delay for energizing to
stop.
When set ETS solenoid hold as
0s, from idle delay over to over
stop timer; if not 0s, its from ETS
delay over to genset at rest.
Pulse width of mains or closing
gens. When it is 0s, output is
continuous.
Used
for
judging
crank
disconnect and detecting rotating
speed. See INSTALLATION in
this manual.
Gens high voltage and low
voltage alarm delay.
When voltage is over the point,
Gens Over Voltage is active.
When the point is 620V, Gens
Over Voltage is disabled.
When voltage is under the point,
Gens Under Voltage is active.
When the point is 30V, Gens
Under Voltage is disabled.
When engine speed is under the
point and holds for 10s, Gens
Under Speed is active.
When engine speed is over the
point and holds for 2s, Gens
Over Speed is active.
Version 1.2
Page 16 of 30
No
Range
Items
Default
26
Under Frequency
(0-75.0)Hz
45.0
27
Over Frequency
(0-75.0)Hz
57.0
28
High Temperature
(80-140)C
98
29
(0-400)kPa
103
30
Loss of
Signal
(0-20.0)s
5.0
31
Charge Failure
(0-30)V
6.0
32
Battery
Voltage
Over
(12-40)V
33.0
33
Battery
Voltage
Under
(4-30)V
8.0
34
CT Rate
(5-6000)/5
500
35
(5-6000)A
500
36
Over
Current
Percentage
(50-130)%
120
Speed
ISSUE 2012-10-30
Description
When generator frequency is
lower than the point and holds for
10s, Gens Under Frequency is
active.
When generator frequency is
over the point and holds for 2s,
Gens Over Frequency is active.
When engine temperature sensor
value is over this point, send
alarm signal. Active from end of
safety run on timer. When the
value is 140, high temperature
alarm is disabled. (only suitable
for temperature sensor)
When engine oil pressure sensor
value is under this point, send
alarm signal. Active from end of
safety run on timer. Low oil
pressure alarm is disabled. (only
suitable for oil pressure sensor)
If set the delay as 0, only warn
not to stop the generator.
During generator is running,
when alternator WL/D+ voltage is
under this point and remains for
5s, generator will send shutdown
alarm.
When battery voltage is over the
point and holds for 20s, Battery
Over Voltage is active. Its a
warning alarm.
When generator battery voltage
is under the point and holds for
20s, Battery Under Voltage is
active. Its a warning alarm.
Current transformer rate
Maximum rated current, used for
calculating over current.
When the load current is over the
point, over current delay begins.
Version 1.2
Page 17 of 30
No
Range
Items
37
Over
Delay
38
Current
Default
Description
When load current is over the
pre-set value, over current is
initiated. When set delay timer as
0, only warning no shutdown,
Factory default: Fuel Relay
Output
Factory default: Energized To
Stop
Factory default: Idle Control
Factory default: Gens Closed
Factory default: Mains Closed
Factory
default:
High
Temperature Alarm
(0-3600)s
1296
Digital Output 1
(0-17)
14
39
Digital Output 2
(0-17)
40
41
42
Digital Output 3
Digital Output 4
Digital Output 5
(0-17)
(0-17)
(0-17)
3
5
6
43
Auxiliary Input 1
(0-15)
(0-1)
(0-20.0)s
2.0
(0-15)
(0-1)
(0-20.0)s
2.0
(0-15)
10
(0-1)
(0-20.0)s
2.0
(0-15)
11
(0-1)
(0-20.0)s
2.0
44
45
46
47
48
49
50
51
52
53
54
Auxiliary Input 1
Active
Auxiliary Input 1
Delay
Auxiliary Input 2
Auxiliary Input
Active
Auxiliary Input
Delay
Auxiliary Input 3
Auxiliary Input
Active
Auxiliary Input
Delay
2
2
3
3
Auxiliary Input 4
Auxiliary Input 4
Active
Auxiliary Input 4
Delay
55
Module Mode
(0-2)
56
Module Address
(1-254)
57
Passwords
(0-9999)
1234
ISSUE 2012-10-30
0: Stop Mode
1: Manual Mode
2: Auto Mode
Communication
controller.
Version 1.2
address
of
Page 18 of 30
No
Range
Items
Default
Description
Conditions of crank disconnect
includes gens, magnetic pickup
and oil pressure which make
starter separate with engine.
See Table 5
When engine speed is over this
point, starter will disconnect.
When generator frequency is
over this point, starter will
disconnect.
When engine oil pressure is over
this point, starter will disconnect.
Factory default: when the
temperature is too high, alarm to
shutdown. Note 1.
Factory
default:
when
oil
pressure is lower, alarm to
shutdown. Note 2
0: 3P4W; 1:2P3W
2:1P2W; 3: 3P3W Note 3
58
Crank Disconnect
(0-5)
59
Engine Speed
(0-3000)RPM
360
60
Engine
Frequency
(10.0-30.0)Hz 14.0
61
(0-400)kPa
200
62
(0-1)
63
Low OP Inhibit
(0-1)
64
Voltage Input
(0-3)
(0-9)
08
SGX
(0-9)
08
SGX
(2-32)
65
66
67
Temp.
Sensor
Select
Pressure Sensor
Select
Number Of Poles
68
Temperature
Sensor Open
(0-2)
69
Oil
Pressure
Sensor Open
(0-2)
70
Defined
Curve
(0-1)
Sensor
ISSUE 2012-10-30
Version 1.2
Page 19 of 30
preset, or low oil pressure alarm input is active, controller will send warning signal only
and not stop unit.
Note 3, if 3P3W is selected, maximum shutdown threshold of Mains Over
Voltage and Gens Over Voltage can be 620V; when select others, maximum
shutdown threshold can be 360V.
Items
Description
Not Used
Common Alarm
Idle Control
Preheat Control
Close Generator
Close Mains
Switching Off
Acceleration Control
Deceleration Control
10
Genset Run
11
12
ISSUE 2012-10-30
Version 1.2
Page 20 of 30
No
13
14
15
16
17
Items
Description
System
In
Auto
The controller work in automatic mode.
Mode
Fuel Relay Output
To control fuel relay output.
Reserved
Reserved
Reserved
Items
Not Used
High Temp. Alarm
TABLE
(ACTIVE
WHEN
Description
Low OP Alarm
Auxiliary Alarm
Auxiliary Shutdown
Coolant To Stop
6
7
Generator Closed
Mains Closed
High Temp. Stop
Inhibit
Low Oil Pressure
Stop Inhibit
HGM410 without
When it is active, prohibit stopping when high
temperature occurs. Note 1
When it is active, prohibit stopping when oil low
pressure occurs. Note 2
HGM420 without
8
9
10
11
12
13
14
15
Low
Fuel
Warn
Low Liquid
Warn
Low
Fuel
Shutdown
Low Liquid
Shutdown
Level
Level
Level
Level
Version 1.2
Page 21 of 30
Temperature
Sensor
Pressure
Sensor
Content
0 Not used
1 Defined Res. Type
2 VDO
3 SGH(Huanghe sensor)
4 SGD(Dongkang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
9 Reserved
0 Not used
1 Defined Res. Type
2 VDO 10Bar
3 SGH(Huanghe sensor)
4 SGD(Dongkang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
Description
Content
Magnetic pickup
Generator
1) The crank disconnect condition has three kinds, the magnetic pickup and the
generator voltage can be used alone, oil pressure must be used with the magnetic
pickup and the generator voltage, in order to make the starter disconnect as soon
as possible.
2) Magnetic pickup is installed in the engine for testing flywheel.
3) When choosing magnetic pickup, ensure the number of flywheel teeth is same as
the set, otherwise over speed or under speed shutdown may appear.
4) If the generator is not installed with magnetic pickup, please don't select
HGM400 Series Genset Controller
ISSUE 2012-10-30
Version 1.2
Page 22 of 30
corresponding item.
5) If the generator has no oil pressure sensor, please don't choose corresponding.
6) If the generator is not selected, controller will not measure and display relative
parameters (This can be applied to the pump set), if not choose magnetic pickup,
the speed signal will come from the generating AC signal.
8 PARAMETERS SETTING
After controller powered on, press
below:
Fig1
1
2
3
4
Set Parameters
Information
Set Language
Mode Select
Set Parameters
When entering password interface, inputting 1234 can set part of the parameter
items in table 1; inputting 0318 can set all the items. (Table 1) If there is need to
set more parameters, please contact the factory.
NOTES:
1. For HGM410, there are no items from 1 to 5 in table 1; there are no digital outputs
about mains in auxiliary output 1-5.
2. Please modify the parameters (such as crank disconnection, auxiliary input/output
and various timers) in standby mode, otherwise alarm to shutdown or other
abnormal conditions may happen.
3. The over-voltage threshold must be greater than the under-voltage threshold;
otherwise over-voltage and under-voltage will occur at the same time.
4. The over-speed threshold must be greater than under-speed threshold, otherwise
over speed and under speed will occur at the same time.
5. Set the frequency (crank disconnect) as low as possible, in order to separate the
starter quickly when crank disconnect.
6. Auxiliary input 1-4 cannot be set as the same item, or will cause incorrect functions.
But auxiliary output 1-5 can be set as the same item.
7. If need to shut down after cooling, please set any auxiliary input as Coolant To
ISSUE 2012-10-30
Version 1.2
Page 23 of 30
Set Language
Chinese, English, Spanish and Russian interface can be selected.
Mode Select
The controller can be set as Manual Test Mode, Manual Mode or Auto Mode.
Note: Pressing
key at any time will quit the setting and return to the previous
setting menu.
9 SENSOR SELECT
1) When choosing sensor, standard of sensor curve will be needed. If set
temperature sensor as SGH (120C resistance type), sensor curve should be SGH
(120oC resistance type); If set as SGD (120C resistance type), sensor curve
should be SGD curve.
2) If there is difference between standard sensor curve and chosen sensor, select
"defined sensor", and then input defined sensor curve.
3) When inputting sensor curve, X value (resistance) must be in accordance with the
order of higher to lower, otherwise errors will occur.
4) When select sensor "Not used", temperature, pressure and fuel level will be
display as" - - -" in LCD.
5) If there is no pressure sensor, but only has low pressure alarm switch, then you
must set pressure sensor as "Not used", otherwise oil pressure low alarm
shutdown may appear.
6) Can set several points of forehand or backmost as the same ordinate, like the
following picture:
ISSUE 2012-10-30
Version 1.2
Page 24 of 30
1Pa
1kgf/cm2
1bar
1psi
1N/m2 (pa)
1kgf/cm2
1bar
(1b/in2) psi
1
9.8x104
1x105
6.89x103
1.02x105
1
1.02
7.03x102
1x105
0.98
1
6.89x102
1.45x104
14.2
14.5
1
10 COMMISSIONING
Before operation, the following checking should be carried out:
1) Check and ensure all the connections are correct and wires diameter is suitable.
2) Ensure that the controller DC power has insurance; battery positive and negative
have correctly connected.
3) Take proper actions to prevent engine to disconnect crank (for example, to remove
the connections of fuel value). If checking is OK, connect start battery, select Manual
Mode, controller will execute the program.
4) Set controller as Manual Mode, press start button to start genset. If failed within the
setting crank times, controller will send Failed to Start signal; then press Reset to
reset controller.
5) Recover actions of preventing engine to disconnect crank (e. g. Connect wire of fuel
value), press start button again, genset will start. If everything goes well, genset will
normal run after idle running (if configured). During this period, watch for engines
running situations and voltage and frequency of alternator. If abnormal, stop genset
and check all connections according to this manual.
6) Select the Auto Mode from front panel, connect to mains signal. After the mains
HGM400 Series Genset Controller
ISSUE 2012-10-30
Version 1.2
Page 25 of 30
normal delay, controller will transfer ATS (if configured) and into mains load. After
cooling, controller will stop genset and into standby state until mains abnormal again.
7) When mains abnormal again, genset will start automatically and into normal running,
send signal to make gens close, transfer ATS and make genset take load. If not like
this, please check connections of ATS according to this manual.
8) If there are any other questions, please contact our technical personnel.
11 TYPICAL APPLICATION
HGM410 Typical wiring diagram
ISSUE 2012-10-30
Version 1.2
Page 26 of 30
CAUTION! Recommend expanding relay with high capacity in start and fuel
output.
ISSUE 2012-10-30
Version 1.2
Page 27 of 30
12 INSTALLATION
12.1 FIXING CLIPS
The module is held into the panel fascia using the supplied fixing clips.
1) Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
2) Pull the fixing clip backwards (towards the back of the module) ensuring four clips
are inside their allotted slots.
3) Turn the fixing clip screws clockwise until they make contact with the panel.
Note: Care should be taken not to over tighten the screws of fixing clips.
ISSUE 2012-10-30
Version 1.2
Page 28 of 30
ISSUE 2012-10-30
Version 1.2
Page 29 of 30
secondary current must be 5A. Besides, the phase of CT and input voltage must
be correct, or the sampling current and active power may be incorrect.
CAUTIONICOM must connect battery anode of the controller.
WARNING! When there is load current; the CT secondary side cannot open
circuit.
5) Withdraw Voltage Test
When the controller has been installed in the control panel, during the test please
disconnect all the terminals, lest high voltage damages the controller.
13 FAULT FINDING
Symptom
Controller inoperative
Genset stops
Emergency shutdown
Possible Remedy
Check starting battery;
Check connections of the controller;
Check the DC fuse.
Check if water/cylinder temperature too high.
Check alternator voltage.
Check the DC fuse.
Check if an emergency stop button is fitted; Ensure
battery positive is connected to the emergency stop
input.
Check if connection is open circuit.
ISSUE 2012-10-30
Version 1.2
Page 30 of 30