You are on page 1of 1

Functions

LDALI Power Supply

BACnet
CEA709

LDALIPWR2-U, LDALIPWR4-U

DALI
OPC

Datasheet #89023218

LWEB

The DALI power supplies LDALIPWR2-U and LDALIPWR4-U are used to power
two or four DALI channels. Per channel, the power supplies provide up to 116mA
to power devices connected to the DALI channel.
When the DALI devices connected to the channel consume more than the 116mA,
two DALI outputs of the power supplies can be used in parallel. Hence, the maximum current provided this way is limited to 232mA.

LROC

Installation
The DALI channel is treated to be non-SELV (Safety Extra Low Voltage). Therefore
the relevant installation regulations for low voltage apply. The cable of a DALI
channel is either limited to a maximum length of 300m using a minimum wire
cross-section of 1.5mm (AWG15) or must ensure a maximal voltage drop of 2V.

LINX

Wide Range Supply Voltage


The power supplies accept a wide range of supply voltage from 85-240VAC,
50/60Hz. They also feature a starting-current limitation.
DALI Power Outputs

LVIS,L-STAT

POWER

DA1+ DA1DALI 1

DA2+ DA2DALI 2

DA3+ DA3DALI 3

DA4+ DA4DALI 4

Made in Austria

DA+ DADALI 1

DA+ DADALI 2

116mA

116mA

LOYTEC
www.loytec.com

85-240VAC
50/60 Hz

L-DALI

OUTPUT
DALI 4x 116mA

LDALI-3E104-U

Made in Austria

LDALI-PWR4-U

PWR N

85-240VAC
L 50/60Hz

USB 2
USB 1

DA+ DADALI 3

116mA

DA1

DA2

DALI 1
DA+ DADALI 4
DA3

116mA

status

DA4

L-DALI

CEA-709 DALI Controller

Ethernet 2
Ethernet 1

NC

FT
B

LDALI

Input
N
L

FT
USB

Power Supply

LOYTEC
www.loytec.com

DALI 2

DALI 3

Gateways

DALI 4

LIOB

The DALI power outputs provide 16V (11V 20.5V) and 116mA. The power outputs are isolated from mains by basic isolation. The power outputs are short circuit
proof and shut down if thermally overloaded. When a thermal overload occurs,
the DALI control lamp switches off.

Accessories

Interfaces

Routers,NIC

85 - 240 VAC

IP-852

TP/FT-10

Specifications
Dimensions (mm)

107x100x60 (LxWxH), DIM023

Installation

DIN rail mounting following DIN43880, top hat rail EN50022

Power supply

85-240V AC, 50/60Hz, current limited start up, max. 12W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

LDALIPWR2-U: 2x16VDC (11V 20.5V), each 116mA, short-circuitproof, basic isolation (not SELV) to the power line
LDALIPWR4-U: 4x16VDC (11V 20.5V), each 116mA, short-circuitproof, basic isolation (not SELV) to the power line

Order number

Product description

LDALIPWR2-U

DALI power supply unit for 2 DALI channels

LDALIPWR4-U

DALI power supply unit for 4 DALI channels

134