Busbar calculation
Exercise data
# Consider a switchboard comprised of at least 5 MV cubicles.
Each cubicle has 3 insulators(1 per phase).
Busbars comprising 2 bars per phase, inter-connect the cubicles
electrically.
10
cm2
18
cm
70
cm
ambient temprature
40
( - n)
50
(90-40=50)
Cellule 1
Cellule 2
Cellule 3
Cellule 4
profile
flat
material
Cellule 5
arrangement:
edge-mounted
d
d
# Rated frequency fr = 50 Hz
1 cm
1 cm
10 cm
5 cm
# Other characteristics:
5 parts in contact with the busbars can withstand a maximum
temperature of max = 100C
5 the supports used have a bending resistance of F = 1 000 daN
12 cm
TED300014EN_030_037.
Gamme
Schneider Electric
Design rules
Lets check
the thermal withstand
of the busbars!
Busbar calculation
0
24.9 ( n )
S p
I = K ------------------------------------------------------------------20 [ 1 + ( 20 )]
with:
ambient temperature
40
( - n)
50
busbar cross-section
10
cm2
busbar perimeter
22
cm
p20
copper:
1.83 cm
temperature coefficient
for the resistivity:
0.004
condition coefficient
product of 6 coefficients (k1, k2, k3, k4, k5, k6),
described below
e /a
0.05
0.06
0.08
0.10
number of bars per phase
2 1.63
1.73
1.76
1.80
3 2.40
2.45
2.50
2.55
0.12
0.14
k1
1.83
1.85
2.60
2.63
0.16
0.18
0.20
1.87
2.65
1.89
2.68
1.91
2.70
In our case:
Schneider Electric
e/a =
number of bars per phase =
giving k1 =
1.80
Gamme
0.1
AMTED300014EN_030_03
Design rules
Busbar calculation
1
1
In our case:
n= 2
In fact, we have:
k = 1.80 1
2
1
3
0.98
giving k6 = 1
0.8
= 1.44
0 . 61
0.5
0 . 39
10
22
24 . 9 ( 90 40 )
I = 1. 44 ----------------------------------------------------------------------------------------------------------------------------------------1 . 83 [ 1 + 0 . 004 ( 90 20 ) ]
0 . 61
0.5
0 . 39
24 . 9 ( n )
S p
I = K ------------------------------------------------------------------------------20 [ 1 + ( 20 ) ]
I=
2 689
Ir < I
TED300014EN_030_037.
Gamme
Schneider Electric
Design rules
Busbar calculation
0.24 20 I th 2 t k
cc = ----------------------------------------------------------2
(n S) c
with:
c
10
Ith
tk
31 500
A rms.
in secs
20
cm2
( - n) :
8.9 g/cm3
1.83 cm
C
50
1.83 10
31 500 )
0.24 1.83
( 31500
cc = ----------------------------------------------------------------2
( 22 /10
10 ) 0.091
0.091 .98.9
Calculation of t must be
looked at in more detail because the
required busbars have to withstand
Ir = 2 500 A at most
and not 2 689 A.
cc =
t = n + ( n ) + cc
=
for I =
Schneider Electric
2 689
40
50
94
C
(see calculation in the previous pages)
Gamme
AMTED300014EN_030_03
Design rules
Busbar calculation
( )
2 689
=
2 500
50 =
( ( ) )
50
0.61
0.61
689
( 22 500
)
1
0.61
50 = 1.126
= 44.3 C
5 temperature t of the conductor after short-circuit,
for a rated current Ir = 2 500 A is:
t = n + + cc
=
40
+ 44.3
88.3
C for Ir = 2 500 A
TED300014EN_030_037.
Gamme
Schneider Electric
Design rules
Lets check
the electrodynamic
withstand of the busbars.
Busbar calculation
F1 = 2 l
d
ldyn2 / 10-8
70
cm
18
cm
Idyn :
2.5
F = F1 / H + h
H
with
F
H
:
:
12
cm
cm
giving F = 683
2
0.5
3
1.25
4
1.10
778
5
1,14
daN
Schneider Electric
Gamme
AMTED300014EN_030_03
Design rules
Busbar calculation
12
with
I/v
70
cm
14.45 cm3
70
1
= 482.3
----------------- ---------12
14.45
S
m
daN/cm
cm2
Cu
A5/L
10
0.089
0.027
cm4
0,83
I/v
cm3
1.66
cm4
83.33
I/v
cm3
16.66
cm4
21.66
I/v
cm3
14.45
cm4
166.66
I/v
cm3
33.33
cm4
82.5
I/v
cm3
33
cm4
250
I/v
cm3
50
x
x
x
x
x
x
x
x
x
x
TED300014EN_030_037.
Gamme
Schneider Electric
Design rules
Let us check
that the chosen busbars
do not resonate.
Busbar calculation
frequency of resonance in Hz
modulus of elasticity
for copper =
0.089
daN/cm
70
cm
21.66
cm4
6 21.66
f = 112 1.3
-----------10
------------------- 0.089 70 4
f = 406 Hz
The solution is OK
In conclusion
bars of 10 1 cm
per phase, are suitable for an Ir = 2 500 A and
2
Schneider Electric
Gamme
AMTED300014EN_030_03