Professional Documents
Culture Documents
2012 07 PotM On Site and Online Tests For Power Transformer PDF
2012 07 PotM On Site and Online Tests For Power Transformer PDF
1 Introduction
Nowadays we are facing a growing demand for electrical energy as well as an increasing average age of
power transformers in our distribution networks. Due to the liberalized energy marked, electrical utilities
focuses on low costs. Since power transformers are the most expensive links in the transmission network
they try to postpone investments for replacements of power transformers. This can be done, if critical
defects are observed before a failure happens. New maintenance strategies based on the transformer
condition are introduced, instead using periodical measurements or refurbishments. For such condition
based maintenance of transformers, reliable transformer diagnostics are needed.
0,05
Active component
40
0,04
Unidentified
30
Bushing
20
0,03
10
0
Tap
changer
0,02
Tank
0,01
Secondary
system
Cooling
0
0
10
20
30
40
50
Operating time / a
110 kV
220 kV
380 kV
(b)
(a)
Figure 1: Failure statistics for Germany from [1] showing a decreasing failure frequency for
higher operation times (a) and failure causes (b)
1/7
Figure 1 shows the failure statistics for power transformers in Germany. The risk of a failure is increasing
for ages higher than 30, which is similar or even less than the average transformer age. Causes for such
failures can be found in the bushings, tap changers, the active parts, the tank or in the secondary system
[1], [2]. To test such systems, different routine measurements can be done like the analysis of an oil
sample during service. For most electrical routine test the transformer has to be switched off. To monitor
changes of the transformer condition more closely, online monitoring systems for power transformers
were developed. The following paper discusses different measurement techniques, their applications and
which information can be derived from them.
at
at
at
Ur > 170kV
Ur > 72,5kV
Ur < 72,5kV
Another important factor influencing the oil quality is the moisture. The moisture in oil can significantly
reduce the breakdown voltage. Also the ageing of the cellulosic insulating material inside the transformer
is significantly accelerated in presence of water. The IEC 60422 classifies the oil according to its moisture
saturation:
Dry
< 6%
Moderately wet
7 21%
Wet
21 30%
Very wet
> 30%
More information can be gathered by measuring the dissipation factor at 90C, the interfacial tension or
the neutralization number. Typical values as well as a classification are given in the IEC 60422.
Very often the Dissolved Gas Analysis (DGA) is used for condition monitoring. This test gives information
not only about the oil itself. Discharges or overheating destroys the oil as well as cellulosic insulation
material. The resulting gases become dissolved in oil and are measured. The composition of gases is
characteristically for different failures.
methane
ethylene
acetylene
Figure 2: DGA Interpretation by Duval Triangle with an example for a thermal fault
If the DGA is performed in a laboratory, the analysis is often done by gas chromatographs giving most
detailed information about the gas composition. Onsite usually photo-acoustic spectroscopy is done. For
online DGA, different sensors are available analyzing a reduced number of key gasses like H2, carbonic
gases or atmospheric gases. The interpretation can be done based on different tables or the Duval
Triangle (Figure 2). They all refer to typical chemical products, which were produces for different failures:
2/7
Arcing
In this case hydrogen and acetylene C2H2 is produced.
Some parts of the DGA are still in research stage. For example new online sensors or the influence of
diffusion time and temperature on DGA are investigated. Also the DGA interpretation for ester fluids is a
research topic.
Winding to winding
Windings to tank
Windings to core
Core to tank
Voltage source
=
A
Instrument
Instrument
Usually the insulation between high and low voltage windings contains the main part of the cellulose and
therefore is recommended for the measurement of the dissipation factor. Examples for such measurement
setups are given in Figure 3.
Current sense 1
=
A
Guard
Guard
CHL
LV
CH
CT
HV
Voltage source
Current sense 2
CL
Current sense 1
CLT
LV
(a)
Figure 3: Measurement setup for dissipation factor measurement
(a) at a two winding transformer
(b) at a three winding transformer
3/7
CHL
MV
(b)
HV
Pressboard
Oil
conductivity
Insulation
Geometry
Pressboard
The measurement of the dielectric response helps to determine ageing, moisture in paper and the
conductivity of oil inside a power transformer. The measurement can be performed in time domain (PDC
method) by measuring the polarization and depolarization current or in frequency domain (FDS method)
by measuring the dissipation factor. The measurement setup is the same as for typical dissipation factor
measurements (Figure 3). The analysis usually done in frequency domain.
The dielectric response of oil-paper-insulated power transformers consists of three components: The
dielectric response of the cellulose insulation (paper, pressboard), the dielectric response of the oil and
the interfacial polarization effect. The superposition of these three components follows in a typical sshaped curve for a power transformer (Figure 4).
0.30
0.10
0.03
0.01
DF
0.001
0.010
0.100
1.000
10.000
100.000
f/Hz
4/7
DF
10.00
DF
5.00
1.00
1.00
0.50
0.20
0.10
0.10
0.05
0.02
0.01
0.01
f/Hz
0.001
0.010
0.100
1.000
10.000
100.00
0.001
0.010
0.100
1.000
10.00
100.00
f/Hz
(a)
(b)
Figure 5: Dielectric response for different transformers
(a) Wet and aged transformer at 20C (3% moisture and 10 pS/m oil conductivity)
(b) Hot, wet and aged transformer at 50C (3% moisture and 43 pS/m oil conductivity)
Measurement technique
- UV-Camera
- Acoustic localization
- DGA
- Apparent charges (pC)
- UHF probes
The common way to describe the electrical behavior of partial discharge faults is the equivalent diagram
shown in Figure 6 (a). The dielectric breakdown of a small cavity will cause a current flow that can be
measured as a charge transfer at the outer terminations A and B. Every local breakdown, this means
every partial discharge, can be detected as a short duration charge pulse, the so-called apparent charge
which is shown in Figure 6 (b). Every discharge type has characteristically patterns (current impulses in
relation to the phase of the applied voltage).
5/7
(a)
(b)
Figure 6: Partial discharges occurring at a cavity
(a) equivalent circuit
(b) characteristic voltage and current impulses
The localization of defects can be done in different ways. The characteristic patterns from the
measurement of the electric impulses can be used to distinguish between different partial discharge types.
The type itself give information, whether the discharges appear at surfaces or inside a dielectric. Further
localization can be done e.g. with an acoustic measurement. In case of a transformer, acoustic sensors
are placed on the transformer tank. Due to the different delay time of the recognized acoustic impulses,
the place of the discharge can be calculated.
Figure 7: Separation of PD and Corona Sources at Different Locations with 3PARD (Three
Phase Amplitude Relation Diagram)
Another possibility is a simultaneous measurement of electric impulses in all three phases. For every
measured impulse a vectorially addition of the three phases is done and the impulse is marked in a
diagram like Figure 7. Measurements over some seconds deliver a cluster of enhanced activity for every
defect. A defect in L1 causes high impulses measured in L1, whereas the measured impulses in L2 and
L3 are rather low. The addition gives a cluster near to L1 (cluster 1 in Figure 7).The same is valid for L2
(cluster 2, 4 and 5) and L3 (cluster 3). External noise cause similar impulses in all three phases. The
vectorially addition causes a cluster in the center of a diagram (cluster 6). This method can therefore help
to recognize external noise, which is the main problem for partial discharge measurements.
6/7
Cooling system
- cooler operation
- cooling medium temperature
- cooler inlet and outlet oil temperature
Tap changer
- tap position
- active power consumption of motor drive
- diverter switch/selector compartment oil temperature
- main tank temperature near tap changer
- diverter oil level and condition
Bushing
5 Conclusion
The establishment of condition based maintenance strategies lead to a high demand of reliable diagnostic
measurements. Routine tests can result in contradictionary findings. Advanced diagnostics can help to
further investigate the condition of a transformer. Two of them, the dielectric response measurement and
the partial discharge measurement are discussed in detail. Furthermore online monitoring is regarded as
a useful tool for observing changes of transformer values in time, enabling a fast reaction time in case of a
defect.
6 Literature
[1] M. Gernandt: Auswertung von Strungen und Gas-in-lanalysen bei HochspannungsTransformatoren, ETG Fachbericht 104, Kassel 2006
[2] Cigre SC 12 WG 12.05 Electra, No.88, 1983
[3] I. Hhlein, A. J. Kachler, S. Tenbolen, M. Stach, T.Leibfried: "Transformer Life Management
German Experience with Condition Assessment"; Contribution for Cigr SC12/A2 Merida
Kolloquium, June 2-4 2003
[4] IEC60422 " Mineral insulating oils in electrical equipment Supervision and maintenance
guidance"; International Electrotechnical Commission; Geneva, Switzerland October 2005
7/7
Americas
OMICRON electronics Corp. USA
3550 Willowbend Blvd,
Houston, TX 77054, USA
Phone: +1 713 830-4660
+1 800-OMICRON
Fax:
+1 713 830-4661
info@omicronusa.com
OMICRON
Asia-Pacific
OMICRON electronics Asia Limited
Suite 2006, 20/F, Tower 2
The Gateway, Harbour City
Kowloon, Hong Kong S.A.R.
Phone: +852 3767 5500
Fax:
+852 3767 5400
info@asia.omicron.at
www.omicron.at www.omicronusa.com