Professional Documents
Culture Documents
Chapter-3: Modeling and Analysis of Line Commutated Converter HVDC System
Chapter-3: Modeling and Analysis of Line Commutated Converter HVDC System
Chapter-3
MODELING AND ANALYSIS OF LINE
COMMUTATED CONVERTER HVDC SYSTEM
3.1
INTRODUCTION
The strength of the AC system at the location of the converter
67
In former a thyristor and in later an IGBT is used. In this work,
conventional systems are considered. The HVDC transmission consists of
two converter stations, which are connected to each other by a
transmission link consisting of an overhead line/or a cable. The main
components of an HVDC station comprising of :
Two series connected six pulse converters consisting of valves
shown
in
Fig
3.2a
and
converter
transformers
shown
in
68
between a positive and negative value depends on the following
properties of the valve. The valve conducts current in only one direction
i.e., the forward direction, from the anode to cathode. Valve blocks the
current in the opposite direction, i.e., if a voltage is applied across the
valve with cathode positive relative to the anode the valve will take up the
voltage and will block the current. This voltage is called reverse blocking
voltage. The valve starts to conduct current in forward direction provided
the following two conditions are satisfied.
The voltage in the forward direction across a valve is positive.
Control pulse is sent to the valve.
Once the valve started to conduct current the magnitude of the current is
determined solely by the main circuits outside the valve. The flow of
current through the valve continues until it decreases by external
influence and tries to pass zero, a negative voltage appears across the
valve and the current through the valve is extinguished. In forward
direction the valve with forward voltage comes into conduction state until
a control pulse is applied to the gate. This voltage is forward blocking
voltage. During each cycle of the alternating voltage the valve under go
the following states of operation.
Forward blocking interval
Conduction interval
Reverse blocking interval.
69
The following assumptions are made during the analysis
An infinite three-phase AC source connected to the converter
transformer with finite leakage inductance (L).
Fig3.2c: AC Filters
70
Valves are ideal
Infinite smoothing reactor
Ripple free current at the output of the bridge
Equal firing interval.
71
(3.2.1)
72
During commutation, three valves are in conducting state. Such a period
is called overlapping period.
Variation of output dc voltage shown in Fig.3.2.1d in relation to firing
angle
Vd = Vdocos 3XcId/
(3.2.2)
(3.2.3)
(3.2.4)
73
described above, but it also can be operated as an inverter with firing
angle increased between 90 to 180.
Expression for the inverter in terms of extinction angle
=
represents overlap angle
Vd = Vdo cos - 3XcId/
(3.2.5)
If the inverter is
74
The control models for both the rectifier and inverter are based
essentially on proportional and integral function blocks. While the
rectifier controls consist only of a current control loop, and the inverter
controls contains both current control and gamma control loop. Voltage
dependent current limits are included in the controls, otherwise during
disturbances, the AC voltage at the rectifier or inverter is depressed and
it will not be helpful to a weak AC system. The voltage dependent current
order limiter (VDCOL) is implemented shown in Fig.3.3 by monitoring the
inverter side DC voltage, and compounding it using the measured
current to that at the mid-point of the cable.
75
and the AC side resonance near second harmonic makes the benchmark
system particularly onerous for DC and control operation.
basic
AC/DC
interaction
phenomenon
is
related
to
76
disturbance, fast recovery of power may cause voltage instability if the
inverter ac system is weaker; effects subsequent commutation failures.
In particularly, low SCR system requires slow recovery of power to ensure
the AC system voltage maintained at satisfactory level.
Recovery time: It is defined as the time from fault clearing to the instant
90% of the pre-fault power is restored.
The design and performance of an HVDC system has significant
impact on the relative strength of AC system to which it is connected.
The behavior of the DC system is a function of the thevenin impedance of
the connected AC system [56]. If the impedance is small, there is very
little variation in the AC bus bar voltage and consequently the converter
operates with less risk of commutation failure and is subject to less
overvoltage stress as the DC load changes. Also, the larger the
impedance the more the likelihood of harmonic resonances which can
have disastrous effects on the converters operation.
The Short Circuit Ratio and Effective Short Circuit Ratio, are the
important indices for characterizing the degree of expected operational
problems in a dc transmission scheme[3]. The relative strength of the ac
system is often parameterized by an index called the Short Circuit Ratio
77
weaker the system higher the impedance. Theshunt capacitors including
ac filters connected at ac terminal of dc link can increase the effective ac
system impedance
For the circuit shown in Fig.3.4 the Short Circuit Ratio is given as
SCR
= /Pdc .
Zs = Thevenin impedance
Pdc = DC Power
V1 = Rated line Voltage
78
The SCR is a complex number which is inversly proportional to
Zs.However,as Zs is highly inductive the SCR is almost imaginary.Hence
the phase of the SCR is ignored and only its magnitude is refered.As a
thumb rule, a system is classified weak or strong according to ESCR
value as shown in Fig.3.5
Short Circuit(SC) MVA =
SCR
(3.1)
ESCR =
1.5
Very
Weak
System
(3.2)
2.5
Weak
system
5.0
Strong
system
ESCR
Very
strong
System
79
in1985, which was later adopted by CIGRE SC-14 to carry out analysis
and studies on the DC control aspects, aiming at the improvement of
information exchange on system simulation. This benchmark model
developed by CIGRE study group 14.02[62] (The Conseil International
des Grands Reseaux Electriques) is an international association based
in France. Both manufacturers and users from all over the world have
been using this benchmark model for testing and evaluating the
performance of the system under study. The main circuit values
proposed are arbitrary and do not represent any particular HVDC
scheme. The test system is particularly selected to have an operationally
difficult configuration. The original CIGRE benchmark model [61] is a 12
pulse bipolar system. Benchmark model of a mono polar two terminal
HVDC transmission system as shown in Fig 3.7 which has been
developed by CIGRE [62], considered for the study.
80
The model has been elaborated for comparative studies of different
HVDC control schemes. All the parameters of the system are in detailed
including component values, ratings, operation conditions for converters,
and steady state conditions.
The CIGRE benchmark system consists of a 500 kV,1000 MW DC
link, which connects two 345 kV and 230 kV AC systems as shown in
Fig.3.7. Each AC system has a preset Short Circuit Ratio (SCR), which
represents the degree of strength of the system. Their values in the
rectifier side (345 kV) and in the inverter side (230 kV) are respectively:
2.5pu/84 and 2.5pu/75. The model also considers AC filters of the
dampedarm type and capacitor banks for reactive power compensation.
The DC transmission line is considered as a long cable system and hence
is represented by a Tsection model with high shunt capacitance and low
series
inductance.
Modeling
of
CIGRE
Bench
mark
model
in
model
of
mono
polar
two
terminal
HVDC
EMTDC
solution
engine
[63].
Typical
PSCAD/EMTDC
81
applications include control system design and coordination of FACTS
and HVDC and optimal design of controller parameters among many
others. This platform supports linear and nonlinear systems modeled in
continuous time, sampled time, or a hybrid of the two.
Several basic components of electrical networks can be found
already modeled in the extensive library supported by PSCAD/EMTDC. A
brief description of those components used in this work are presented
below.
82
the fault current through the valves. In this simulation no tap changer is
considered because only transient phenomena is concerned. Fig3.8.1
depicts the complete configuration of the rectifier converter. Design
procedure of the converter transformer are provided in the Appendix-B.
3.8.2 DC System
DC system consists of DC cables, DC filters and smoothing
reactors. In this simulation DC line is modeled using an equivalent T
network shown in Fig.3.8.2.
83
Fig.3.8.2: DC Line
This model is based on Bergons travelling wave method used by
EMTP.DC Filters are used to eliminate the higher order harmonics which
may cause interference with nearby voice frequency communication
circuits. For an HVDC system using a cable as a transmission link, this
interference problem will not arise. Hence DC filters are not used in the
simulation with a cable.
84
Fig3.8.3: AC System Representation
This component models a 3-phase AC voltage source, with
specified
source
or
zero-sequence
impedance. A
zero-sequence
85
Fig.3.8.5: AC Filter
86
The 12 pulse converter system generates characteristics of the
order 11th, 13th, 23rd, 25th, 35th, 37th and so on. In this simulation
passive tuned shunt R-L-C are used for removing lower order harmonics
(11th and 13th).A high pass filter is used for higher order harmonics.
Shunt capacitors: These filters generate fixed amount of reactive power
at the fundamental frequency. The reactive power requirement of the
converters varies with the load. Passive shunt filters are used to supply
reactive power of 50-60% of the total active power. In this simulation,
capacitor banks are represented by fixed capacitors.
87
88
89
90
maximum rectifier firing angle is 17.15,inverter firing angle 141.6and
gamma angle 15 are observed.
SYSTEM
FOR
91
Fig.3.10.1a to 3.10.1j. Due to the fault ,the AC voltage of the inverter bus
reduces as shown in Fig 3.10.1a and
92
currents. To prevent the transient instability in synchronous machines
and energy loss these faults should be recovered as fast as possible.
93
94
95
2.00
Valve Currentyy
Valve CurrentYY&YDR
1.50
1.00
0.50
0.00
-0.50
-1.00
-1.50
-2.00
Time(s)
0.975
1.000
1.025
1.050
1.075
1.100
1.125
1.150
1.175
1.200
3.10.2:
...
...
...
96
phase) reduces to zero shown in Fig 3.10.2f. Since,thyristor is a
unidirectional device DC current shown in Fig 3.10.2h goes to zero
immediately. Rectifier DC voltage in Fig.3.10.2g and DC current in
Fig3.10.2h also reduces. No power is transferred until the fault is
cleared. Rectifier current controller attempts to increase the DC voltage
by reducing the firing angle of the rectifier shown in Fig 3.10.2i. Inverter
takes control of current and therefore inverter gamma increases. With
the fault at one phase of the rectifier bus results unbalance in the other
phase voltages shown in Fig 3.10.2j cause to generate second harmonic
oscillations in DC voltages and DC currents shown in Fig3.10.2g & Fig
3.10.2h. Due to this, oscillations appear in rectifier firing angle shown in
Fig 3.10.2i and inverter angle shown in Fig3.10.2d. When the fault is
cleared after 5 cycles, due to sudden increase in the rectifier AC bus
voltage shown in Fig3.10.2f, the DC voltage and DC current represented
in Fig3.10.2g & Fig3.10.2h increases. Current controller at rectifier
attempts to reduce the current by increasing its firing angle. During the
post fault period distortion appears in AC voltages of rectifier shown in
Fig 3.10.2f and inverter in Fig 3.10.2a. The recovery slows down due to
occurrence of single commutation failure at the inverter.
97
98
99
100
101
102
103
: Graphs
Fig3.10.3h: DC Current at the Rectifier
Rectifier
During Remote Single Line
Alpha OrderFault(LG) on the AC Side of the Inverter.
to
Ground
100
90
80
70
AO R
60
50
40
30
20
10
0
Time(s)
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
...
...
...
104
3.10.4
105
AC voltage shown in Fig 3.10.4f is distorted and over voltages up to
1.35pu appear on them. During the faulted period, the DC voltage in Fig
3.10.4g oscillates about zero value. After the fault is cleared the rectifier
DC voltage transiently reverses due to commutation failure at inverter.
The rectifier DC voltage and DC current in Fig 3.10.4g & Fig 3.10.4h
oscillate and reaches to pre-fault value in about 12 cycles after the fault
is cleared.
106
107
108
109
3.10.4c & Fig3.10.4h which are almost equal in magnitude to the initial
fault current levels. Normal operation is resumed at around 1.4s which is
almost 240ms after the clearance of the fault. As the damping is not
provided for rise in current order for rectifier it reduces the firing angle
shown in Fig.3.10.4i without allowing the voltage to rise. This cause
commutation failures and delay in the restoration process. Due to
commutation failure, the DC link voltage reduces causing
an abrupt
110
determined by the VDCL. When the fault is cleared, rectifier controls DC
current and inverter resumes extinction angle control. During
the
faulted period over voltages are observed on the AC voltage of the rectifier
bus shown in Fig.3.10.5f is approximately 1.24pu and at the inverter
shown in Fig 3.10.5a is 1.1pu. When the fault is cleared at t=1.1s the
increase in AC voltage shown in Fig 3.10.5a momentarily increases the
DC voltage shown in Fig.3.10.5b, and decreases the DC current
presented in Fig.3.10.5c.
111
112
113
114
3.10.6
The
The fault is applied for 5 cycles. When the fault is applied at DC line side
of inverter, it causes the DC voltage to collapse to Zero and DC current to
rises to 1.6 pu at rectifier shown in Fig 3.10.6g & Fig 3.10.6h. HVDC
control systems plays an important role in clearing the fault. A force
retard function sense the DC fault and operates the rectifier as inverter.
The order of the rectifier forces to high value shown in Fig 3.10.6f and
operates in inverter mode. At the same time the alpha angle order at the
inverter as shown in Fig3.10.6d is 88,i.e., inverter acts as rectifier. DC
line voltage becomes negative as shown in Fig 3.10.6b and energy stored
in line is returned to AC network causing rapid extinction of fault current
at next zero crossing. When is released DC voltage and DC current
recover approximately in 500 ms when fault is cleared. The smoothing
reactor and DC line impedance limits these peak values. The alpha order
at the rectifier reacts to short circuit and increases from its pre-fault
value to maximum value to reduce the fault current. It is also observed
that since the rectifier is connected to a weak system a commutation
failure occurred at the rectifier indicated with rise in DC Current shown
in Fig 3.10.6h and fall in DC Voltage shown in Fig3.10.6g. The dc power
transfer is Zero at the inverter as DC Voltage and DC Current shown in
Fig3.10.6b and Fig3.10.6c is zero at the instant of fault period.
115
116
Inverter : Graphs
180
Alpha Order
160
140
AO I
120
100
80
60
40
Time(s)
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
...
...
...
117
118
one or more commutation failures. The system however recovers after the
fault is cleared.
During normal operation rectifier is under Constant current mode
and inverter is at Constant extinction angle mode. During faults, when
the AC current decreases below the current reference of the inverter, the
inverter takes control of current .After fault is cleared constant current is
transferred back to rectifier.
3.12 SUMMARY
In this chapter an HVDC system based on the CIGRE Benchmark
model is presented. Description of various subsystems such as AC
system, AC/DC filters, Converters, Converter transformers, DC cables
and control strategies representing both rectifier and inverter are
presented.
Modeling
of
each
subsystem
is
performed
using
inverter.
of the inverter.
119
The AC bus voltage ,DC Voltage ,DC current, Angle order and Valve
currents have been recorded at both the inverter and rectifier side. The
results for the performance analysis of HVDC line commutated converter
with low short circuit ratio(SCR=2.5) for both at inverter side and rectifier
side) have been presented.
From the analysis of the simulation results it is observed that
HVDC systems when connected to weak AC systems it is subjected to
high magnitude of AC voltage oscillations, recovery from disturbances,
AC voltage fluctuations are highly undesirable causing harm to AC
equipment, and thus maintain poor quality of power, whereas on DC side
the probability of commutation failure increases. High magnitude of AC
voltage oscillations is a consequence for high magnitude of AC
impedance, causing small current perturbations leading large voltage
deviations. Results presented demonstrate the controller performance in
recovery of HVDC links from various disturbances.