INTRODUCTION
Crompton Greaves Ltd. is one of the leading manufacturers of SF6 Gas Circuit Breakers in the world having a range
extending from 6.6 kV to 420 kV.
More than 9000 Crompton Greaves SF6 Gas Circuit Breakers upto 420 kV for outdoor application have been put into service
in various environments in many countries since 1983 where they are operating satisfactorily.
Our manufacturing and quality systems adhere to the requirements of the quality standards and scope of ISO 9001.
FEATURES
FIG. 1(a)
FIG. 1
INTERRUPTING UNIT
STATIONARY
ARC CONTACT
STATIONARY CONTACT
NOZZLE
MOVING CONTACT
ARC
STATIONARY
CONTACT
SF6 GAS
SUPPORTING
PORCELAIN
STATIONARY
ARCING CONTACT
INSULATING ROD
SF6 GAS
MOVING ARCING
CONTACT
NOZZLE
MOVING
CONTACT
OPERATING ROD
PUFFER
CYLINDER
LINK
LEVER
OPERATING
MECHANISM
HOUSING
FIXED FINGER
CONTACT
ROD
CONTROL VALVE
PISTON
AIR RESERVOIR
OPERATING
MECHANISM
COMPRESSED AIR
(15 kg/cm2)
PISTON
INTERRUPTING PRINCIPLE
CYLINDER
CLOSING SPRING
COMPRESSED AIR
SUPPLY UNIT
SHOCK ABSORBER
FIG. 2
INTERRUPTING
UNIT
STATIONARY
ARC CONTACT
MOVING ARC
CONTACT
STATIONARY
CONTACT
MOVING CONTACT
SF6 GAS
INSULATING ROD
LINK (1)
OPERATING ROD
ROD (3)
LINK (2)
LINK (3)
ROD (2)
LINK (4)
LEVER (4)
LEVER (3)
LEVER (1)
ROD (1)
CONTROL
VALVE
OPERATING
MECHANISM
AIR
RESERVOIR
PISTON
CYLINDER
COMPRESSED
AIR (15 kg/cm2)
CLOSING SPRING
SHOCK ABSORBER
COMPRESSED AIR
SUPPLY UNIT
SUPPORTING
FRAME
STATIONARY
CONTACT
CAM
MOVING CONTACT
LEVER
EXHAUST
PORT
PIN "A"
TRIGGER
ROLLER
PLUNGER
PLUNGER
SPRING A
CLOSING COIL
TRIP COIL
ANTI-PUMPING
LEVER
TRIGGER
EXHAUST
PORT
LATCH
CYLINDRICAL
VALVE
AIR RESERVOIR
PISTON
ROD
ANTI-PUMPING
PIN
CONTROL
COMPRESSRD
VALVE
AIR (15 kg/cm2)
PISTON
COMPRESSED
AIR (15 kg/cm2)
CYLINDER
PISTON
PISTON ROD
SHOCK
ABSORBER
CLOSING
SPRING
SHOCK ABSORBER
CLOSED POSITION
AIR RESERVOIR
CYLINDER
VALVE SEAT
CLOSING
SPRING
COMPRESSED
AIR (15 kg/cm2-g)
HOLDING LATCH
OPENING STAGE
OPEN POSITION
FIG. 4
SF6 GAS
GAS FEED
PORT
GAS PIPING
No. B
No. C
INTERRUPTING UNIT
No. A
No. D
AIR PRESSURE GAUGE
AIR PRESSURE SWITCH
(FOR ALARM AND LOCK)
GAS PRESSURE
GAUGE
GAS TEMPERATURE
COMPENSATED
PRESSURE SWITCH
63G
63AL 63AG
OPERATING
MECHANISM
HOUSING
AIR PIPING
CONTROL VALVE
OPERATING
MECHANISM
COMPRESSED
AIR (15kg/cm2)
COMPRESSED AIR
SUPPLY UNIT
DRAIN VALVE
SAFETY VALVE
CHECK VALVE
ROUTINE TESTING
All routine tests as specified in IEC 56 are conducted on the fully assembled breakers at our factory. In addition to the specified tests
as per IEC, the following additional tests are done on each breaker.
1) Gas leakage test.
2) Air leakage test.
3) Speed and timing test.
4) Pneumatic system test.
5) Air & Gas pressure switches test.
CGL testing laboratory is fully equipped with the latest testing equipment like
1) 600 kV Test Transformer - Programmable Logic Control MUR 24A.
2) High precision mass spectometer type leak detector (with capability todetect leaks as low as 1 ppm).
3) Multichannel breaker Speed / Time analysers.
4) Millivolt drop test set.
5) Primary injection test set.
Typically, a fully assembled breaker is tested in 4 hours. Full testing before despatch of breaker ensures trouble free operation at
site and complete customer satisfaction.
:
:
:
UNITS
kV
kVp
kV
160
230
275
325
460
520 / 610
:
:
:
:
:
:
mm
A
Hz
1820
3075
3625
3625
4250
IEC 56, BSS 5311 & JEC 181
SPRING - PNEUMATIC
3150
O-0.3 sec-CO-3 min-CO
50/60
6125
10500
sec.
110/220 V DC
6 A max. at 110 V DC
:
:
ms
ms
100
kA
31.5
40
31.5
40
kAp
80
100
80
100
A / pu
10 / <2.5
50 / <2.5
63 / <2.5
A / pu
250 / <2.5
160 / <2.5
A / pu
250 / <2.5
kA
:
:
: Kg/cm2
: Kg/cm2
: Kg/cm2
72.5 kV
123 kV
145 kV
145 kV
170 kV
245 kV
420 kV
70-SFM-32A 120-SFM-32A 120-SFM-32A 120-SFM-40A 150-SFM-32A 200-SFM-40A 400-SFM-40A
72.5
123
145
145
170
245
420
325
550
650
650
750
1050
1425
275
3
220 V DC
3 A max. at
220 V DC
40
150
60
120
300 / <2.5
7.9
10
100
7.9
10
1.5
9 NO + 9 NC8 NO + 8 NC / POLE
5.0
4.5
4.0
6.0
5.5
5.0
6.0
5.5
5.0
7.0
6.5
6.0
1700/2000 1700/2000
3365
4003
4738
5376
2000
4003
5376
2000
4003
5536
:
:
:
:
mm
mm
mm
mm
1400
3065
4118
:
:
kg
kg
1650
2000
2000
2200
2000
UNITS
mm / kV
72.5 kV
25
123 kV
25,31,35,
40,45
145 kV
25,31,35,
40,45
145 kV
25,31,35
170 kV
25,31,38
1.3
6.0
5.5
5.0
4600
4605
6965
6000
8360*
8760*
3900
7950
9600
* WITH SUPPORT STRUCTURE
OPTIONALS
1. CREEPAGE DISTANCE
2. CLOSING / TRIPPING COIL VOLTAGE
3. PRESSURE RELIEF DEVICE & AUTO
DRAIN VALVE FOR AIR RESERVOIR
4. CLEARANCE OF LIVE PARTS TO
GROUND
5. MAX. ALTITUDE ABOVE SEA LEVEL
6. AUXILLIARY CONTACTS
7. SEISMIC ACCELERATION
V (DC)
110/125/220
CAN BE PROVIDED
m
g
1700
2500
2500
15 NO5 & 15 NC
0.3/0.5
1000
245 kV
25,31,37
420 kV
25
2400
1000
15 NO + 15 NC / POLE
0.3
3500
72.5 kV breaker
1220
250
520
80
Dimensional Details
350
500
1000
300
A
50
50
500
40
SUGGESTED TRENCH
FOR CABLE ENTRY
300
540
1400
350
1400
C.L.
G.L.
PHASE A
123/145 kV breaker
PHASE C
4100
1220
50
80
50
500
40
SUGGESTED TRENCH
FOR CABLE ENTRY
250
520
300
1000
500
350
540
700
300
PHASE B
350
*300
2200
1700
1700
PHASE A
PHASE B
C.L.
G.L.
PHASE C
2
4700
500
50
300
540
500
40
SUGGESTED TRENCH
FOR CABLE ENTRY
520
300
1000
800
50
80
500
2200
2000
350
2000
5320
PHASE B
245 kV breaker
490 700
520
= =
150
300
70
1450
7000
1450
800
580
200
=
300
1000
1325
1325
1450
1450
1450
AIR
PIPE
1325
7000
15870
PHASE-B
PHASE-C
40 40 40
150
44.5
CONDUCTOR
SIDE
M24-ANCHOR BOLT
16
72.5 to 170 kV
44.5
18 4 HOLES
72.5 to 245 kV
BREAKER
SIDE
14 4
HOLES
CONNECTOR
SIDE
44.5 60
140
420 kV
160
90
36
26
40 50 40
170
400
400
100
245 kV
4NOS.,M24 BOLTS
100
420 kV
100
730
250
1450
1325
PHASE-A
55
400
400
200
630
= =
= = 430
300
820
200
80
630
25
80
150
20
3x4 M30 ANCHOR BOLTS
100
50
CONDUIT
ENTRANCE
M30
ANCHOR
BOLT
100
1600
4. Air Reservoir
5. Frame (For Gang Operated Breakers)
6. Closing Resistor (420 kV Breaker)
7. Grading Capacitor (420 kV Breaker)
PHASE'C'
420 kV breaker
1600
630
KEY
1. Interrupter
2. Supporting Porcelain
3. Operating Mechanism Housing
PHASE'B'
730
800
==
1400
525
250
CABLE
TRENCH
C.L.
G.L.
200
4500
PHASE 'A'
800
1000
580
10270
2230
1500
1000
80
4500
925 250
165
540
1
7
= =
CONDUCTOR
180
80
250
50
PHASE C
1000
PHASE A
C.L.
G.L.
44.5
300
250
1220
*300
BREAKER
SIDE
Power Systems
A Business Unit of Crompton Greaves Ltd.
SF6 Switchgear Divn.
Switchgear Complex
A-3, MIDC, Ambad, Nashik - 422 010 India
Tel:
(+91) 253 382271 Ext 107/108/110
Fax:
(+91) 253 382219/381247
E-mail: exports@cglmail.com (Exports)
mktg@cglmail.com (General)
URL: www.cgswgear.com
Regd. Office : 6th Floor, CG House, Dr. Annie Besant Road, Prabhadevi, Mumbai - 400 025, India.
CG-S&C/EXP/Cat.No.SF6-105/3/01/2000
Data subject to change