Design calculation sheet

Project no:

PEARL QATAR Facility Mgt(Q07048)

Subject:

AIR HANDLING UNIT - PRESSURE DROP

Date:27/12/2007

Sheet no.:

of

1 Computed by:

A.B

Checked by:

N.E

Approved by:

INTERNAL STATIC
PRESSURE. AIR
SIDE (in Pa)

Column number

Tag number

WH-AHU-02

WH-AHU-01

System served

Ware House

Ware House

Location

Ware House

Ware House

Floor Served

First

Ground

Accessories Static

50.000

1.432

Cooling Coil

50.000

1.036

Sub total ( Internal)

100.000

2.468

Supply Duct work


Duct Run (m)

44.000

80

Friction Pa\m

20.000

0.065

Return Duct work

EXTERNAL STATIC
PRESSURE. AIR
SIDE (in Pa)

TOTAL AIR SIDE


Summary

NOTE:

Duct Run (m)

25.000

65

Friction Pa\m

20.000

0.099

Duct Work

1380.000

0.171

Fittings 15%

207.000

0.026

Volume Damper

25.000

0.100

Duct Heater (if any)

0.000

0.000

Fire Damper

25.000

0.100

Terminal Box (if any)

75.000

0.000

Air Outlet

25.000

0.100

Fresh Air Louver (if any)

0.000

0.000

30% Safety

483.600

0.089

Sub total ( External)

2220.600

0.585

TOTAL + 10% safety

2552.660

3.358

EXTERNAL (pa)

2220.600

146

TOTAL (pa)

2553

836

Accessories Static consists of:1-Flat filter


2-Bag filter 3-Mixing Box Section 4-Fan
Section

3.5KW-94%

11.6KW-77.4%