Project:- Square one TD Entrance Renovation

Air Quantity Calculation for new fan


1. Considering max pressurization of 5 Pascal
Q= 2610 x A x (dP)
A= leakage area Sqft
dP= Differential Pressure 10 Pa
Q= Airflow CFM
considering 0.2" gap for leakage around the perimeter of doors (9 ft high and total length of 21ftx 2)
A=
1.6728 Sqft
Q=
620 CFM
2. Considering Velocity across doors leakage area
Q=A x V
V = 350 fpm
A=
Q=

1.6728 Sqft
590 Cfm

Hence Considering AirFlow of 620 CFM

New Coil Sizing


Q = 1.08 x CFM x dT
Q=
Required GPM

Considering dT as (110-60)
33.48 MBH
3.348

Maxium Coil Draw


Old Coil Data
Q =65 MBH, water side dT= 20 F, Flow = 6.5 Gpm, Pipe size= 1 1/4", air side dT = 30 F

Maximum Flow we get from 1 1/4 pie is 12 USGPM with velocity @2.57 fps and friction factor as 4.35 f
Hence we can draw almost 6 usgpm from the existing pipe
Maximum Coil size with 6 GPM flow @ dT = 20F
Q=500 x GPM x dT
Max Q=
60 MBH
Max GPM=
6 USGPM

however considering the pressurization and air flow limit, and supply air temp limit we can
Q = 33.48 MBH of heat supply with water flow rate at 3.348 USGPM and dT

and total length of 21ftx 2)

ide dT = 30 F

s and friction factor as 4.35 ft of wc/100 ft of pipe

pply air temp limit we can only provide


e at 3.348 USGPM and dT = 50 F (110-60)