You are on page 1of 1

EACH LUMINAIRE TO HAVE

ITS OWN ELECTRIC SERVICE


BROUGHT DOWN TO HANDHOLE

50

#12-2 W/GRD AWG


TYPE UF, SOLID CU
1 EACH PER LUMINAIRE

50 STEEL POLE 2-PIECE


TAPERED ROUND POLE
KIM PTRS50-11188 C/DB-P

HANDHOLE FOR WIRING ACCESS.


CONDUCTOR TAILS TO EXTEND
18" FROM HANDHOLE. IN-LINE
FUSES TO BE INSTALLED ON
EACH CONDUCTOR.

GROUND TO CONNECT TO
GROUND BOSS IN POLE

LUMINAIRE KIM LIGHTING


TYPE 4C or 2C/VLA29W5/
1000HPS/480 VOLT/DB-P.
LUMINAIRE TOPS TO BE
MOUNTED LEVEL.
CABLE GRIPS
1 EACH PER CABLE
OWNER FURNISHED LUMINAIRES, POLE,
BASE COVER, ANCHOR BOLTS, AND 1000W HPS
LAMPS, CONTRACTOR SHALL PROVIDE CONCRETE
BASE, CONDUIT, CABLES, GROUND ROD,
ASSEMBLE, SET AND WIRE POLE,
AND GROUT BASE

NOTE: POLE SHALL BE VISUALLY TRUE


& VERTICAL. FOUNDATION SHALL BE
PLUMB & TRUE ON ALL SIDES.

ISU ID# PLACED UNDER EACH


LUMINAIRE. ISU SUPPLIED,
CONTRACTOR INSTALLED.

GROUT. PROVIDE CHANNEL THROUGH THE


GROUT FOR LIQUID DRAINAGE FROM POLE
INTERIOR

1" CHAMFER

6 - #6 BARS EQUAL
SPACING. 2" CLEARANCE
FROM ANY SURFACE

3
"
4

PVC SCH 40 CONDUIT


FOR GROUND CABLE
#6 AWG B.C.

36"

BOND GROUND
CONDUCTOR
TO REBAR

#3 TIES AT 12"

95% STANDARD COMPACT


FILL AS REQUIRED

8-0"

CONNECT WITH CADWELD


OR BURNDY TYPE YGHPC
HYTAP CONNECTION

GRADE

GROUND ROD
5
" x 10-0"
8
4000 PSI CONCRETE
FOOTING 24" DIAMETER

2" SCH 40 PVC CONDUITS


AS REQUIRED.
INSTALL 1 EA. EXTRA FOR
FUTURE USE. CAP CONDUIT
UNDERGROUND.

TYPICAL 50 FT LIGHT POLE FOUNDATION & POLE


SCALE: NONE

DATE: 1/07