Generator Unit 02 Breakdown Report PDF
Generator Unit 02 Breakdown Report PDF
: 1.6MW
Voltage
: 6.3kV
Type
: SFW16696/1400
Serial No
: 130003
Thomson Electricals visited site on 3rd November 2015 and MBSL insurance Loss
adjuster who Mr.Sugath Weerarathne visited site on 13th of November.
Then management has decided to repair generator unit 02 from Thomson Electricals.
Repairing Methodology
Thomson electricals had decided to replace two damaged winding coil and they used
two spare coils which have supplied with the generator to replace. See appendix 1 for
Thomson report.
V-U=24.22 M
V-E=9.303 M
W-U=24.90 M
W-E=10.65 M
V-W=23.93 M
Then stator winding coil sample of generator unit 02 was tested by Mr.Ajith
Rathnayeke from Fentons. He concluded that coils have poor insulation resistance and
all coils (90 coils) should replace. (See Appendix 2 for Mr.Ajith Rathnayekes report.
Then management has decided to replace all coil and Houghton International in UK
was selected to manufacture coils and supply other necessary accessories. Sample coil
and other accessories sample were sent to Houghton.
While the coil is manufacturing, the generator unit 02 was submitted to The Electrical
Company in Wattla to do the repair.
Winding coil and other accessories were received from Houghton in July 2016.
Repairing Methodology
Please see Appendix 3 for detail method statement of Mr.Alwis who is managing
partner of The Electric Company.
V-U=4.1 G
V-E=2.46 G
W-U=3.5 G
W-E=2.62 G
V-W=4.55 G