You are on page 1of 1

FIRE - Fire Sprinkler Hydraulics Calculation Program

hazem mohamed

Elite Software Development, Inc.


PROJECT TEST Page 2

General Project Data Report


General Data
Project Title:
Designed By:
Code Reference:
Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:

PROJECT TEST
ENG . YASSER FATHY
NFPA 13 , NFPA14

Project File Name:


Date:
Approving Agency:
Phone:
City, State Zip Code:
Representative:
City And State:

PROJECT TEST.fiw
07, 2016
Civil Defense

Building Owner:
Phone at Building:

Project Data
Description Of Hazard:
Design Area Of Water Application:
Default Sprinkler K-Factor:
Inside Hose Stream Allowance:
In Rack Sprinkler Allowance:
Sprinkler Specifications
Make:
Size:

Ordinary 1
1500
5.65
100.00
0.00

ft
K
gpm
gpm

Sprinkler System Type:


Wet
Maximum Area Per Sprinkler:
130 ft
Default Pipe Material:
SCHED 40 WET STEEL
Outside Hose Stream Allowance:
250.00 gpm

Model:
Temperature Rating:

0.5"

160 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID:
Hydrant Elevation:
Test Flow Rate:
Calculated System Flow Rate:
Available Inflow Residual Pressure:

Date Of Test:
0
0.00
280.05
0

ft
gpm
gpm
psi

Static Pressure:
Test Residual Pressure:
Calculated Inflow Residual Pressure:

0.00 psi
0.00 psi
87.99 psi

Calculation Project Data


Calculation Mode:
HMD Minimum Residual Pressure:
Number Of Active Nodes:
Number Of Active Pipes:
Number Of Active Sprinklers:

Active Version 6.0.164

Demand
14.50 psi
17
16
11

Minimum Desired Flow Density:


Number Of Inactive Pipes:
Number Of Inactive Sprinklers:

1000 Pipe Capacity

0.15 gpm/ft
0
0

07 , 2016

You might also like