You are on page 1of 2

FPRA Flexi Power Rectifier

The FPRA is a 6kW output power AC rectifier package made up of three individual 2kW AC/DC power
modules operating in a parallel mode configuration. The FPRA also includes a Power Distribution
Assembly (PDA), which has a fully integrated battery protection LVD, load/battery circuit breakers,
battery current shunt and alarm signals to the BTS EAC interface.
Main features:

Compact 3U high 19inch wide rectifier module


Outdoor IP55 compliant stand alone module
Wide operating temperature & voltage range
Modular construction for future expansion

GENERAL

INPUT

Efficiency
Losses, max
Cooling
Air flow
IP class

AC connection &
nominal voltages

240 (US 1-phase)


230 (Europe 1-phase)
202 (Japan 3-phase delta)
3-phase input supported
max 350VAC overvoltage up to
60 seconds

AC range, full
power
AC range, limited
power

180VAC to 315VAC

Frequency range
Power factor

45Hz to 66Hz
0.95

>91%
<180W
Fan on each rectifier module
Back to Front
IP54 (w/o front/rear covers)
IP55 (with front/rear covers)
Operating ambient -40C to +55C
Storage temperature -45C to +45C
Start up temperature -40C ->
Distribution
5 x 63A (2 for loads, 3 for
batteries)

80VAC to 180VAC

OUPUT
Nominal voltage
DC range
Over voltage
protection

-54VDC 2V
-40VDC to -58.5VDC
-58.5VDC 1V

Ripple & noise


Hold up time
Current

300mV (6kW @ +55C)


20mS
37.6A @ -53.3VDC

MECHANICS (Chassis)

CONTROL AND MONITORING

Height
Width
Depth

Controller
Display
Functions

3U
19 inch
559mm (with front/rear covers)
422mm (w/o front/rear covers)
Weight
~37kg (fully equipped)
~25kg (bare 3U chassis)
Mounting
Vertical/horizontal
MECHANICS (Rectifier module)
Height
100mm
Width
81.8mm
Depth
383.7mm
Weight
~3.9kg

Interface

Integrated in PDA unit


LCD type with buttons
System monitoring
(local/remote)
Parameter setting
Temperature compensation
Float/boost charging
Alarm relay definition
Manual/periodic battery test
RJ45