You are on page 1of 42

CT Theory and Testing

William H. Hardy, PhD


Chief Engineer
10737 Lexington Drive
Knoxville, TN 37932
Phone: (865) 966-5856
1

www.powermetrix.com

Current Transformers (CTs)


CTs allow the
measurement of high
currents at potentially high
voltages.
They come in many shapes
and sizes for different
applications
They are potentially
extremely dangerous.

They can kill you!


2

Current Transformers (CTs)

Current Transformers (CTs)


Basic Theory
Basic formula: Is = Ipy(Np/Ns) = Ip/Ns
Open Circuit Voltage: V = 3.5 Z b I p / N s
Where:
Zb = Burden Impedance
Ip = Primary Current
Ns = Number of Secondary Turns (Ratio to 1)
V = 3.5 10 1000 / 200 = 1320V
5

Tests have shown values


ranging from 500 to 11,000
volts.

CT Accuracy Class/Burden
Most CTs used in North
America are 0.3 (0.3
percent) Class devices.
When an accuracy class
is specified the maximum
burden for which the
device meets the class
accuracy is also
specified.

CT Class 0.3
Metering error shall be less
than 0.3% when the CT is
used at FULL RATED
LOAD and with rated
burden.
Metering error shall be less
than 0.6% when the CT is
used between 10% and
100% of full rated load.
Error is a combination of
amplitude and phase error.

CT Accuracy Burden - Load


No Spec

Meets 0.6 Spec


Meets
Accuracy
Spec

Burden Class 0.3


IEEE C57.13 ACCURACY
0.3% @ BX.X RF 4.0
X CT TEST POINT
C20 METER TEST POINT

0.6% ACCURACY REGION

0.60
0.3% ACCURACY

ACCURACY CLASS

ACTUAL

0.30
0.15

0.15

5%
10%

50%

100%

200

300

400

0.30

0.60

MAXIMUM CONTINUOUS
AMPS (RF=4.0)
NO ACCURACY GUARANTEED
IN FRONT OF THIS LINE

RATING
FACTOR

0.1

1.0

2.0

3.0

4.0

5.0

10

15

20

SECONDARY
CURRENT

.25 1.0
0.5

2.5

Slide Courtesy Kent Jones, GE

Burden Class 0.15


PROPOSED IEEE C57.13.6 ACCURACY
0.15 @ E0.04, 0.15 @ E0.20, 0.15 @ BX.X RF 4.0

0.60

X CT TEST POINT
C20 METER TEST POINT

0.3% ACCURACY REGION

ACCURACY CLASS

0.15% ACCURACY
ACTUAL

0.30
0.15

0.15

5%
10%

50%

100%

200

300

400

0.30
MAXIMUM CONTINUOUS
CURRENT (RF=4.0)

0.60

RATING
FACTOR

NO ACCURACY GUARANTEED
IN FRONT OF THIS LINE

0.1

1.0

2.0

3.0

4.0

5.0

10

15

20

SECONDARY
CURRENT

.25 1.0
0.5

2.5

Slide Courtesy Kent Jones, GE

Burden Class 0.15S


PROPOSED IEEE C57.13.6 ACCURACY
0.15S @ E0.04, 0.15S @ E0.20, 0.15S @ BX.X RF 4.0
X CT TEST POINT
C20 METER TEST POINT

0.60

ACCURACY CLASS

0.15% ACCURACY REGION

0.30

ACTUAL

0.15
5%
0.15

50%

100%

200

300

400

10%

0.30
MAXIMUM CONTINUOUS
CURRENT (RF=4.0)

0.60

RATING
FACTOR

NO ACCURACY GUARANTEED
IN FRONT OF THIS LINE

0.1

1.0

2.0

3.0

4.0

5.0

10

15

20

SECONDARY
CURRENT

.25 1.0
0.5

10

2.5

Slide Courtesy Kent Jones, GE

Errors with Current Transformers

11

Errors with Current Transformers


CTs require a lot of care to insure
accurate metering.
Burden Over burden reduces CT accuracy.
Wiring Faulty or improper wiring reduces
accuracy by increasing burden.
Shunt Failure to remove the safety shunt
will not keep the CT from operating but it will
reduce the readings by 50-80%

12

Errors with Current Transformers


When you see
a CT spec
sheet it will give
you the burden
at which the CT
meets a
specific
accuracy Class

13

Errors with Current Transformers


Many CTs are
only rated at
B0.1 and B0.2

14

#16 wire is 4.5 m/ft


#14 wire is 2.8 m/ft
#12 wire is 1.8 m/ft
#10 wire is 1.1 m/ft
#8 wire is 0.7 m/ft
50 ft of #12 wire is
nearly 100 m

Errors with Instrument Transformers


CT - Shunt
Leaving the shunt in the wrong position
produces wrong readings not no readings.

SHUNT CLOSED
15

SHUNT OPEN

Errors with Instrument Transformers


CT - Polarity
Polarity of the
connection matters.
Wrong polarity
means totally wrong
metering.
When PF0,
reversed polarities
may not be obvious.
16

CT Rating Factor
The MOST Misunderstood Spec

Rating Factor has absolutely nothing


to do with burden.
If a CT has a rating factor of 4 it
means that at 30C it can be used up
to 4X its label current and maintain its
accuracy Class.

17

CT Rating Factor
Rating Factor is a strong
function of temperature.
If a CT has a rating factor
of 4 it means that at 30C
it can be used up to 4X its
label current and maintain
its accuracy Class.
Operating temperature
affects Rating Factor
significantly.
A CT with RF=4 at 30C is
only RF=3 at 55C

18

CT Testing
Three Approaches in use today
Direct RATIO measurement with applied
burden
Most accurate approach tells us exactly what we
want to know
Measures directly the quantity we care about CT
Ratio
Is more complicated to perform.

19

CT Testing
Alternate Approaches
Burden only
A compromise: tells us if circuit is stable under
excess burden
Cant give us the ratio which is what we really care
about.

Admittance Testing
Allows us to look for changes from previous
measurements.
Doesnt directly give ratio
Accuracy typically 5%
20

On Site CT Testing
The meter measures ONLY the voltage and current reaching the
meter terminals.
To verify that the CT is working at the site we have to test the entire
circuit.

21

CT Transformers
Field Verification Full Ratio Measurement

Measure
Here

Measure
Here
22

CT Ratio with Burden Testing


Ratio Testing is the
preferred approach when
we can gain access to the
CT primary.
Various types of probes
can be used for primary
side.
Flex
HV

23

CT Ratio with Burden Testing

24

Secondary
connection is
made through
the test switch
Same
connection that
is used for the
rest of the site
testing.

Ratio Testing with applied burden is the


most accurate and complete approach for
testing at CT in service.

Testing Current Transformers


Ratio vs Applied Burden

CT testing can be done with very high accuracy


Reference CT
measured using
PowerMaster with
752 clamp-on
probes.
Essentially NO
ratio error, phase
shift, or change in
secondary current
versus applied
burden.

25

Testing Current Transformers


Ratio vs Applied Burden

CT testing can be done with very high accuracy


Reference CT
measured using
PowerMaster with
752 clamp-on
probes.
Essentially NO
ratio error, phase
shift, or change in
secondary current
versus applied
burden.

26

Testing Current Transformers


Ratio vs Applied Burden

CT testing can be done with very high accuracy

Reference CT
measured using
PowerMaster with
752 clamp-on
probes.
Essentially NO
ratio error, phase
shift, or change in
secondary current
versus applied
burden.

27

Testing Current Transformers


Ratio vs Applied Burden

CTs installations can be fully verified in the field


Burden Class 0.1
CTs various
issues: too small
gauge wire, bad
connections, high
harmonic content.

28

We can verify that the ratio is correct and constant as burden changes.

Testing Current Transformers


Ratio vs Applied Burden

CTs installations can be fully verified in the field


Burden Class 0.1
CTs various
issues: too small
gauge wire, bad
connections, high
harmonic content.

29

We can verify that the ratio is correct and constant as burden changes.

Testing Current Transformers


Ratio vs Applied Burden

CTs installations can be fully verified in the field

CT Phase C highly harmonic load.

CT Phase C harmonic load removed.

Same CT in BOTH cases.


30

Testing Current Transformers


Ratio vs Applied Burden

CTs installations can be fully verified in the field

These are the waveforms and harmonics


when the CT falied.
31

Testing Current Transformers


Ratio vs Applied Burden

CTs installations can be fully verified in the field

Without the harmonic load this CT passed its test.


32

Testing Current Transformers


Burden Test Only
If we cannot get to the primary side of the CT we can
check that the output is constant as burden changes.

Burden Class 0.2


CTs can look
quite bad but
actually be within
specs.

33

Testing Current Transformers


Burden Test Only
If we cannot get to the primary side of the CT we can
check that the output is constant as burden changes.

Same performance
from Burden Class
0.5 CTs is well out
of specification.

34

CT Accuracy Burden - Load


No Spec

Meets 0.6 Spec


Meets
Accuracy
Spec

35

Testing Current Transformers


Whats Wrong?
Same site as above: What went wrong???

36

Testing Current Transformers


Whats Wrong?
Same site as above: What went wrong???

37

Testing Current Transformers


Whats Wrong?
Same site as above: What went wrong???

38

Testing Current Transformers


Whats Wrong? Power Theft

A simple piece of wire


wrapped around the CT.

39

Testing Current Transformers


Whats Wrong?

Phase A CT reversed.
40

Testing Current Transformers


Whats Wrong?

Phase A & B CTs swapped.


41

PowerMaster

42

You might also like